DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/14/2025        Last Data Refresh: 03/13/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 9802292   Latitude    28° 2' 7.4994
 
Name KK FOOD MART
4275 NEW TAMPA HWY
Longitude    82° 1' 7.6809
  LAKELAND, FL 33815 LL Method    DPHO
 
Contact MD MONIRUJJAMAN   LL Status    REVIEWED
 
Phone (561) 425-0966   Status Date    09/18/2023
 
Account Owner Information
 
Name ADIB PETROLEUM INC
4275 NEW TAMPA HWY
LAKELAND, FL 33815
Effective Date    03/28/2024
 
Contact MD MONIRUJJAMAN
 
Phone (561) 425-0966
 
Email JEWELSYL@GMAIL.COM
  Placard # / Date    702660 - 10/28/2024
Property Owner Information
 
Name BD OIL ENTERPRISES LLC
4275 NEW TAMPA HWY
LAKELAND, FL 33815
Effective Date    03/28/2024
 
Contact MD HASAN AHMMED
 
Phone (954) 330-6229
 
Email HASANAHMMED@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
2 12000 Unleaded Gas (B) 10/01/1999 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
4 10000 Unleaded Gas (B) 05/01/2006 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 12000 Unleaded Gas (B) 10/01/1999 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Vehicular Diesel (D) 10/01/1999 UNDERGROUND Out of Service (T)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   02/26/2024 02/26/2025 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2019 04/21/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2018 04/21/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2017 04/21/2018 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2016 04/21/2017 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2015 04/21/2016 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/21/2014 04/21/2015 ACE
INSURANCE   04/21/2011 04/21/2012 ACE
INSURANCE   04/22/2010 04/22/2011 ZURICH-AMERICAN
INSURANCE   12/17/2008 12/17/2009 AMERICAN INTERNATIONAL SPECIALTY LINES
INSURANCE   12/01/2000 04/30/2004 SOONER INSURANCE COMPANY
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   12/01/2000 12/01/2002
INSURANCE   03/01/2000 03/01/2001 GREAT AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
LTR 04/05/2006 04/06/2006 GONZALEZ_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NCLI FOLLOW UP LETTER.
 
CRDE 02/01/2006 02/01/2006 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
NCLI 01/27/2006 01/27/2006 GONZALEZ_J 0/3 COMPLIANCE ASSURANCE
 
IRFR 01/09/2006 01/10/2006 GONZALEZ_J 0/0 DISCHARGE PROJECT
 
 Completion Notes DISCOVERY: ? MONITORING: LIQUID DETECTOR. SUBSTANCE: GASOLINE. INVOLVES: RELEASE DETECTION EQUIP. PREMIUM INTERSTITIAL HAS WATER.
 
TCI 12/16/2005 01/27/2006 SIGNIFICANT OUT-OF-COMPLIANCE GONZALEZ_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes ONE PHOTO. PIPING: UNDERGROUND DOUBLE WALLED FIBERGLASS: AMERON; UNABLE TO IDENTIFY TYPE.
 
TCR 04/11/2005 05/03/2005 IN-COMPLIANCE NEWBERG_D 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #1105.
 
CWOE 04/11/2005 05/03/2005 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
TCQA 02/09/2005 05/12/2005 IN-COMPLIANCE RANDOLPH_L 0/0 COMPLIANCE ASSURANCE
 
NCLI 01/10/2005 01/11/2005 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
TCI 12/23/2004 01/11/2005 MINOR OUT-OF-COMPLIANCE NEWBERG_D 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 1 PHOTO TAKEN. PIPING: DOUBLE-WALLED AMERON RED RIGID FIBERGLASS. RESOLVES VIOLATON #144 & 155.
 
CALL 09/28/2004 10/13/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes HURRICANE DAMAGE ASSESSMENT. FRAN FRANCONI STATED NO DAMAGE TO STORAGE TANKS SYTEM.
 
RRBD 08/26/2004 08/27/2004 COOK_J 0/0 DISCHARGE PROJECT
 
 Completion Notes 8/16/04 INCIDENT RESOLVED. PRIMARY LINE TESTED TIGHT. SECONDARY REPAIRED. NO DISCHARGE INDICATED.
 
IRFR 08/17/2004 08/27/2004 COOK_J 0/0 DISCHARGE PROJECT
 
 Completion Notes DISCOVERY: 8/16/04. MONITORING: VISUAL OBSERVATION. SUBSTANCE: GASOLINE. INVOLVES: PIPE SECONDARY. CAUSE: HAND DIGGING. LINE IS BEING REPAIRED. NO PRODUCT LEAK OR DISCHARGE OBSERVED.
 
