DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 01/22/2025        Last Data Refresh: 01/21/2025        Report Generated from DOPPLER
 
District Southeast   Type    Fuel user/Non-retail
 
County Broward   Status    OPEN
 
ID 9803662   Latitude    26° 10' 0
 
Name TIDES AT BRIDGESIDE SQUARE
3020 NE 32ND AVE
Longitude    80° 6' 10
  FORT LAUDERDALE, FL 33308 LL Method    AGPS
 
Contact CARMELA PALADINO   LL Status    REVIEWED
 
Phone (954) 630-1311   Status Date    06/24/2004
 
Account Owner Information
 
Name TIDES AT BRIDGESIDE SQUARE CONDO ASSOC
3020 NE 32ND AVE
FORT LAUDERDALE, FL 33308
Effective Date    08/07/2006
 
Contact CARMELA PALADINO
 
Phone (954) 630-1311
 
Email MANAGER@TIDESBRIDGESIDE.COM
  Placard # / Date    701843 - 10/03/2024
Property Owner Information
 
Name PAVADISIO AT BRIDGESIDE LLC
401 E LAS OLAS BLVD #1500
FORT LAUDERDALE, FL 33301
Effective Date    05/13/2004
 
Contact TOM BLUTH
 
Phone (954) 522-4800
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Generator/Pump Diesel (H) 11/01/2000 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (B) Steel/galvanized metal
(C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(M) Double wall - pipe jacket
(2) Visual inspect pipe sumps
(F) Monitor dbl wall tank space
(J) Monitor piping/liner space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   11/01/2024 11/01/2025 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   11/01/2022 11/01/2023 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   11/01/2020 11/01/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   11/01/2017 11/01/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   11/01/2015 11/01/2016 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   02/20/2014 02/20/2015 COMMERCE & INDUSTRY
INSURANCE   02/20/2012 02/20/2013 COMMERCE & INDUSTRY
INSURANCE   02/20/2011 02/20/2012 COMMERCE & INDUSTRY
INSURANCE   11/07/2009 11/07/2010 COMMERCE & INDUSTRY
INSURANCE   11/07/2008 11/07/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 07/20/2005 07/25/2005 IN-COMPLIANCE SINGER_S 0/1 COMPLIANCE ASSURANCE
 
TCI 07/02/2004 07/12/2004 IN-COMPLIANCE SINGER_S 0/1 COMPLIANCE ASSURANCE
 
TCI 04/15/2004 04/26/2004 SIGNIFICANT OUT-OF-COMPLIANCE SINGER_S 0/1 COMPLIANCE ASSURANCE
 
TCI 03/18/2003 08/29/2003 IN-COMPLIANCE GILLESPIE_D 0/1 COMPLIANCE ASSURANCE
 
LTR 11/08/2002 11/08/2002 PINE_CM 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED VIA FAX A COPY OF CFR ...
 
WLI 07/26/2002 07/31/2002 PINE_CM 0/0 COMPLIANCE ASSURANCE
 
CALL 07/22/2002 07/31/2002 PINE_CM 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SPOKE WITH JENNIFER SCOTT (954) 630-1311. SHE INFORMED ME THAT IN A TELEPHONE CONVERSATION WITHE HER CORPORATE OFFICE, SHE LEARNED THAT THIS FACILITY DOES NOT HAVE THIRD-PARTY STORAGE TANK LIABILITY INSURANCE.
 
CALL 07/19/2002 07/31/2002 PINE_CM 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes (1) SPOKE WITH JAMIE MORRELL, LEASING CONSULTANT (954) 630-1311. SHE AGREED TO HAVE HER ENGINEERING MGR. CALL BACK.
 
CALL 07/16/2002 07/31/2002 PINE_CM 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes LEFT MESSAGE FOR JENNIFER SCOTT, REQUESTING MISSING DOCUMENTATION NEEDED TO COMPLY.
 
CALL 06/17/2002 07/31/2002 GILLESPIE_D 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes CONTACTED JENNIFER SCOTT, (954) 630-1311, AND REQUESTED THIRD PARTY LIABILITY INSURANCE INFO/CFR ...
 
CALL 06/03/2002 07/31/2002 GILLESPIE_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes Received non-tank related insurance. Contacted Jennifer Scott, (954) 630-1311, and requested third party liability insurance info/CFR ...
 
