Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Lake | Status | OPEN | ||||||||
ID | 9700727 | Latitude | 28° 35' 24.569 | ||||||||
Name |
CIRCLE K #2722114 810 N US 27 |
Longitude | 81° 45' 9.3166 | ||||||||
MINNEOLA, FL 34715 | LL Method | DPHO | |||||||||
Contact | IRA LEWIS | LL Status | REVIEWED | ||||||||
Phone | (984) 389-1300 | Status Date | 09/18/2023 | ||||||||
Account Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 01/08/2016 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Placard # / Date | 697980 - 06/29/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 02/21/2020 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 12000 | Unleaded Gas (B) | 06/01/1997 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 06/01/1997 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 6000 | Vehicular Diesel (D) | 06/01/1997 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
GUARANTEE | 04/24/2022 | 08/21/2023 | |||||||||
INSURANCE | 12/01/2020 | 12/01/2021 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2018 | 12/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2017 | 12/01/2018 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2016 | 12/01/2017 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2015 | 12/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 11/01/2014 | 11/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 11/01/2012 | 11/01/2013 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 11/01/2011 | 11/01/2012 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 10/29/2010 | 10/29/2011 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||||||
INSURANCE | 11/01/2009 | 11/01/2010 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||||||
INSURANCE | 11/01/2008 | 11/01/2009 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/11/2006 | 04/13/2006 | IN-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes SENSOR CERT. DONE 2/06, MLLD DONE 10/05, "NO ALARM" NOTED ON VISUALS. | |||||||||||
TCR | 05/26/2005 | 06/07/2005 | IN-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes R/UL STP SUMP ENTRY BOOT REPAIRED. | |||||||||||
TCI | 04/12/2005 | 04/14/2005 | MINOR OUT-OF-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REPAIR RIPPED PIPING ENTRY BOOT IN R/UL STP SUMP. MLLDS TESTED 10/28/04, SENSOR OPERABILITY 2/8/05 (3 INT. 3 SUMPS). | |||||||||||
TCR | 05/20/2004 | 05/26/2004 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes LIQUID REMOVED, SHEAR VALVES SECURED. | |||||||||||
TCI | 04/20/2004 | 04/26/2004 | MINOR OUT-OF-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes MLLD 10/10/03, SENSOR CERT. 4/20/04, REMOVE LIQUID FROM STP SUMPS, WORK ON SHEAR VALVES | |||||||||||
TCI | 04/22/2003 | 05/02/2003 | IN-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes MLLD 10/17/02, SENSOR CERT. 4/22/03. | |||||||||||
TCI | 04/10/2002 | 04/18/2002 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE. MLLD 10/8/01 | |||||||||||
TCI | 03/08/2001 | 03/09/2001 | IN-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE | |||||||||||
TCI | 03/22/2000 | 03/24/2000 | IN-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE | |||||||||||
TCI | 04/23/1999 | 05/13/1999 | IN-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/07/2025 | Satisfied | HALL_DK | Enforcement | |||||||
Enforcement Referral | 06/21/2024 | Accepted | GREGORY_JW_1 | Enforcement | |||||||
Electronic Communication | 02/29/2024 | Satisfied | GREGORY_JW_1 | Compliance Assistance | |||||||
Site Inspection | 07/31/2023 | Minor Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Letter | 07/31/2023 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 07/24/2023 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 03/02/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 03/02/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 01/21/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 01/03/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 09/24/2021 | Minor Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Letter | 09/24/2021 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 09/13/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 06/29/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 06/28/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 03/11/2019 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/11/2019 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 01/02/2019 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 12/16/2016 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/26/2015 | In Compliance | COX_CD_1 | 0/3 | Installation | ||||||
Site Inspection | 02/26/2015 | In Compliance | COX_CD_1 | 0/3 | Closure | ||||||
Letter | 11/21/2014 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 11/20/2014 | Minor Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 11/20/2014 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Document Management | 04/25/2013 | Complete | COX_CD_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 04/25/2013 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Document Management | 04/25/2013 | Complete | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 04/25/2013 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Record Document | 06/07/2012 | Satisfied | ZIMMERMAN_RA_1 | Installation | |||||||
Site Inspection | 05/29/2012 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Closure | ||||||
Site Inspection | 05/25/2012 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Installation | ||||||
Site Inspection | 05/10/2012 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 03/29/2012 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/29/2012 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 04/27/2011 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Record Document | 04/27/2011 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 03/29/2011 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/29/2011 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Document Management | 08/23/2010 | Complete | COX_CD_1 | Discharge | |||||||
Site Inspection | 03/24/2010 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Record Document | 07/02/2009 | Satisfied | COX_CD_1 | Installation | |||||||
Record Document | 06/22/2009 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 06/22/2009 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Letter | 06/22/2009 | Satisfied | COX_CD_1 | Closure | |||||||
Letter | 04/23/2009 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 04/23/2009 | Minor Out of Compliance | COX_CD_1 | 0/3 | Installation | ||||||
Site Inspection | 03/05/2009 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/05/2009 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Record Document | 05/13/2008 | Satisfied | COX_CD_1 | Closure | |||||||
Site Inspection | 04/01/2008 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Meeting | 10/17/2007 | Satisfied | COX_CD_1 | Discharge | |||||||
Letter | 10/05/2007 | Satisfied | COX_CD_1 | Discharge | |||||||
TCAR | 10/05/2007 | Satisfied | COX_CD_1 | Closure | |||||||
Record Document | 06/22/2007 | Satisfied | ZIMMERMAN_RA_1 | QA/QC | |||||||
Site Inspection | 06/22/2007 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Letter | 06/19/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 06/19/2007 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Closure | ||||||
Site Inspection | 06/15/2007 | Minor Out of Compliance | COX_CD_1 | 0/3 | Installation | ||||||
Site Inspection | 06/15/2007 | Minor Out of Compliance | COX_CD_1 | 0/3 | Closure | ||||||
Record Document | 05/25/2007 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 05/22/2007 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
Site Inspection | 04/11/2007 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 04/11/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/09/2007 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
07/31/2023 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Replace the lid cover to protect the tank components. | |||||||
07/31/2023 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Submit proof of the required annual testing of the overfill protection for the regular and premium tanks. | |||||||
07/31/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Repair the STP sump lids to allow access to the sumps for visual inspections. | |||||||
07/31/2023 | 6003 | Minor | 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Update (correct the city name) on the registration. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/21/2007 | COMPLETED | 10 | |||||||||