Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Retail Station | ||||||||
County | Collier | Status | OPEN | ||||||||
ID | 9803121 | Latitude | 26° 15' 2.8943 | ||||||||
Name |
TEXACO-ISLAND WALK 6155 TOWNCENTER CIR |
Longitude | 81° 42' 41.6106 | ||||||||
NAPLES, FL 34119-7517 | LL Method | DPHO | |||||||||
Contact | DAVID GIVNEY | LL Status | REVIEWED | ||||||||
Phone | (239) 513-0045 | Status Date | 09/21/2023 | ||||||||
Account Owner Information | |||||||||||
Name | ISLAND WALK HOMEOWNERS ASSOC INC 6155 TOWN CTR CIR #101 NAPLES, FL 34119 |
Effective Date | 09/01/2000 | ||||||||
Contact | MARK PUTHOFF | ||||||||||
Phone | (239) 513-0045 | ||||||||||
MPUTHOFF@KWPM.COMOM | |||||||||||
Placard # / Date | 692849 - 06/21/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | ISLAND WALK HOMEOWNERS ASSOC INC 6155 TOWN CTR CIR #101 NAPLES, FL 34119 |
Effective Date | 03/04/2003 | ||||||||
Contact | MARK PUTHOFF | ||||||||||
Phone | (239) 513-0045 | ||||||||||
MPUTHOFF@KWPM.COMOM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Unleaded Gas (B) | 05/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 05/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/01/2025 | 02/01/2026 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 02/01/2024 | 02/01/2025 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 02/01/2023 | 02/01/2024 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 02/01/2022 | 02/01/2023 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 02/01/2020 | 02/01/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 02/01/2019 | 02/01/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 02/01/2018 | 02/01/2019 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2017 | 02/01/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2016 | 02/01/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2015 | 02/01/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2014 | 02/01/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2013 | 02/01/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2011 | 02/01/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2010 | 02/01/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/01/2009 | 02/01/2010 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 01/31/2006 | 02/01/2006 | OWEN_JA | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes MLLD TEST RESULTS REC'D VIA FAX. ALL PASSED. | |||||||||||
FR | 01/24/2006 | 01/24/2006 | MINOR OUT-OF-COMPLIANCE | SNYDERBURN_P | 0/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes DURING NCLI DRAFT A SPECEFIC VIOLATION WAS FOUND FOR THE ANNUAL TESTING ON THE MLLD - 1103 AND ADDED AS A VIOLATION. | |||||||||||
TCI | 12/15/2005 | 01/12/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | OWEN_JA | /2 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PROOF OF OVERFILL. ANNUAL TESTS DUE MMLD WAS DUE 12/05. SENSORS DUE 1/06. VIOLATION #'S 1117, 1031 | |||||||||||
CWOE | 01/21/2005 | 01/25/2005 | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CLOSED #1117 | |||||||||||
RRBD | 01/21/2005 | 01/25/2005 | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REC'D SUMP & ANNULAR SENSOR TESTS...CLOSE #1117 | |||||||||||
NCLI | 01/10/2005 | 01/10/2005 | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NEEDS SUMP & INTERSTITIAL SENSORS TESTED | |||||||||||
RRBD | 12/20/2004 | 12/20/2004 | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | ||||||
Completion Notes ANNUAL TESTS FOR LEAK DETECTORS REC'D...#117 REMAINS OPEN ==> SUMP SENSORS & INTERSTITIAL SENSORS NEED ANNUAL OPERABILITY TESTS | |||||||||||
TCI | 12/16/2004 | 12/16/2004 | MINOR OUT-OF-COMPLIANCE | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes NEEDS ANNUAL TESTS | |||||||||||
TCI | 12/11/2003 | 12/11/2003 | IN-COMPLIANCE | KOLANDA | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: DW FIBERGLASS | |||||||||||
RRBD | 02/04/2003 | 02/25/2003 | HOGAN_S | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes LLD PASSED TEST. SUMP AND TANK INTERSTICE SENSORS PASSED TEST. FACILITY IS NOW IN COMPLIANCE. CLOSE 157/N. | |||||||||||
CWOE | 02/04/2003 | 02/25/2003 | HOGAN_S | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/03/2003 | 02/03/2003 | HOGAN_S | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NCLI FOR TCI DATED 1/28/03 | |||||||||||
TCI | 01/28/2003 | 01/29/2003 | MINOR OUT-OF-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes SUMP SENSORS, TANK INTERSTICE SENSORS AND LLD NEED ANNUAL OPERABILITY TEST | |||||||||||
TCI | 03/15/2002 | 03/15/2002 | IN-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes IN COMPLIANCE | |||||||||||
TIN | 05/24/2001 | 05/24/2001 | IN-COMPLIANCE | KOLANDA_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes TANK SENTINEL 1001 EQ-327...SUMP/TANK INTERSTICE EQ-456....LINE LEAK DETECTOR EQ-360 | |||||||||||
TIN | 06/30/2000 | 12/15/2000 | IN-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes HYDRO TEST ON SUMPS, SPILL BUCKETS, AND DISPENSER LINERS | |||||||||||
TIN | 06/06/2000 | 12/15/2000 | IN-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes SECONDARY PIPING INSATLLED. EQ# 378 | |||||||||||
TIN | 06/02/2000 | 12/15/2000 | IN-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes PRIMARY PIPING INSTALLED. EQ# 378 | |||||||||||
TIN | 04/13/2000 | 12/15/2000 | IN-COMPLIANCE | HOGAN_S | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes TANKS INSTALLED. EQ# 156 | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Tracking | 04/08/2025 | Closed Without Enforcement | GRAH_G | Enforcement | |||||||
Letter | 04/01/2025 | Satisfied | STANDIFORD_JA | Compliance Assistance | |||||||
Letter | 03/31/2025 | Satisfied | STANDIFORD_JA | Compliance Assistance | |||||||
Site Inspection | 03/31/2025 | Major Out of Compliance | STANDIFORD_JA | 0/2 | Routine Compliance | ||||||