TCI 03/29/2002 04/03/2002 SIGNIFICANT OUT-OF-COMPLIANCE GILLESPIE_D 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 11/08/2024 Major Out of Compliance BARRETT_RN_1 0/1 Routine Compliance
 
Letter 11/08/2024 Satisfied BARRETT_RN_1 Compliance Assistance
 
Electronic Communication 11/07/2024 Satisfied BARRETT_RN_1 Routine Compliance
 
Letter 07/14/2023 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Record Document 07/14/2023 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Enforcement Tracking 07/14/2023 Closed Without Enforcement KOENIG_EJ_1 Enforcement
 
Enforcement Referral 02/06/2023 Accepted KOENIG_EJ_1 Enforcement
 
Record Document 09/21/2022 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Site Inspection 08/18/2022 Major Out of Compliance GRAJEDACARDENAS_CJ_1 0/1 Routine Compliance
 
Letter 08/18/2022 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Electronic Communication 08/17/2022 Satisfied GRAJEDACARDENAS_CJ_1 Routine Compliance
 
Enforcement Tracking 12/27/2021 Closed Without Enforcement KOENIG_EJ_1 Enforcement
 
Letter 12/27/2021 Satisfied KOENIG_EJ_1 Enforcement
 
Record Document 12/23/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Letter 12/23/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Electronic Communication 12/02/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Electronic Communication 11/08/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Letter 10/05/2021 Satisfied KOENIG_EJ_1 Enforcement
 
Record Document 06/18/2021 Satisfied KOENIG_EJ_1 Compliance Assistance
 
Enforcement Referral 05/20/2021 Accepted KOENIG_EJ_1 Enforcement
 
Record Document 05/06/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Electronic Communication 04/29/2021 Satisfied MAXWELL_BC_1 Routine Compliance
 
Record Document 02/16/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Record Document 01/28/2021 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Letter 11/18/2020 Satisfied MAXWELL_BC_1 Compliance Assistance
 
Site Inspection 11/18/2020 Major Out of Compliance MAXWELL_BC_1 0/1 Routine Compliance
 
Phone Conversation 11/16/2020 Satisfied MAXWELL_BC_1 Routine Compliance
 
Phone Conversation 09/22/2020 Satisfied MAXWELL_BC_1 Routine Compliance
 
Letter 08/13/2018 Satisfied WICKE_CJ_1 Routine Compliance
 
Site Inspection 08/13/2018 In Compliance WICKE_CJ_1 0/1 Routine Compliance
 
Phone Conversation 07/30/2018 Satisfied WICKE_CJ_1 Routine Compliance
 
Site Inspection 08/30/2016 In Compliance WICKE_CJ_1 0/1 Routine Compliance
 
Phone Conversation 08/22/2016 Satisfied WICKE_CJ_1 Routine Compliance
 
Site Inspection 09/15/2014 In Compliance WICKE_CJ_1 0/1 Routine Compliance
 
Site Inspection 12/03/2012 In Compliance GILLESPIE_D_1 0/1 Routine Compliance
 
Site Inspection 08/11/2011 In Compliance GILLESPIE_D_1 0/1 Routine Compliance
 
Site Inspection 09/29/2010 In Compliance GILLESPIE_D_1 0/1 Routine Compliance
 
Site Inspection 10/20/2009 In Compliance GILLESPIE_D_1 0/1 Routine Compliance
 
Site Inspection 10/01/2008 In Compliance SINGER_SD_1 0/1 Routine Compliance
 
Site Inspection 07/16/2007 In Compliance SINGER_SD_1 0/1 Routine Compliance
 
Record Document 09/06/2006 Satisfied SINGER_SD_1 Non-Compliance
 
Site Inspection 07/25/2006 Minor Out of Compliance SINGER_SD_1 0/1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/07/2024 6024 Minor 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. Have annual operability integrity testing for single walled spill bucket completed. Provide results of testing to robarrett@broward.org
 
11/07/2024 6062 Minor 2.5 Release detection devices not tested annually. Have annual operability testing for tank's release detection conducted. Provide testing results to robarrett@broward.org
 
11/07/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Have annual operability testing for overfill protection completed. Provide testing results to robarrett@broward.org
 
11/05/2024 6075 Minor 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. Provide Class C Operator training to on staff personnel. Provide proof of certification to robarrett@broward.org
 
11/05/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair or replace tank's high-level alarm. Provide documentation of repair or replacement to robarrett@broward.org
 
 
 
No Discharges Found