DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County St. Johns   Status    OPEN
 
ID 9701332   Latitude    29° 59' 11.3876
 
Name CENTER PARK SHELL
120 CENTER PLACE WAY
Longitude    81° 27' 17.5196
  SAINT AUGUSTINE, FL 32092 LL Method    DGPS
 
Contact ABBAS JAFERI   LL Status    REVIEWED
 
Phone (407) 654-4395   Status Date    08/25/2003
 
Account Owner Information
 
Name BOCA GAS COMPANY HOLDINGS 2 LLC
6971 FEDERAL HWY #102
BOCA RATON, FL 33487
Effective Date    01/08/2020
 
Contact ABBAS JAFERI / MASBAH CHOWDHURY
 
Phone (561) 774-8077
 
Email ABBAS@BOCAGAS.COM
  Placard # / Date    697202 - 06/28/2024
Property Owner Information
 
Name BOCA GAS COMPANY HOLDINGS 2 LLC
6971 FEDERAL HWY #102
BOCA RATON, FL 33487
Effective Date    01/08/2020
 
Contact ABBAS JAFERI / MASBAH CHOWDHURY
 
Phone (561) 774-8077
 
Email ABBAS@BOCAGAS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 15000 Unleaded Gas (B) 11/01/1997 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 15000 Unleaded Gas (B) 11/01/1997 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   11/22/2023 11/22/2026 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   11/22/2022 11/22/2023 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   11/22/2021 11/22/2022 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   04/23/2018 04/23/2020 NAUTILUS INSURANCE COMPANY
INSURANCE   04/23/2016 04/23/2018 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   04/23/2014 04/23/2016 CRUM & FORSTER INDEMNITY
INSURANCE   04/02/2013 04/02/2014 AMERICAN SAFETY INDEMNITY CO
INSURANCE   04/02/2011 04/02/2012 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/02/2010 04/02/2011 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/02/2009 04/02/2010 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/02/2008 04/02/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 08/02/2005 08/25/2005 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 08/03/2004 09/15/2004 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TIN 09/15/2003 10/08/2003 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 07/24/2003 07/25/2003 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 07/16/2002 08/09/2002 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 08/21/2001 09/05/2001 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 10/05/2000 11/13/2000 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
TCI 10/14/1999 11/05/1999 IN-COMPLIANCE CERIC 0/2 COMPLIANCE ASSURANCE
 
UTCI 03/19/1998 04/01/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 Completion Notes PLACARD NOT ON SITE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 04/15/2024 Accepted GAINEY_H_1 Enforcement
 
Electronic Communication 04/10/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Document Management 04/09/2024 Satisfied CHRISTIAN_ED_1 Incident
 
Incident 04/09/2024 Has not led to Discharge CHRISTIAN_ED_1 Incident
 
Document Management 04/09/2024 Satisfied CHRISTIAN_ED_1 Incident
 
Electronic Communication 04/09/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 03/21/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 03/07/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 02/20/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Letter 02/12/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Site Inspection 02/09/2024 Major Out of Compliance CHRISTIAN_ED_1 0/2 Compliance Assistance
 
Letter 01/19/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Site Inspection 01/19/2024 Major Out of Compliance CHRISTIAN_ED_1 0/2 Routine Compliance
 
Phone Conversation 01/02/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 01/02/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 04/25/2022 Satisfied MCARTOR_H_1 Compliance Assistance
 
Letter 04/25/2022 Satisfied RICHARDS_JE_1 Compliance Assistance
 
Electronic Communication 04/12/2022 Satisfied RICHARDS_JE_1 Compliance Assistance
 
Site Inspection 01/27/2022 Major Out of Compliance MCKINLEY_DN_1 0/2 Routine Compliance
 
Letter 01/27/2022 Satisfied MCKINLEY_DN_1 Compliance Assistance
 
Electronic Communication 10/31/2019 Satisfied LUNN_RJ_1 Routine Compliance
 
Letter 10/23/2019 Satisfied LUNN_RJ_1 Routine Compliance
 
Site Inspection 10/23/2019 In Compliance LUNN_RJ_1 0/2 Routine Compliance
 
Letter 06/29/2018 Satisfied MONDO_PW_1 Closure
 
Site Inspection 06/29/2018 In Compliance MONDO_PW_1 0/2 Installation
 
Site Inspection 06/29/2018 In Compliance MONDO_PW_1 0/2 Closure
 
Letter 06/29/2018 Satisfied MONDO_PW_1 Installation
 
Letter 06/07/2018 Satisfied RICHARDS_JE_1 Closure
 
TCAR 06/07/2018 Satisfied RICHARDS_JE_1 Closure
 
Site Inspection 07/25/2017 In Compliance GREGORY_HM_1 0/2 Compliance Assistance
 
Letter 07/25/2017 Satisfied GREGORY_HM_1 Compliance Assistance
 
Letter 02/27/2017 Satisfied GREGORY_HM_1 Non-Compliance
 
Site Inspection 02/24/2017 Minor Out of Compliance GREGORY_HM_1 0/2 Routine Compliance
 
Electronic Communication 02/24/2017 Satisfied GREGORY_HM_1 Routine Compliance
 
Electronic Communication 02/15/2017 Satisfied GREGORY_HM_1 Routine Compliance
 
Issue Document 09/29/2014 Satisfied PEREA_AO_1 Routine Compliance
 
Site Inspection 09/25/2014 In Compliance KASSEES_RP_1 0/2 Routine Compliance
 
Emergency Preparedness Information 09/24/2014 Satisfied KASSEES_RP_1 Routine Compliance
 
