Report Run Date: 03/14/2025        Last Data Refresh: 03/13/2025        Report Generated from DOPPLER
 
District South   Type    Retail Station
 
County Sarasota   Status    OPEN
 
ID 9803498   Latitude    27° 16' 6.3403
 
Name Jafco petro inc
5808 S TAMIAMI TRL
Longitude    82° 31' 49.0369
  SARASOTA, FL 34231-3928 LL Method    DPHO
 
Contact Muhammad Jafri   LL Status    REVIEWED
 
Phone (561) 756-5987   Status Date    11/10/2015
 
Account Owner Information
 
Name STUART PETRO HOLDINGS LLC
2995 SE DIXIE HWY
Stuart, FL 34994
Effective Date    05/24/2023
 
Contact JAFRI MUHAMMAD
 
Phone (561) 756-5987
 
Email PAOLA@UNITEDPETROMANAGEMENT.COM
  Placard # / Date    703164 - 10/28/2024
Property Owner Information
 
Name FLORIDA GNCW LLC
5808 S Tamiami Trl
Sarasota, FL 34231-3928
Effective Date    06/14/2021
 
Contact David Lee
 
Phone (407) 765-6455
 
Email SHELLSTATION163798@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 15000 Unleaded Gas (B) 01/01/2001 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 01/01/2001 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/01/2023 06/01/2024 ACE AMERICAN INSURANCE COMPANY
LETTER OF CREDIT   05/31/2019 01/31/2021
INSURANCE   12/31/2017 12/31/2018 SCOTTSDALE INSURANCE COMPANY
INSURANCE   01/01/2016 12/31/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2014 12/31/2015 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2012 12/31/2014 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2011 12/31/2012 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2010 12/31/2011 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2009 12/31/2010 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2008 12/31/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 11/14/2005 12/05/2005 IN-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
RRBD 11/14/2005 12/05/2005 IN-COMPLIANCE WALL 0/0 COMPLIANCE ASSURANCE
 
TCR 04/18/2005 04/19/2005 MINOR OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TIN 04/18/2005 04/19/2005 IN-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TXI 04/18/2005 04/19/2005 IN-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TCR 03/24/2005 03/28/2005 SIGNIFICANT OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TCI 12/09/2004 12/13/2004 SIGNIFICANT OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
RRBD 05/17/2004 05/17/2004 IN-COMPLIANCE WALL 0/0 COMPLIANCE ASSURANCE
 
TCR 02/27/2004 03/01/2004 SIGNIFICANT OUT-OF-COMPLIANCE WALL /2 COMPLIANCE ASSURANCE
 
TCI 11/17/2003 11/18/2003 SIGNIFICANT OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TCR 12/26/2002 12/27/2002 IN-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TCI 11/13/2002 11/14/2002 MINOR OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
RRBD 12/12/2001 12/17/2001 WALL 0/0 COMPLIANCE ASSURANCE
 
TCI 11/19/2001 11/20/2001 MINOR OUT-OF-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
TIN 06/05/2001 06/07/2001 IN-COMPLIANCE WALL 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/12/2024 Accepted TYKOSKI_B_1 Enforcement
 
Site Inspection 05/28/2024 Minor Out of Compliance TYKOSKI_B_1 0/2 Routine Compliance
 
Electronic Communication 05/23/2024 Satisfied TYKOSKI_B_1 Routine Compliance
 
Electronic Communication 05/17/2024 Satisfied TYKOSKI_B_1 Routine Compliance
 
Enforcement Referral 12/13/2022 Accepted MURPHY_MA_1 Enforcement
 
Electronic Communication 08/18/2022 Satisfied MURPHY_MA_1 Compliance Assistance
 
Electronic Communication 07/27/2022 Satisfied MURPHY_MA_1 Compliance Assistance
 
Electronic Communication 02/25/2022 Satisfied MURPHY_MA_1 Routine Compliance
 
Electronic Communication 02/25/2022 Satisfied MURPHY_MA_1 Routine Compliance
 
Letter 02/25/2022 Satisfied MURPHY_MA_1 Compliance Assistance
 
Site Inspection 02/25/2022 Minor Out of Compliance MURPHY_MA_1 0/2 Routine Compliance
 
Phone Conversation 02/25/2022 Satisfied MURPHY_MA_1 Routine Compliance
 
Letter 05/06/2020 Satisfied GIANQUINTO_T_1 Routine Compliance
 
Site Inspection 05/06/2020 In Compliance MURPHY_MA_1 0/2 Routine Compliance
 
Electronic Communication 04/30/2020 Satisfied MURPHY_MA_1 Routine Compliance
 
Letter 06/21/2018 Satisfied MURPHY_MA_1 Compliance Assistance
 
Record Document 06/14/2018 Satisfied MURPHY_MA_1 Compliance Assistance
 
Letter 05/31/2018 Satisfied MURPHY_MA_1 Compliance Assistance
 
Electronic Communication 04/30/2018 Satisfied MURPHY_MA_1 Routine Compliance
 
Electronic Communication 04/30/2018 Satisfied MURPHY_MA_1 Routine Compliance
 
Site Inspection 04/30/2018 Minor Out of Compliance MURPHY_MA_1 0/2 Routine Compliance
 
