Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9701333 | Latitude | 27° 57' 28.7766 | ||||||||
Name |
HARBOURWOOD HEALTH & REHAB CTR 549 SKY HARBOR DR #31 |
Longitude | 82° 43' 15.9345 | ||||||||
CLEARWATER, FL 33759-4056 | LL Method | DPHO | |||||||||
Contact | Danny Davis NHA | LL Status | REVIEWED | ||||||||
Phone | (727) 724-6800 | Status Date | 04/12/2004 | ||||||||
Account Owner Information | |||||||||||
Name | HARBOURWOOD FL OPCO LLC 549 SKY HARBOR DR BLDG 31 CLEARWATER, FL 33759 |
Effective Date | 01/23/2023 | ||||||||
Contact | DANNY DAVIS | ||||||||||
Phone | (727) 313-0052 | ||||||||||
ADMIN@HARBOURWOODHC.COM | |||||||||||
Placard # / Date | 684607 - 06/06/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | 549 SKY HARBOR DR LLC 2017 Flatbush Ave Brooklyn, NY 11234-3522 |
Effective Date | 01/01/2019 | ||||||||
Contact | JONATHAN FRANKEL | ||||||||||
Phone | (718) 338-2999 | ||||||||||
JONATHAN.FRANKEL@TLMGMT.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 2600 | Emerg Generator Diesel (G) | 12/01/2020 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
894642 | 750 | Emerg Generator Diesel (G) | 07/01/1996 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system |
(1) Continuous electronic sensing (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/17/2020 | 09/17/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/17/2019 | 09/17/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/17/2018 | 09/17/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/17/2017 | 09/17/2018 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/17/2016 | 09/17/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/17/2015 | 09/17/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/17/2014 | 09/17/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/17/2012 | 09/17/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 05/14/2010 | 05/14/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 05/14/2008 | 05/14/2009 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
LTR | 07/29/2005 | 07/29/2005 | BARNETT | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/29/2005 | 07/29/2005 | IN-COMPLIANCE | BARNETT | 1/0 | COMPLIANCE ASSURANCE | |||||
LTR | 10/27/2004 | 10/28/2004 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/26/2004 | 10/28/2004 | IN-COMPLIANCE | PINK | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 03/24/2004 | 03/26/2004 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NO CORRECTIONS - SUBMITTAL OF ANNUAL OPERABILITY OF RUPTURE BASIN ALARM | |||||||||||
NCLI | 03/17/2004 | 03/22/2004 | COMPLIANCE ASSURANCE | ||||||||
TCI | 03/12/2004 | 03/22/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | SOWERS | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/30/2003 | 06/04/2003 | HALSCOTT | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 03/21/2003 | 03/25/2003 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 03/03/2003 | 03/06/2003 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/28/2003 | 02/28/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | TAM | 1/0 | COMPLIANCE ASSURANCE | |||||
TCI | 12/11/2001 | 12/28/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | HALSCOTT | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 12/11/2001 | 01/06/2002 | COMPLIANCE ASSURANCE | ||||||||
NCLI | 12/11/2001 | 01/02/2002 | HALSCOTT | 0/0 | COMPLIANCE ASSURANCE | ||||||
FR | 12/22/2000 | 12/22/2000 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 07/24/2000 | 08/03/2000 | HALSCOTT | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/24/2000 | 08/01/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | HALSCOTT | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 02/21/2000 | 02/28/2000 | HALSCOTT | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/14/2000 | 02/22/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | HALSCOTT | 1/0 | COMPLIANCE ASSURANCE | |||||
ATCI | 10/27/1998 | 11/03/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Record Document | 02/01/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Record Document | 01/26/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Record Document | 01/19/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Electronic Communication | 01/17/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Enforcement Referral | 01/11/2023 | Accepted | LASHBROOK_SJ_1 | Enforcement | |||||||
Letter | 01/09/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Site Inspection | 01/06/2023 | Major Out of Compliance | SHOCK_E_1 | 2/0 | Closure | ||||||
Record Document | 11/29/2022 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Electronic Communication | 11/08/2022 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Electronic Communication | 11/08/2022 | Satisfied | SHOCK_E_1 | Routine Compliance | |||||||