Issue Document 09/16/2014 Satisfied TOWLE_M Discharge
 
Record Document 09/16/2014 Satisfied TOWLE_M Discharge
 
Discharge Reporting 09/16/2014 Satisfied TOWLE_M Discharge
 
Discharge Reporting 09/16/2014 Satisfied TOWLE_M Discharge
 
Issue Document 08/14/2014 Satisfied TOWLE_M Discharge
 
Record Document 08/14/2014 Satisfied TOWLE_M Discharge
 
Issue Document 07/09/2014 Satisfied TOWLE_M Discharge
 
Record Document 07/09/2014 Satisfied TOWLE_M Discharge
 
Issue Document 07/09/2014 Satisfied TOWLE_M Discharge
 
Record Document 07/09/2014 Satisfied TOWLE_M Discharge
 
Record Document 05/23/2014 Satisfied TOWLE_M Discharge
 
Issue Document 05/23/2014 Satisfied TOWLE_M Discharge
 
Record Document 03/04/2014 Satisfied TOWLE_M Discharge
 
Issue Document 03/04/2014 Satisfied TOWLE_M Discharge
 
Record Document 12/05/2013 Satisfied TOWLE_M Discharge
 
Issue Document 12/05/2013 Satisfied TOWLE_M Discharge
 
Record Document 09/26/2013 Satisfied TOWLE_M Discharge
 
Issue Document 09/26/2013 Satisfied TOWLE_M Discharge
 
Record Document 09/13/2013 Satisfied TOWLE_M Discharge
 
Record Document 08/15/2013 Satisfied TOWLE_M Discharge
 
Record Document 08/15/2013 Satisfied TOWLE_M Discharge
 
Issue Document 08/15/2013 Satisfied TOWLE_M Discharge
 
Issue Document 08/15/2013 Satisfied TOWLE_M Discharge
 
Record Document 07/15/2013 Satisfied TOWLE_M Discharge
 
Issue Document 07/05/2013 Satisfied TOWLE_M Discharge
 
Site Inspection 06/30/2013 In Compliance CERIC_M_1 0/2 Routine Compliance
 
Emergency Preparedness Information 06/30/2013 Satisfied CERIC_M_1 Routine Compliance
 
Incident 06/28/2013 Led to Discharge (Incident promoted) TOWLE_M Incident
 
Meeting 06/28/2013 Satisfied TOWLE_M Discharge
 
Issue Document 05/31/2013 Satisfied TOWLE_M Discharge
 
Record Document 05/31/2013 Satisfied TOWLE_M Discharge
 
Record Document 04/08/2013 Satisfied TOWLE_M Discharge
 
Issue Document 04/08/2013 Satisfied TOWLE_M Discharge
 
Record Document 03/22/2013 Satisfied TOWLE_M Discharge
 
Issue Document 03/22/2013 Satisfied TOWLE_M Discharge
 
Issue Document 01/22/2013 Satisfied TOWLE_M Discharge
 
Record Document 01/22/2013 Satisfied TOWLE_M Discharge
 
Issue Document 07/13/2012 Satisfied LUBINSKI_D Discharge
 
Record Document 04/10/2012 Satisfied LUBINSKI_D Discharge
 
Issue Document 04/10/2012 Satisfied LUBINSKI_D Discharge
 
Issue Document 03/02/2012 Satisfied LUBINSKI_D Discharge
 
Issue Document 01/23/2012 Satisfied DOHANEY_T Non-Compliance
 
Issue Document 12/01/2011 Satisfied LUBINSKI_D Discharge
 
Letter 10/31/2011 Satisfied CERIC_M_1 Non-Compliance
 
Site Inspection 10/31/2011 Major Out of Compliance CERIC_M_1 0/2 Routine Compliance
 
Emergency Preparedness Information 10/28/2011 Satisfied CERIC_M_1 Routine Compliance
 
Site Inspection 10/11/2010 In Compliance CERIC_M_1 0/2 Routine Compliance
 
Record Document 03/29/2010 Satisfied CERIC_M_1 Non-Compliance
 
Letter 02/10/2010 Satisfied CERIC_M_1 Non-Compliance
 
Site Inspection 02/10/2010 Minor Out of Compliance CERIC_M_1 0/2 Routine Compliance
 
Site Inspection 09/08/2008 In Compliance CERIC_M_1 0/2 Non-Compliance
 
Letter 09/08/2008 Satisfied CERIC_M_1 Non-Compliance
 
Site Inspection 08/07/2008 Minor Out of Compliance CERIC_M_1 0/2 Routine Compliance
 
Record Document 08/30/2007 Satisfied CERIC_M_1 Non-Compliance
 
Letter 08/03/2007 Satisfied CERIC_M_1 Non-Compliance
 
Letter 08/03/2007 Satisfied CERIC_M_1 Non-Compliance
 
Site Inspection 07/18/2007 Minor Out of Compliance CERIC_M_1 0/2 Routine Compliance
 
Emergency Preparedness Information 02/08/2007 Satisfied HORSLEY_JK Routine Compliance
 
Record Document 02/07/2007 Satisfied CERIC_M_1 Non-Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied HORSLEY_JK Routine Compliance
 
Site Inspection 08/08/2006 Minor Out of Compliance CERIC_M_1 0/2 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
01/17/2024 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. Investigate the issue to determine if a discharge has occurred.
 
01/17/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Facility must remove liquid from the Premium STP sump and dispose of liquid properly. Further, due to the fuel alarms, liquid must be removed from the Diesel and Regular STP sump, and the Premium-Diesel (Tank 1) Interstitial space. Responsible party must determine the source of the liquid and determine if a discharge has occurred to the environment or not. Incident investigation and resolution documentation must be provided. Post liquid removal integrity testing may be required. Sampling may be required.
 
01/17/2024 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Investigate the issue.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
06/26/2013   COMPLETED
 
02/25/2011   COMPLETED 10