Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/10/2025 Last Data Refresh: 05/09/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Lake | Status | OPEN | ||||||||
ID | 9800225 | Latitude | 28° 47' 55.3733 | ||||||||
Name |
CIRCLE K #2705935 439 S DUNCAN DR |
Longitude | 81° 44' 24.664 | ||||||||
TAVARES, FL 32778 | LL Method | DPHO | |||||||||
Contact | GRAHAM BIGGS | LL Status | REVIEWED | ||||||||
Phone | (919) 774-6700 | Status Date | 09/18/2023 | ||||||||
Account Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 03/30/2001 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Placard # / Date | 698088 - 06/29/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | RFCD PARTNERSHIP 8401 BLIND PASS RD SAINT PETERSBURG, FL 33736 |
Effective Date | 03/13/1998 | ||||||||
Contact | PAUL RESOP | ||||||||||
Phone | (813) 360-4079 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 12000 | Unleaded Gas (B) | 02/01/1998 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 12000 | Unleaded Gas (B) | 02/01/1998 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 10000 | Vehicular Diesel (D) | 02/01/1998 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
GUARANTEE | 04/24/2022 | 08/21/2023 | |||||||||
INSURANCE | 12/01/2020 | 12/01/2021 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2018 | 12/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2017 | 12/01/2018 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2016 | 12/01/2017 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2015 | 12/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2014 | 12/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2013 | 12/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2011 | 12/01/2013 | CHUBB | ||||||||
INSURANCE | 12/01/2011 | 12/01/2012 | CHUBB | ||||||||
INSURANCE | 12/17/2010 | 12/17/2011 | CHUBB | ||||||||
INSURANCE | 12/17/2009 | 12/17/2010 | CHUBB | ||||||||
INSURANCE | 12/17/2008 | 12/17/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCR | 04/13/2006 | 04/18/2006 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes SPILL BUCKETS AND DISP. 1/2 CLEANED OUT OK. | |||||||||||
TCI | 03/14/2006 | 03/19/2006 | MINOR OUT-OF-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PLLD AND VR/SENSOR CERT DONE 3/06. REMOVE LIQUID/DEBRIS FROM SPILL/FILL BUCKETS AND DISP. 1/2. | |||||||||||
LTR | 03/31/2005 | 04/05/2005 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED PLLD OP. TEST AND VR/SENSOR CERT. | |||||||||||
TCI | 03/14/2005 | 03/21/2005 | MINOR OUT-OF-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PLLD OP TEST AND SENSOR CERT - 3/05. "LIQUID STATUS" AS RD. | |||||||||||
LTR | 07/02/2004 | 07/20/2004 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED PROPERLY PERFORMED CLOSURE FROM ECS. LAKE COUNTY ON SITE TO OBSERVE. ORIGINAL ATC CLOSURE IN FILE BUT NOT VALID. CLOSURE STATES NO CONTAMINATION. | |||||||||||
TXI | 06/24/2004 | 06/28/2004 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes NEW CLOSURE WAS PERFORMED ON REG. UNLEADED SPILL BUCKET, INCLUDING SAMPLING AT ONE FOOT INTERVALS. | |||||||||||
LTR | 04/27/2004 | 04/27/2004 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED INF AND RESULTS STATING NO DISCHARGE. | |||||||||||
TCR | 04/22/2004 | 04/27/2004 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes LIDS PAINTED & SHEAR VALVES SECURE. | |||||||||||
IRFR | 04/15/2004 | 04/27/2004 | BOWERS | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes RECEIVED INF DATED 4/7/04 STATING FAILED HYDRO ON SPILL BUCKETS. RECEIVED LETTER ON 4/27/04 STATING NO DISCHARGE IN CONJUNCTION WITH THE INCIDENT. | |||||||||||
TXI | 04/08/2004 | 04/09/2004 | MINOR OUT-OF-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOVAL & REPLACEMENT OF 4 SPILL BUCKETS. CLOSURE DONE BT ATC. INF NOT FILED WITHIN 24 HRS. OF DISCOVERY. | |||||||||||
TCI | 03/16/2004 | 03/22/2004 | MINOR OUT-OF-COMPLIANCE | COX, BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PLLD TESTED 4/10/03, SENSOR CERT. 3/10/04 | |||||||||||
PR | 10/14/2003 | 11/07/2003 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED $2,000.00 FINE RESULTING FROM ENFORCEMENT ACTION. | |||||||||||
EPI | 08/25/2003 | 10/07/2003 | BOWERS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes AMENDED STATEMENT OF VIOLATION AND NOTICE OF HEARING ISSUED 8/25/03 TO APPEAR BEFOR THE CODE BOARD 9/10/03. ORDER OF ENFORCEMENT ISSUED ON 9/16/03 FOR A FINE OF $2,000.00. | |||||||||||
LTR | 05/13/2003 | 05/28/2003 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED MLLD. | |||||||||||
TCR | 05/02/2003 | 05/02/2003 | IN-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes RECEIVED MLLD. | |||||||||||
TCI | 03/25/2003 | 03/27/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | COX, BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DW FIBERGLASS PIPING. MLLD 4/10/03. | |||||||||||
DCCR | 02/24/2003 | 02/24/2003 | COX, BOWERS | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes DRF RECEIVED, DISCHARGE INSPECTION CONFIRMED | |||||||||||
TCDI | 02/24/2003 | 02/24/2003 | IN-COMPLIANCE | COX,BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DRF RECEIVED, DIESEL FUEL SPILLED IN PARKING LOT, RAN INTO WRA, FORWARDED TO SEMINOLE COUNTY FOR CLEAN UP | |||||||||||
TCI | 03/29/2002 | 04/01/2002 | IN-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE. PLLD 3/16/02 | |||||||||||
TCI | 03/23/2001 | 03/27/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | BOWERS/COX | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE | |||||||||||