Electronic Communication 02/25/2016 Satisfied RAMSEY_TH_2 Installation
 
Electronic Communication 02/25/2016 Satisfied RAMSEY_TH_2 Closure
 
Site Inspection 02/24/2016 In Compliance RAMSEY_TH_2 0/2 Installation
 
Site Inspection 02/24/2016 In Compliance RAMSEY_TH_2 0/2 Closure
 
Letter 12/03/2015 Satisfied WALL_KD_1 Non-Compliance
 
Site Inspection 11/12/2015 Major Out of Compliance WALL_KD_1 0/2 Routine Compliance
 
Phone Conversation 11/12/2015 Satisfied WALL_KD_1 Routine Compliance
 
Phone Conversation 11/12/2015 Satisfied WALL_KD_1 Routine Compliance
 
Issue Document 11/10/2015 Satisfied WALL_KD_1 Routine Compliance
 
Site Inspection 04/15/2014 In Compliance WALL_KD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 04/14/2014 Satisfied WALL_KD_1 Routine Compliance
 
Emergency Preparedness Information 04/11/2014 Satisfied WALL_KD_1 Routine Compliance
 
Site Inspection 12/12/2011 In Compliance WALL_KD_1 0/2 Non-Compliance
 
Record Document 10/05/2011 Satisfied WALL_KD_1 Non-Compliance
 
Letter 09/12/2011 Satisfied WALL_KD_1 Non-Compliance
 
Emergency Preparedness Information 09/09/2011 Satisfied WALL_KD_1 Routine Compliance
 
Site Inspection 09/09/2011 Minor Out of Compliance WALL_KD_1 0/2 Routine Compliance
 
Document Management 04/13/2011 Complete WALL_KD_1 Discharge
 
Discharge Reporting 04/13/2011 Satisfied WALL_KD_1 Discharge
 
Site Inspection 08/09/2010 In Compliance WALL_KD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 08/06/2010 Satisfied WALL_KD_1 Routine Compliance
 
Site Inspection 10/27/2009 In Compliance WALL_KD_1 0/2 Non-Compliance
 
Emergency Preparedness Information 10/19/2009 Satisfied WALL_KD_1 Routine Compliance
 
Record Document 10/19/2009 Satisfied WALL_KD_1 Routine Compliance
 
Letter 10/19/2009 Satisfied WALL_KD_1 Non-Compliance
 
Site Inspection 10/19/2009 Major Out of Compliance WALL_KD_1 0/2 Routine Compliance
 
Record Document 03/19/2009 Satisfied WALL_KD_1 Discharge
 
Letter 03/19/2009 Satisfied WALL_KD_1 Discharge
 
TCAR 03/04/2008 Satisfied WALL_KD_1 Closure
 
Site Inspection 12/12/2007 In Compliance WALL_KD_1 0/2 Installation
 
Site Inspection 12/11/2007 In Compliance WALL_KD_1 0/2 Closure
 
Site Inspection 11/16/2007 Major Out of Compliance WALL_KD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 11/16/2007 Satisfied WALL_KD_1 Routine Compliance
 
Letter 11/16/2007 Satisfied WALL_KD_1 Non-Compliance
 
Letter 02/28/2007 Satisfied WALL_KD_1 Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied WALL_KD_1 Routine Compliance
 
Site Inspection 11/27/2006 Minor Out of Compliance WALL_KD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 09/21/2006 Satisfied ANDERS_DT_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/23/2024 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Submit Registration Form to update current Property Owner information. When completed notify via email petroleumstorage@scgov.net.
 
05/17/2024 6066 Minor 4.4 Not repaired per applicable standards. 1. To restore the structural integrity of the storage tank system and in a manner that will prevent releases or discharges from structural failure or corrosion investigate severity of the corrosion on the Regular STP and components and repair as necessary. Email repair invoice or photo of repaired Regular STP and components to petroleumstorage@scgov.net. 2-5. To restore the structural integrity of the storage tank system and in a manner that will prevent releases or discharges from structural failure or corrosion investigate severity of the issues and repair/replace as necessary. Email repair invoice or photo of repaired/replaced components to petroleumstorage@scgov.net.
 
02/25/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Please provide passed integrity test for all sumps including; double wall spill buckets, dispenser sumps and STP sumps to this office by email
 
02/25/2022 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Overfill prevention system tested and provide certification to this office by email
 
02/25/2022 6062 Minor 2.5 Release detection devices not tested annually. Have release detection system tested and provide certification to this office by email
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/15/2009   COMPLETED 32