Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | State Government | ||||||||
County | Leon | Status | OPEN | ||||||||
ID | 9803375 | Latitude | 30° 23' 10.5747 | ||||||||
Name |
FL DEPT MGMT SRVCS-SHARED RESOURCE CTR 2575 SHUMARD OAK BLVD |
Longitude | 84° 13' 54.1887 | ||||||||
TALLAHASSEE, FL 32399 | LL Method | DPHO | |||||||||
Contact | RICHARD WILLIAMS | LL Status | REVIEWED | ||||||||
Phone | (850) 528-9089 | Status Date | 05/27/2004 | ||||||||
Account Owner Information | |||||||||||
Name | FL DEPT MGMT SRVCS - BUREAU OF MAINT 4050 ESPLANADE WAY #315.9Z Tallahassee, FL 32399-950 |
Effective Date | 11/29/2000 | ||||||||
Contact | RANDI HEYS (850) 519-6625 | ||||||||||
Phone | (850) 922-7535 | ||||||||||
REDM_EHS_COORDINATOR@DMS.FL.GOV | |||||||||||
Placard # / Date | 699269 - 07/10/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | FL DEPT MGMT SRVCS - BUREAU OF MAINT 4050 ESPLANADE WAY #315.9Z Tallahassee, FL 32399-950 |
Effective Date | 11/29/2000 | ||||||||
Contact | RANDI HEYS (850) 519-6625 | ||||||||||
Phone | (850) 922-7535 | ||||||||||
REDM_EHS_COORDINATOR@DMS.FL.GOV | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Generator/Pump Diesel (H) | 04/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (P) Level gauges/alarms |
(I) Suction piping system (M) Double wall - pipe jacket (N) Approved synthetic material |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (I) Not required (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 6000 | Emerg Generator Diesel (G) | 05/01/2008 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(F) Double wall (V) Violation |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 09/04/2024 | 09/04/2034 | |||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 12/28/2008 | 12/28/2009 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 01/30/2006 | 01/31/2006 | IN-COMPLIANCE | HATCHER | 0/1 | COMPLIANCE ASSURANCE | |||||
TIN | 03/29/2005 | 03/30/2005 | IN-COMPLIANCE | HATCHER | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes UNDERGROUND GENERATOR TANK | |||||||||||
CWOE | 03/02/2004 | 03/02/2004 | HATCHER | 0/1 | COMPLIANCE ASSURANCE | ||||||
TCR | 03/02/2004 | 03/02/2004 | IN-COMPLIANCE | HATCHER | 0/1 | COMPLIANCE ASSURANCE | |||||
NCLI | 02/23/2004 | 02/23/2004 | FRENCH | 0/1 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/02/2004 | 02/23/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | HATCHER | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes PROVIDE OVERFILL PROTECTION | |||||||||||
TCI | 02/24/2003 | 02/25/2003 | IN-COMPLIANCE | HATCHER | 0/1 | COMPLIANCE ASSURANCE | |||||
NCLI | 02/27/2002 | 02/27/2002 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CONDUCT CLOSURE ASSESSMENT FOR THE REPLACEMENT OF THE SPILL CONTAINMENT BUCKET. | |||||||||||
TCI | 02/19/2002 | 02/27/2002 | MINOR OUT-OF-COMPLIANCE | ROSS | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 02/28/2001 | 03/05/2001 | IN-COMPLIANCE | SHEFFIELD | 0/1 | COMPLIANCE ASSURANCE | |||||
TIN | 11/20/2000 | 11/29/2000 | IN-COMPLIANCE | SHEFFIELD/ROSS | 0/1 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 03/25/2025 | Accepted | FRENCH_EC_1 | Enforcement | |||||||
Site Inspection | 09/11/2024 | Minor Out of Compliance | FRENCH_EC_1 | 1/1 | Routine Compliance | ||||||
Letter | 09/11/2024 | Satisfied | FRENCH_EC_1 | Compliance Assistance | |||||||
Letter | 08/30/2022 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Site Inspection | 08/30/2022 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Electronic Communication | 10/21/2020 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 08/06/2020 | Minor Out of Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Letter | 08/06/2020 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 07/11/2018 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 10/14/2016 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 10/23/2015 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 09/17/2014 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 05/30/2014 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 08/29/2013 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 07/31/2012 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 08/09/2011 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 09/27/2010 | In Compliance | HATCHER_JD_1 | 1/1 | Non-Compliance | ||||||
Record Document | 09/20/2010 | Satisfied | FRENCH_EC_1 | Non-Compliance | |||||||
Site Inspection | 09/09/2010 | Major Out of Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Letter | 09/09/2010 | Satisfied | HATCHER_JD_1 | Non-Compliance | |||||||
Site Inspection | 05/03/2010 | In Compliance | FRENCH_EC_1 | 1/1 | Installation | ||||||
Site Inspection | 05/03/2010 | Major Out of Compliance | FRENCH_EC_1 | 1/1 | Closure | ||||||
Site Inspection | 08/25/2009 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 10/07/2008 | In Compliance | FRENCH_EC_1 | 1/0 | Installation | ||||||
Site Inspection | 10/07/2008 | In Compliance | HATCHER_JD_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 10/10/2007 | In Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 12/28/2006 | In Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
09/11/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide current annual operability test results for the release detection to this department. | |||||||
09/11/2024 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Provide A//B operator training certificate for the operation of the under ground storage tank. | |||||||
09/11/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide current annual operability test results for the release detection (interstitial sensor/ATG) to this department. | |||||||
09/11/2024 | 6024 | Minor | 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. | Provide current three year hydro testing for the piping sumps and spill buckets on the under ground storage tank system to this department. | |||||||
09/11/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide current annual operability test results for the overfill protection (audible alarm) on the AST. | |||||||
09/11/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Provide current overfill protection test results for the UST to this department. | |||||||
No Discharges Found |