RRBD 05/21/2004 06/21/2004 CROWELL_M 0/0 DISCHARGE PROJECT
 
 Completion Notes RECEIVED REQUESTED TEST RESULTS. RESOLVES VIOLATION #204.
 
RRBD 04/30/2004 06/21/2004 CROWELL_M 0/0 DISCHARGE PROJECT
 
 Completion Notes FORM RECEIVED. RESOLVES VIOLATION #9.
 
RRBD 03/12/2004 06/21/2004 CROWELL_M 0/0 DISCHARGE PROJECT
 
 Completion Notes RESOLVES VIOLATION #194.
 
CNLI 03/09/2004 03/09/2004 CROWELL_M 0/0 DISCHARGE PROJECT
 
TDI 02/18/2004 03/09/2004 MINOR OUT-OF-COMPLIANCE CROWELL_M 0/3 DISCHARGE PROJECT
 
 Completion Notes 9 PHOTOS TAKEN.
 
DCCR 02/09/2004 03/15/2004 COOK_J 0/0 DISCHARGE PROJECT
 
 Completion Notes ANALYTICAL RESULTS SUBMITTED SHOWING GCTLS EXCEEDED (BENZENE, MTBE).
 
RRBD 01/05/2004 01/16/2004 CROWELL_M 0/0 DISCHARGE PROJECT
 
 Completion Notes RESOLVED-NO DISCHARGE TO ENVIRONMENT.
 
RRBD 01/05/2004 01/16/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #87, #127, & #86. VIOLATION #86 CITED BY MISTAKE SHOULD HAVE BEEN #87.
 
RRBD 12/05/2003 01/16/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes MANIFEST RECEIVED. RESOLVES VIOLATION #155.
 
NCLI 12/05/2003 12/10/2003 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
RRBD 11/21/2003 01/16/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
RRBD 11/21/2003 01/16/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED WORK ORDER. RESOLVES VIOLATION #81.
 
RRBD 11/06/2003 01/16/2004 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED INF AND INVESTIGATION RESULTS. RESOLVES VIOLATION #9 & #197.
 
TCI 11/05/2003 12/10/2003 SIGNIFICANT OUT-OF-COMPLIANCE CROWELL_M 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 7 PHOTOS TAKEN. RESOLVES VIOLATION #30. PIPING: DOUBLE-WALLED AMERON RED RIGID FIBERGLASS.
 
TXI 03/14/2003 12/10/2003 IN-COMPLIANCE NEWBERG_D 0/3 COMPLIANCE ASSURANCE
 
RRBD 11/06/2002 12/10/2003 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #209.
 
NCLI 10/30/2002 11/01/2002 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #6
 
TIN 10/18/2002 11/01/2002 MINOR OUT-OF-COMPLIANCE NEWBERG_D 0/3 COMPLIANCE ASSURANCE
 
NCLI 07/31/2002 08/01/2002 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
RRBD 07/25/2002 07/25/2002 NEWBERG_D 0/0 DISCHARGE PROJECT
 
 Completion Notes WATER REMOVED, MANIFEST FROM AQUA CLEAN ENVIRONMENTAL RECEIVED
 
TCI 07/19/2002 08/01/2002 MINOR OUT-OF-COMPLIANCE NEWBERG_D 0/3 COMPLIANCE ASSURANCE
 
CWOE 11/07/2001 01/07/2002 HUGHES 0/0 COMPLIANCE ASSURANCE
 
RRBD 11/07/2001 01/07/2002 HUGHES 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED PAPERWORK REQUESTED
 
NCLI 11/02/2001 11/05/2001 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
TCI 10/25/2001 11/05/2001 MINOR OUT-OF-COMPLIANCE HUGHES_J 0/3 COMPLIANCE ASSURANCE
 
CALL 10/18/2001 11/05/2001 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SCHEDULE TCI
 
TCI 04/27/2001 05/07/2001 IN-COMPLIANCE RANDOLPH_L 0/3 COMPLIANCE ASSURANCE
 
TIN 03/07/2000 03/23/2000 IN-COMPLIANCE RONEY_B 0/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 02/28/2025 Major Out of Compliance GLENN_LE_1 0/2 Routine Compliance
 
Site Inspection 06/15/2022 Major Out of Compliance GLENN_LE_1 0/3 Routine Compliance
 
Electronic Communication 06/08/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Site Inspection 06/08/2019 Major Out of Compliance JARRETT_SE_1 0/3 Routine Compliance
 
Letter 06/08/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 06/08/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/04/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/04/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 05/04/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Document Management 07/20/2017 Satisfied JARRETT_SE_1 Closure
 