Site Inspection | 11/04/2022 | Major Out of Compliance | SHOCK_E_1 | 2/0 | Routine Compliance | ||||||
Electronic Communication | 10/17/2022 | Satisfied | SHOCK_E_1 | Routine Compliance | |||||||
Site Inspection | 05/27/2021 | Major Out of Compliance | STRAUSS_RH_1 | 1/0 | Installation | ||||||
Letter | 05/27/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 03/13/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 03/13/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 01/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 01/03/2020 | Major Out of Compliance | STRAUSS_RH_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 12/30/2019 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Record Document | 02/01/2018 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 02/01/2018 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 10/18/2017 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 10/18/2017 | Major Out of Compliance | STRAUSS_RH_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 10/11/2017 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Record Document | 06/01/2015 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 02/27/2015 | In Compliance | STRAUSS_RH_1 | 1/0 | Non-Compliance | ||||||
Issue Document | 02/27/2015 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 02/04/2015 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 02/04/2015 | Major Out of Compliance | STRAUSS_RH_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 03/12/2013 | Satisfied | SOWERS_JA_1 | Routine Compliance | |||||||
Site Inspection | 03/12/2013 | In Compliance | SOWERS_JA_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 09/16/2010 | In Compliance | LONGEN_JL_1 | 1/0 | Routine Compliance | ||||||
Record Document | 07/20/2009 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 07/17/2009 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 07/17/2009 | Major Out of Compliance | LONGEN_JL_1 | 1/0 | Routine Compliance | ||||||
Record Document | 12/01/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 10/14/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 10/14/2008 | Major Out of Compliance | LONGEN_JL_1 | 1/0 | Non-Compliance | ||||||
Record Document | 10/14/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 09/30/2008 | Major Out of Compliance | LONGEN_JL_1 | 1/0 | Non-Compliance | ||||||
Letter | 09/30/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 08/18/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 08/18/2008 | Major Out of Compliance | LONGEN_JL_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 09/21/2007 | In Compliance | BARNETT_JX | 1/0 | Routine Compliance | ||||||
Site Inspection | 03/15/2007 | Minor Out of Compliance | BARNETT_JX | 1/0 | Routine Compliance | ||||||
Letter | 03/15/2007 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/06/2023 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Complete registration update to show that FDEP Tank 894642 has been closed and removed from site. | |||||||
11/02/2022 | 7125 | SNC-A | 1.17 Owner, operator, or supplier deposited motor fuel into storage tank without current valid registration placard. | Pay for storage tank registration, print and post storage tank registration placard immediately. Provide copy of current registration or provide photo of registration placard when posted. | |||||||
11/02/2022 | 7095 | Minor | 1.14 Records requiring 3 year documentation period not kept by facility. | Maintain storage tank records for 3 years and make available for review at inspection. | |||||||
11/02/2022 | 7094 | Minor | 1.13 Permanent records not available within 5 working days notice. | Provide all storage tank records for review. | |||||||
11/02/2022 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide financial responsibility (insurance) and Certification of Financial Responsibility documents. | |||||||
11/02/2022 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide annual operability testing for rupture basin sensor / alarm panel. The testing should indicate that the rupture basin sensor was removed, manually sent into alarm, and an alarm response (light / buzzer) occurred at the panel. | |||||||
11/02/2022 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide annual operability testing results for the Krueger tank gauge that indicates the gauge was removed from the tank, it was manipulated manually and it is operating as designed. | |||||||
05/27/2021 | 5006 | Minor | 1.1 Notification of installation not received in required timeframes. | Please ensure these notifications are provided to the Pinellas tank program before the installation of any regulated petroleum storage tank in Pinellas or Pasco Counties | |||||||
05/27/2021 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Please provide proof of current coverage | |||||||
No Discharges Found |