UTII | 06/05/1998 | 09/15/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/07/2025 | Satisfied | FARRIS_J | Enforcement | |||||||
Enforcement Referral | 06/21/2024 | Accepted | GREGORY_JW_1 | Enforcement | |||||||
Electronic Communication | 02/29/2024 | Satisfied | GREGORY_JW_1 | Routine Compliance | |||||||
Letter | 07/17/2023 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 07/17/2023 | Major Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 07/10/2023 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 07/10/2023 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 02/04/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 02/04/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 02/03/2022 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Site Inspection | 10/18/2021 | Major Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Letter | 10/18/2021 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/12/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 06/29/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Incident | 11/21/2020 | Has not led to Discharge | RAUENZAHN_RA_1 | Incident | |||||||
Electronic Communication | 10/04/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 10/04/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 08/30/2019 | Minor Out of Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Letter | 08/30/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 08/07/2019 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Letter | 01/12/2018 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 07/26/2017 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 09/18/2015 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 09/15/2015 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 01/23/2014 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Document Management | 11/27/2013 | Complete | RAUENZAHN_RA_1 | Incident | |||||||
Document Management | 11/27/2013 | Complete | RAUENZAHN_RA_1 | Incident | |||||||
Site Inspection | 03/15/2013 | In Compliance | BECKER_GT_1 | 0/1 | Closure | ||||||
Site Inspection | 03/13/2013 | In Compliance | BECKER_GT_1 | 0/1 | Installation | ||||||
Issue Document | 03/13/2013 | Satisfied | BECKER_GT_1 | Installation | |||||||
Site Inspection | 02/21/2012 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/22/2011 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 06/17/2010 | In Compliance | COX_CD_1 | 0/3 | Non-Compliance | ||||||
Incident | 05/25/2010 | Has not led to Discharge | COX_CD_1 | Incident | |||||||
Site Inspection | 02/17/2010 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 12/28/2009 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 06/11/2009 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Letter | 03/23/2009 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 03/23/2009 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 11/25/2008 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Closure | ||||||
Record Document | 09/05/2008 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
Record Document | 06/16/2008 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
TCAR | 06/10/2008 | Satisfied | COX_CD_1 | Closure | |||||||
Record Document | 05/12/2008 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Record Document | 05/07/2008 | Satisfied | COX_CD_1 | Installation | |||||||
Site Inspection | 05/02/2008 | Minor Out of Compliance | COX_CD_1 | 0/3 | Installation | ||||||
Site Inspection | 04/28/2008 | Minor Out of Compliance | COX_CD_1 | 0/3 | Closure | ||||||
Record Document | 04/17/2008 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Record Document | 04/17/2008 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
Site Inspection | 04/14/2008 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 04/11/2008 | Minor Out of Compliance | COX_CD_1 | 0/3 | Closure | ||||||
Site Inspection | 04/11/2008 | Minor Out of Compliance | COX_CD_1 | 0/3 | Installation | ||||||
Site Inspection | 03/18/2008 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/18/2008 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 09/14/2007 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 06/06/2007 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Letter | 06/06/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 05/11/2007 | Minor Out of Compliance | COX_CD_1 | 0/3 | Non-Compliance | ||||||
Letter | 05/11/2007 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Letter | 05/04/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 05/04/2007 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 03/14/2007 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/14/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/05/2007 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/21/2006 | Satisfied | ZIMMERMAN_RA_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
07/17/2023 | 6001 | Minor | 2.1 No reasonable access provided. | Replace the handles on the STP sump covers to allow access to the sumps for inspections and testing. | |||||||
07/17/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove the water from all three of the spill buckets. | |||||||
07/17/2023 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | File an INF for the failed testing and repair the dispenser. Investigate the incident to determine if a discharge occurred. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
02/21/2003 | COMPLETED | 29 | |||||||||