Site Inspection 01/27/2017 In Compliance CASSELS_CR_2 0/3 Non-Compliance
 
Electronic Communication 01/27/2017 Satisfied CASSELS_CR_2 Non-Compliance
 
Record Document 01/26/2017 Satisfied CASSELS_CR_2 Installation
 
Letter 11/22/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Site Inspection 11/22/2016 Minor Out of Compliance CASSELS_CR_2 0/2 Installation
 
Site Inspection 11/22/2016 Minor Out of Compliance CASSELS_CR_2 0/2 Closure
 
Electronic Communication 11/22/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Letter 11/22/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Electronic Communication 10/24/2016 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 10/24/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Electronic Communication 10/24/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Letter 10/24/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Site Inspection 10/24/2016 Minor Out of Compliance CASSELS_CR_2 0/3 Routine Compliance
 
Document Management 09/27/2016 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 04/23/2014 Satisfied WINN_JP_1 Routine Compliance
 
Site Inspection 04/23/2014 In Compliance WINN_JP_1 0/3 Routine Compliance
 
Electronic Communication 12/19/2012 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 12/19/2012 Satisfied DERY_WC_1 Non-Compliance
 
Electronic Communication 12/19/2012 Satisfied DERY_WC_1 Non-Compliance
 
Enforcement Tracking 05/10/2012 Closed With Enforcement PEDIGO_L Enforcement
 
Record Document 02/01/2012 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 01/25/2012 Minor Out of Compliance NEWBERG_DR_1 0/3 Routine Compliance
 
Letter 01/25/2012 Satisfied NEWBERG_DR_1 Non-Compliance
 
Discharge Reporting 07/11/2011 Satisfied CASSELS_CR_1 Discharge
 
Document Management 07/11/2011 Complete CASSELS_CR_1 Discharge
 
Record Document 10/04/2010 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Letter 09/24/2010 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Meeting 09/21/2010 Satisfied DERY_WC_1 Installation
 
Phone Conversation 09/07/2010 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Letter 07/30/2010 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 07/30/2010 Minor Out of Compliance SLAPPEY_WR_1 0/3 Routine Compliance
 
Record Document 01/13/2010 Minor Out of Compliance WINN_JP_1 Routine Compliance
 
Meeting 12/08/2009 Satisfied PEDIGO_L Enforcement
 
Letter 10/29/2009 Satisfied WINN_JP_1 Non-Compliance
 
Phone Conversation 08/12/2009 Satisfied WINN_JP_1 Routine Compliance
 
Letter 07/30/2009 Satisfied WINN_JP_1 Non-Compliance
 
Site Inspection 07/30/2009 Minor Out of Compliance WINN_JP_1 0/3 Routine Compliance
 
Enforcement Referral 06/11/2009 Accepted PEDIGO_L Enforcement
 
Record Document 09/09/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 08/11/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 07/22/2008 Minor Out of Compliance SLAPPEY_WR_1 0/3 Routine Compliance
 
Site Inspection 07/22/2008 In Compliance SLAPPEY_WR_1 0/4 Routine Compliance
 
Letter 07/22/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 07/21/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
TCAR 02/29/2008 Satisfied CASSELS_CR_1 Closure
 
Letter 02/19/2008 Satisfied DERY_WC_1 Closure
 
TCAR 02/19/2008 Satisfied DERY_WC_1 Closure
 
Letter 11/05/2007 Satisfied DERY_WC_1 Closure
 
TCAR 11/05/2007 Complete DERY_WC_1 Closure
 
Record Document 09/19/2007 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 09/12/2007 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 08/30/2007 In Compliance SLAPPEY_WR_1 0/3 Routine Compliance
 
Site Inspection 04/17/2007 In Compliance NEWBERG_DR_1 0/1 Closure
 
Site Inspection 04/17/2007 In Compliance NEWBERG_DR_1 0/1 Installation
 
Record Document 04/04/2007 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 03/13/2007 Satisfied DERY_WC_1 Non-Compliance
 
Emergency Preparedness Information 02/11/2007 Satisfied DIXON_R Routine Compliance
 
Record Document 01/30/2007 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 01/03/2007 Satisfied DERY_WC_1 Routine Compliance
 
Record Document 12/22/2006 Satisfied DERY_WC_1 Routine Compliance
 
Record Document 12/12/2006 Satisfied SLAPPEY_WR_1 Routine Compliance
 
Emergency Preparedness Information 09/27/2006 Satisfied CASSELS_CR_1 Routine Compliance
 
