Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/23/2025 Last Data Refresh: 02/22/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9802636 | Latitude | 25° 46' 23.3267 | ||||||||
Name |
SRCTD 44-200 LLC 200 SE 1ST ST #1002 |
Longitude | 80° 11' 24.3936 | ||||||||
MIAMI, FL 33131 | LL Method | DPHO | |||||||||
Contact | ARON MANDEL | LL Status | REVIEWED | ||||||||
Phone | (561) 421-3883 | Status Date | 02/05/2025 | ||||||||
Account Owner Information | |||||||||||
Name | SRCTD 44-200 LLC 2151 W HILLSBORO BLVD SUITE 204 DEERFIELD BEACH, FL 33442 |
Effective Date | 05/06/2022 | ||||||||
Contact | ARON MANDEL | ||||||||||
Phone | (561) 421-3883 | ||||||||||
ARON@STONEROCKCAP.COM | |||||||||||
Placard # / Date | 705146 - 02/11/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | SRCTD 44-200 LLC 2151 W HILLSBORO BLVD SUITE 204 DEERFIELD BEACH, FL 33442 |
Effective Date | 05/06/2022 | ||||||||
Contact | ARON MANDEL | ||||||||||
Phone | (561) 421-3883 | ||||||||||
ARON@STONEROCKCAP.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2500 | Emerg Generator Diesel (G) | 02/01/2000 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (I) Double wall (M) Spill containment bucket |
(A) Abv, no soil contact (B) Steel/galvanized metal (F) Double wall |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/01/2019 | 09/01/2020 | GREENWICH INSURANCE COMPANY | ||||||||
INSURANCE | 03/01/2017 | 03/01/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2016 | 03/01/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2015 | 03/01/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2014 | 03/01/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2013 | 03/01/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2012 | 03/01/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2011 | 03/01/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2010 | 03/01/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/01/2008 | 03/01/2009 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 08/18/2005 | 08/19/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 08/17/2005 | 08/19/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | RODRIGUEZ, J | 1/0 | COMPLIANCE ASSURANCE | |||||
TCR | 09/23/2004 | 09/27/2004 | IN-COMPLIANCE | RODRIGUEZ, J | 1/0 | COMPLIANCE ASSURANCE | |||||
TCI | 08/18/2004 | 08/19/2004 | MINOR OUT-OF-COMPLIANCE | RODRIGUEZ, J | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 09/02/2003 | 09/12/2003 | ODANIEL, J | 1/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/25/2003 | 09/03/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | O'DANIEL, J | 1/0 | COMPLIANCE ASSURANCE | |||||
TCI | 11/12/2002 | 12/03/2002 | IN-COMPLIANCE | O'DANIEL, J | 1/0 | COMPLIANCE ASSURANCE | |||||
TCI | 10/23/2001 | 11/06/2001 | IN-COMPLIANCE | O'DANIEL, J | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 09/20/2000 | 09/20/2000 | FERNANDEZ, J | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/28/2000 | 08/03/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | FERNANDEZ, J | 1/0 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 02/05/2025 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Site Inspection | 02/05/2025 | Major Out of Compliance | SANPEDRO_A_2 | 1/0 | Routine Compliance | ||||||
Letter | 02/05/2025 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Electronic Communication | 01/06/2025 | Satisfied | SANPEDRO_A_2 | Routine Compliance | |||||||
Letter | 08/07/2020 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Site Inspection | 08/07/2020 | In Compliance | GODWIN_MR_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 07/30/2020 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Phone Conversation | 07/30/2020 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Letter | 01/12/2018 | Satisfied | CABRERA_VE_1 | Compliance Assistance | |||||||
Site Inspection | 01/12/2018 | In Compliance | CABRERA_VE_1 | 1/0 | Compliance Assistance | ||||||
Letter | 01/12/2018 | Satisfied | CABRERA_VE_1 | Compliance Assistance | |||||||
Site Inspection | 10/30/2017 | Minor Out of Compliance | CABRERA_VE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 10/17/2017 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Electronic Communication | 10/05/2017 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Electronic Communication | 07/20/2017 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Site Inspection | 05/12/2015 | In Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 05/11/2015 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Electronic Communication | 08/29/2013 | Satisfied | LINCHETA_CR_1 | Non-Compliance | |||||||
Site Inspection | 08/29/2013 | In Compliance | LINCHETA_CR_1 | 1/0 | Non-Compliance | ||||||
Record Document | 08/29/2013 | Satisfied | LINCHETA_CR_1 | Non-Compliance | |||||||
Site Inspection | 07/18/2013 | Minor Out of Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 07/18/2013 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Letter | 07/18/2013 | Satisfied | LINCHETA_CR_1 | Non-Compliance | |||||||
Site Inspection | 04/12/2013 | In Compliance | LINCHETA_CR_1 | 1/0 | Non-Compliance | ||||||
Site Inspection | 02/11/2013 | Minor Out of Compliance | LINCHETA_CR_1 | 1/0 | Non-Compliance | ||||||
Site Inspection | 12/21/2012 | Major Out of Compliance | LINCHETA_CR_1 | 1/0 | Routine Compliance | ||||||
Letter | 12/21/2012 | Satisfied | LINCHETA_CR_1 | Non-Compliance | |||||||
Site Inspection | 02/10/2011 | In Compliance | REID_MT_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 10/19/2010 | Closed Without Enforcement | SYKORA_JJ_1 | Enforcement | |||||||
Site Inspection | 06/27/2010 | In Compliance | REYES_D_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 11/24/2008 | Minor Out of Compliance | SYKORA_JJ_1 | 1/0 | Routine Compliance | ||||||
Enforcement Referral | 11/24/2008 | Accepted | SYKORA_JJ_1 | Enforcement | |||||||
Issue Document | 11/24/2008 | Satisfied | SYKORA_JJ_1 | Enforcement | |||||||
Letter | 11/24/2008 | Satisfied | SYKORA_JJ_1 | Non-Compliance | |||||||
Site Inspection | 08/17/2007 | In Compliance | PADRON_JE_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 08/25/2006 | In Compliance | RODRIGUEZ_Y_1 | 1/0 | Non-Compliance | ||||||
Site Inspection | 08/10/2006 | Major Out of Compliance | RODRIGUEZ_Y_1 | 1/0 | Routine Compliance | ||||||
Letter | 08/10/2006 | Satisfied | RODRIGUEZ_Y_1 | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/05/2025 | 7094 | Minor | 1.13 Permanent records not available within 5 working days notice. | Provide monthly visual and electronic release detection inspection logs. | |||||||
02/05/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide a current and passing annual operability test for the overfill protection device. | |||||||
02/05/2025 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Submit a registration form to the Florida Department of Environmental Protection (FDEP) to update: - the information for the account owner, the property owner, and the facility contacts - the tank’s construction and monitoring attributes | |||||||
02/05/2025 | 7009 | SNC-B | 1.7 No financial responsibility instrument or expired instrument for < 180 days. | Provide proof of financial responsibility for the tank. | |||||||
02/05/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide a current and passing annual operability test for the release detection device. | |||||||
02/05/2025 | 7091 | Minor | 3.15 Exterior Coatings not maintained to prevent corrosion. | Remove the heavy corrosion noted on some sections of the tank, the generator housing, and the metal platform supporting the tank and generator. | |||||||
No Discharges Found |