Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9800068 | Latitude | 25° 46' 8.4609 | ||||||||
Name |
ICON BRICKELL 465 BRICKELL AVE |
Longitude | 80° 11' 22.3335 | ||||||||
MIAMI, FL 33131 | LL Method | DPHO | |||||||||
Contact | CARLOS SANTIESTEBAN | LL Status | REVIEWED | ||||||||
Phone | (305) 709-0590 | Status Date | 03/21/2025 | ||||||||
Account Owner Information | |||||||||||
Name | ICONBRICKELL MASTER ASSOC 465 BRICKELL AVE #200 MIAMI, FL 33131 |
Effective Date | 08/25/2010 | ||||||||
Contact | KARINA SCHULER | ||||||||||
Phone | (305) 709-0590 | ||||||||||
MA@ICONBRICKELL.COM | |||||||||||
Placard # / Date | 705522 - 04/09/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | TRG BRICKELL POINT COMMONS LTD 495 BRICKELL AVE MIAMI, FL 33131 |
Effective Date | 09/29/2008 | ||||||||
Contact | CHARLES CARRENO | ||||||||||
Phone | (305) 372-0637 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 3000 | Emerg Generator Diesel (G) | 09/01/2008 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (J) Pressurized piping system |
(F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1000 | Emerg Generator Diesel (G) | 01/01/1981 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass | (B) Steel/galvanized metal | (I) Not required | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 03/31/2020 | 03/31/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 03/31/2017 | 03/31/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2016 | 03/31/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2015 | 03/31/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2014 | 03/31/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2013 | 07/01/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2012 | 07/01/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2011 | 07/01/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2010 | 07/01/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/15/2009 | 06/15/2009 | MERCURY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 03/21/2025 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Site Inspection | 03/21/2025 | Major Out of Compliance | SANPEDRO_A_2 | 1/0 | Routine Compliance | ||||||
Letter | 03/21/2025 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Electronic Communication | 02/11/2025 | Satisfied | SANPEDRO_A_2 | Routine Compliance | |||||||
Letter | 11/13/2020 | Satisfied | GODWIN_MR_1 | Compliance Assistance | |||||||
Site Inspection | 11/12/2020 | In Compliance | GODWIN_MR_1 | 1/0 | Compliance Assistance | ||||||
Site Inspection | 09/10/2020 | Major Out of Compliance | GODWIN_MR_1 | 1/0 | Routine Compliance | ||||||
Letter | 09/10/2020 | Satisfied | GODWIN_MR_1 | Compliance Assistance | |||||||
Electronic Communication | 08/27/2020 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Phone Conversation | 08/27/2020 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Letter | 01/02/2018 | Satisfied | CABRERA_VE_1 | Compliance Assistance | |||||||
Letter | 01/02/2018 | Satisfied | CABRERA_VE_1 | Compliance Assistance | |||||||
Site Inspection | 01/02/2018 | In Compliance | CABRERA_VE_1 | 1/0 | Compliance Assistance | ||||||
Site Inspection | 12/13/2017 | Minor Out of Compliance | CABRERA_VE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 11/29/2017 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Electronic Communication | 11/22/2017 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Site Inspection | 09/08/2015 | In Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 08/31/2015 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Phone Conversation | 08/31/2015 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Site Inspection | 09/04/2013 | In Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 09/04/2013 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Site Inspection | 08/04/2011 | In Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 10/25/2010 | Closed Without Enforcement | KONG_TE_1 | Enforcement | |||||||
Site Inspection | 09/02/2010 | In Compliance | REYES_D_1 | 1/0 | Non-Compliance | ||||||
Letter | 07/18/2010 | Satisfied | REYES_D_1 | Non-Compliance | |||||||
Site Inspection | 07/18/2010 | Major Out of Compliance | REYES_D_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/15/2009 | Minor Out of Compliance | SYKORA_JJ_1 | 1/0 | Non-Compliance | ||||||
Phone Conversation | 06/09/2009 | Satisfied | SYKORA_JJ_1 | Non-Compliance | |||||||
Site Inspection | 09/29/2008 | Major Out of Compliance | SYKORA_JJ_1 | 1/0 | Non-Compliance | ||||||
Letter | 09/23/2008 | Satisfied | SYKORA_JJ_1 | Non-Compliance | |||||||
Enforcement Referral | 09/23/2008 | Accepted | KONG_TE_1 | Enforcement | |||||||
Site Inspection | 09/23/2008 | Major Out of Compliance | SYKORA_JJ_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 09/23/2008 | Satisfied | KONG_TE_1 | Enforcement | |||||||
Site Inspection | 09/23/2008 | Minor Out of Compliance | SYKORA_JJ_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/21/2025 | 7058 | Minor | 3.2 Valves do not meet standards of Section 7 of PEI/RP200-13 for piping systems with gravity head. | Install the anti-siphon valves on the supply lines in the following order: tank-> isolation valve-> anti-siphon valve ->line leak detector. | |||||||
03/20/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide a current and passing annual operability test of the Morrison clock gauge. | |||||||
03/20/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide a current and passing annual operability test of the leak gauge. | |||||||
03/20/2025 | 7009 | SNC-B | 1.7 No financial responsibility instrument or expired instrument for < 180 days. | Provide a current copy of the certificate of financial responsibility for the regulated tank. | |||||||
03/20/2025 | 7071 | SNC-B | 3.9 Small diameter integral piping with secondary containment: Applicable release detection methods not used. | Provide a current and passing annual operability test of two (2) line leak detectors. | |||||||
03/20/2025 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Submit a registration form to FDEP to update the facility contact, property owner, and account owner’s information. | |||||||
No Discharges Found |