Site Inspection | 03/27/2025 | Minor Out of Compliance | STANDIFORD_JA | 0/2 | Component Closure | ||||||
Enforcement Referral | 11/06/2024 | Accepted | HERNANDEZ_N_5 | Enforcement | |||||||
Electronic Communication | 11/03/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 11/03/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 10/14/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 10/13/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 09/08/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 08/26/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Letter | 08/08/2022 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 08/08/2022 | Satisfied | HERNANDEZ_N_5 | Routine Compliance | |||||||
Site Inspection | 08/08/2022 | Minor Out of Compliance | HERNANDEZ_N_5 | 0/2 | Routine Compliance | ||||||
Site Inspection | 07/27/2020 | In Compliance | HERNANDEZ_N_5 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 07/27/2020 | Satisfied | HERNANDEZ_N_5 | Routine Compliance | |||||||
Letter | 07/27/2020 | Satisfied | HERNANDEZ_N_5 | Routine Compliance | |||||||
Electronic Communication | 10/04/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Site Inspection | 10/04/2018 | In Compliance | BATES_TD_1 | 0/2 | Compliance Assistance | ||||||
Letter | 10/04/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/03/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/03/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/03/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Letter | 09/04/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Site Inspection | 09/04/2018 | Major Out of Compliance | BATES_TD_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 03/28/2016 | In Compliance | BATES_TD_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 06/29/2014 | In Compliance | SPARKS_JD_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 10/03/2013 | Satisfied | SNYDERBURN_PJ_2 | Routine Compliance | |||||||
Site Inspection | 06/20/2013 | In Compliance | SNYDERBURN_PJ_2 | 0/2 | Non-Compliance | ||||||
Letter | 02/27/2013 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 02/27/2013 | Major Out of Compliance | SNYDERBURN_PJ_2 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/25/2012 | Satisfied | SPARKS_JD_1 | Routine Compliance | |||||||
Site Inspection | 01/27/2012 | Minor Out of Compliance | SNYDERBURN_PJ_2 | 0/2 | Non-Compliance | ||||||
Site Inspection | 12/11/2011 | Minor Out of Compliance | SNYDERBURN_PJ_2 | 0/2 | Routine Compliance | ||||||
Letter | 12/11/2011 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 08/10/2010 | In Compliance | NOVAK_KM_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 07/22/2009 | In Compliance | NOVAK_KM_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 07/22/2009 | Satisfied | NOVAK_KM_1 | Routine Compliance | |||||||
Record Document | 08/05/2008 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 07/28/2008 | Minor Out of Compliance | WILSON_KM | 0/2 | Routine Compliance | ||||||
Letter | 07/28/2008 | Satisfied | WILSON_KM | Non-Compliance | |||||||
Record Document | 07/28/2008 | Satisfied | WILSON_KM | Non-Compliance | |||||||
Emergency Preparedness Information | 07/22/2008 | Satisfied | WILSON_KM | Routine Compliance | |||||||
Letter | 02/21/2007 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/12/2007 | Satisfied | POTTS_CR | Routine Compliance | |||||||
Site Inspection | 01/17/2007 | Minor Out of Compliance | POTTS_CR | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/28/2006 | Satisfied | OWEN_JA | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/19/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Within 90 days of the inspection date, please perform two months worth of MVI's and monthly ERD then email the completed MVI log/ associated ERD printouts to the Inspector within the same time frame. A MVI log was created for the facility and provided in a Compliance Assistance email (attachment) where all issues/violations observed during the TCI (attached below). Visual inspections. At least once a month, but not exceeding 35 days, every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances that can be inspected visually shall be visually inspected and documented as to its condition pursuant to Rule 62-761.710, F.A.C. Any visual inspection of a storage tank system that reveals uncontrolled pitting corrosion, structural damage, leakage, or other similar problems is considered a positive response. The positive response shall be recorded as part of the release detection records. Repairs shall be made in accordance with Rule 62-761.700, F.A.C. The positive response shall be reported and investigated as an incident pursuant to Rule 62-761.430, F.A.C., if it is determined that a release has occurred. A monthly visual inspection is not required for any system component using an electronic release detection method; however, piping and dispenser sumps that use an electronic release detection method must also be visually inspected every six months and records kept of the visual inspection. Electronic release detection devices shall be inspected for proper operation at least once every calendar month, but not exceeding 35 days. A record or summary of the alarm history, sensor status, and testing results related to potential releases shall be printed from any electronic release detection device and kept, or be provided to the county or Department upon request through electronic documentation. If the release detection system is not capable of printing records, a manual log shall be maintained of the alarm history, sensor status, and testing results. Associated records must then be maintained for three years thereafter. | |||||||
No Discharges Found |