District Southeast   Type    Fuel user/Non-retail
 
County Miami-Dade   Status    OPEN
 
ID 9800068   Latitude    25° 46' 8.4609
 
Name ICON BRICKELL
465 BRICKELL AVE
Longitude    80° 11' 22.3335
  MIAMI, FL 33131 LL Method    DPHO
 
Contact CARLOS SANTIESTEBAN   LL Status    REVIEWED
 
Phone (305) 709-0590   Status Date    03/21/2025
 
Account Owner Information
 
Name ICONBRICKELL MASTER ASSOC
465 BRICKELL AVE #200
MIAMI, FL 33131
Effective Date    08/25/2010
 
Contact KARINA SCHULER
 
Phone (305) 709-0590
 
Email MA@ICONBRICKELL.COM
  Placard # / Date    705522 - 04/09/2025
Property Owner Information
 
Name TRG BRICKELL POINT COMMONS LTD
495 BRICKELL AVE
MIAMI, FL 33131
Effective Date    09/29/2008
 
Contact CHARLES CARRENO
 
Phone (305) 372-0637
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
2 3000 Emerg Generator Diesel (G) 09/01/2008 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(J) Pressurized piping system
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Emerg Generator Diesel (G) 01/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass   (B) Steel/galvanized metal (I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   03/31/2020 03/31/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   03/31/2017 03/31/2018 COMMERCE & INDUSTRY
INSURANCE   03/31/2016 03/31/2017 COMMERCE & INDUSTRY
INSURANCE   03/31/2015 03/31/2016 COMMERCE & INDUSTRY
INSURANCE   07/01/2014 03/31/2015 COMMERCE & INDUSTRY
INSURANCE   07/01/2013 07/01/2014 COMMERCE & INDUSTRY
INSURANCE   07/01/2012 07/01/2013 COMMERCE & INDUSTRY
INSURANCE   07/01/2011 07/01/2012 COMMERCE & INDUSTRY
INSURANCE   07/01/2010 07/01/2011 COMMERCE & INDUSTRY
INSURANCE   06/15/2009 06/15/2009 MERCURY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 03/21/2025 Satisfied SANPEDRO_A_2 Compliance Assistance
 
Site Inspection 03/21/2025 Major Out of Compliance SANPEDRO_A_2 1/0 Routine Compliance
 
Letter 03/21/2025 Satisfied SANPEDRO_A_2 Compliance Assistance
 
Electronic Communication 02/11/2025 Satisfied SANPEDRO_A_2 Routine Compliance
 
Letter 11/13/2020 Satisfied GODWIN_MR_1 Compliance Assistance
 
Site Inspection 11/12/2020 In Compliance GODWIN_MR_1 1/0 Compliance Assistance
 
Site Inspection 09/10/2020 Major Out of Compliance GODWIN_MR_1 1/0 Routine Compliance
 
Letter 09/10/2020 Satisfied GODWIN_MR_1 Compliance Assistance
 
Electronic Communication 08/27/2020 Satisfied GODWIN_MR_1 Routine Compliance
 
Phone Conversation 08/27/2020 Satisfied GODWIN_MR_1 Routine Compliance
 
Letter 01/02/2018 Satisfied CABRERA_VE_1 Compliance Assistance
 
Letter 01/02/2018 Satisfied CABRERA_VE_1 Compliance Assistance
 
Site Inspection 01/02/2018 In Compliance CABRERA_VE_1 1/0 Compliance Assistance
 
Site Inspection 12/13/2017 Minor Out of Compliance CABRERA_VE_1 1/0 Routine Compliance
 
Electronic Communication 11/29/2017 Satisfied CABRERA_VE_1 Routine Compliance
 
Electronic Communication 11/22/2017 Satisfied CABRERA_VE_1 Routine Compliance
 
Site Inspection 09/08/2015 In Compliance LINCHETA_CR_1 1/0 Routine Compliance
 
Electronic Communication 08/31/2015 Satisfied LINCHETA_CR_1 Routine Compliance
 
Phone Conversation 08/31/2015 Satisfied LINCHETA_CR_1 Routine Compliance
 
Site Inspection 09/04/2013 In Compliance LINCHETA_CR_1 1/0 Routine Compliance
 
Electronic Communication 09/04/2013 Satisfied LINCHETA_CR_1 Routine Compliance
 
Site Inspection 08/04/2011 In Compliance LINCHETA_CR_1 1/0 Routine Compliance
 
Enforcement Tracking 10/25/2010 Closed Without Enforcement KONG_TE_1 Enforcement
 
Site Inspection 09/02/2010 In Compliance REYES_D_1 1/0 Non-Compliance
 
Letter 07/18/2010 Satisfied REYES_D_1 Non-Compliance
 
Site Inspection 07/18/2010 Major Out of Compliance REYES_D_1 1/0 Routine Compliance
 
Site Inspection 06/15/2009 Minor Out of Compliance SYKORA_JJ_1 1/0 Non-Compliance
 
Phone Conversation 06/09/2009 Satisfied SYKORA_JJ_1 Non-Compliance
 
Site Inspection 09/29/2008 Major Out of Compliance SYKORA_JJ_1 1/0 Non-Compliance
 
Letter 09/23/2008 Satisfied SYKORA_JJ_1 Non-Compliance
 
Enforcement Referral 09/23/2008 Accepted KONG_TE_1 Enforcement
 
Site Inspection 09/23/2008 Major Out of Compliance SYKORA_JJ_1 0/1 Routine Compliance
 
Issue Document 09/23/2008 Satisfied KONG_TE_1 Enforcement
 
Site Inspection 09/23/2008 Minor Out of Compliance SYKORA_JJ_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/21/2025 7058 Minor 3.2 Valves do not meet standards of Section 7 of PEI/RP200-13 for piping systems with gravity head. Install the anti-siphon valves on the supply lines in the following order: tank-> isolation valve-> anti-siphon valve ->line leak detector.
 
03/20/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide a current and passing annual operability test of the Morrison clock gauge.
 
03/20/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Provide a current and passing annual operability test of the leak gauge.
 
03/20/2025 7009 SNC-B 1.7 No financial responsibility instrument or expired instrument for < 180 days. Provide a current copy of the certificate of financial responsibility for the regulated tank.
 
03/20/2025 7071 SNC-B 3.9 Small diameter integral piping with secondary containment: Applicable release detection methods not used. Provide a current and passing annual operability test of two (2) line leak detectors.
 
03/20/2025 7002 Minor 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Submit a registration form to FDEP to update the facility contact, property owner, and account owner’s information.
 
 
 