Record Document 08/01/2006 Satisfied NEWBERG_DR_1 Non-Compliance
 
Record Document 07/31/2006 Satisfied NEWBERG_DR_1 Non-Compliance
 
Meeting 07/11/2006 Satisfied CROWELL_MP Installation
 
Record Document 07/11/2006 Satisfied CROWELL_MP Closure
 
Meeting 06/26/2006 Satisfied CROWELL_MP Routine Compliance
 
Record Document 06/21/2006 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Letter 06/13/2006 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 06/12/2006 Major Out of Compliance SLAPPEY_WR_1 0/3 Installation
 
Letter 06/12/2006 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 06/12/2006 Major Out of Compliance NEWBERG_DR_1 0/1 Closure
 
Meeting 06/01/2006 Satisfied NEWBERG_DR_1 Installation
 
Meeting 05/31/2006 Satisfied SLAPPEY_WR_1 Installation
 
Meeting 05/25/2006 Satisfied CASSELS_CR_1 Installation
 
Phone Conversation 05/24/2006 Satisfied CROWELL_MP Closure
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/28/2025 6062 Minor 2.5 Release detection devices not tested annually. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
02/28/2025 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
02/28/2025 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
02/28/2025 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. 03/2024 to present, monthly release detection monitoring records or the next two months (January & February) of inspections must be provided to the Department as they are performed.
 
02/28/2025 6062 Minor 2.5 Release detection devices not tested annually. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
02/28/2025 6062 Minor 2.5 Release detection devices not tested annually. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
02/28/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. PCW must be removed and the Department notified.
 
02/28/2025 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
06/14/2022 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Documentation must be provided or an investigation performed to determine the cause of the alarms with the results provided to the Department.
 
06/14/2022 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. Documentation must be provided or an Incident Notification Form (INF) completed, and provided to the Department.
 
06/08/2019 4071 Minor 4.6 Integrity test not completed on repaired component before being placed into operation or service. A breach of integrity test should have been performed on the regular UST prior to placing it back into service; if the test was performed, the test records must be submitted to the Department. - If the test was not performed, it must be performed immediately with the test results submitted to the Department.
 
06/08/2019 4071 Minor 4.6 Integrity test not completed on repaired component before being placed into operation or service. Breach of integrity records must be submitted for the damaged system components; if the components have not been repaired, they must be tested and repaired immediately with appropriate documentation provided to the Department.
 
06/08/2019 4079 Minor 2.7 Records requiring 3 years documentation period not kept by facility. Repair and test records must be submitted to the Department immediately for the damaged system components.
 
06/08/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. Therefore, an INF must be completed and submitted to the Department.
 
06/08/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Investigations must be completed with the investigation results, repair records, and breach of integrity test results submitted to the Department.
 
06/08/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Therefore, an investigation (including hydrostatic test of the sump) must be performed, with the investigation results, repair and breach of integrity test records submitted to the Department.
 
06/08/2019 4006 Minor 2.5 Following owner change or discovery of unregistered facility, Registration Form not submitted. A registration form must be completed to list the correct facility information with the form submitted to the Department.
 
06/08/2019 4069 SNC-B 4.4 Storage tank system not taken out of operation until repair is made. Repair records must be submitted to the Department for the damaged components; if the components have not been repaired, they must be immediately taken out of service or isolated from the systems until such time as the systems have been repaired with the documentation submitted to the Department.
 
06/08/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. An INF must be completed and submitted to the Department.
 
06/08/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Repair records for the regular UST must be provided to the Department.
 
06/08/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. An investigation must be performed to determine the cause of the alarm, with the investigation results, repair, and breach of integrity test records submitted to the Department.
 
06/08/2019 4070 Minor 4.5 Repair not made in accordance with manufacturer's specifications and applicable reference guidelines. Repair and test records for the damaged components must be submitted to the Department.
 
06/08/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. A plate to seal the conduit must be installed with appropriate documentation provided to the Department.
 
06/08/2019 4065 SNC-B 4.2 Storage tank release detection requirements not met. Water must be removed, the sump cleaned and the Department contacted for inspection.
 
06/08/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Either records must be provided the damaged penetration fittings were repaired and tested or they must be repaired and tested immediately with the appropriate documentation provided to the Department.
 
06/08/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Water must be removed with appropriate documentation provided to the Department and the Department contacted for inspection.
 
06/08/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. INFs must be completed and submitted to the Department.
 
06/08/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Water must be removed, the sump cleaned, and the Department contacted for inspection.
 
06/08/2019 4001 Minor 2.2 Operator certification requirements not met. The Class C Operator training certification must be submitted to the Department.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/14/2007   COMPLETED 30
 
02/09/2004   COMPLETED 30