DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Clay   Status    OPEN
 
ID 9804186   Latitude    30° 6' 5.7731
 
Name MURPHY USA #6686
1495 CR 220
Longitude    81° 42' 26.3781
  ORANGE PARK, FL 32003 LL Method    DGPS
 
Contact STORE MGR   LL Status    REVIEWED
 
Phone (904) 541-0221   Status Date    11/04/2003
 
Account Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    08/28/2001
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
  Placard # / Date    679936 - 06/05/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 21000 Unleaded Gas (B) 07/01/2001 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 21000 Unleaded Gas (B) 07/01/2001 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2023 04/30/2025
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2021 04/30/2023
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2018 05/01/2021
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2017 04/30/2018
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2016 04/30/2017
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2015 04/30/2016
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2014 04/30/2015
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2013 04/30/2014
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2012 04/30/2013
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/11/2011 04/30/2012
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2010 04/30/2011
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2009 04/30/2010
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2008 04/30/2009
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 09/27/2005 10/05/2005 IN-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LINE/LD TESTG 11/05/04 4/4 PASS
 
TCI 03/31/2004 04/13/2004 IN-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LINE/LD TEST 12/30/03 4/4 LINES AND 3/3 LD PASS ANNUAL OPERABILITY 12/31/03
 
RRBD 03/27/2003 03/27/2003 BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL OPERABILITY 3/6/03
 
RRBD 01/15/2003 03/27/2003 BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LEAK DETECTOR TEST 10/5/02 SENSOR OPERABILTIY TEST 10/5/02
 
TCI 11/22/2002 12/09/2002 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes DOUBLEWALL SYSTEM
 
TIN 08/02/2001 11/07/2001 IN-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 03/17/2025 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 03/11/2025 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 11/25/2024 Major Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 11/25/2024 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 11/25/2024 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 04/28/2023 Satisfied RAMSEY_TH_1 Closure
 
Document Management 04/28/2023 Satisfied RAMSEY_TH_1 Closure
 
TCAR 04/28/2023 Satisfied RAMSEY_TH_1 Closure
 
Site Inspection 04/27/2023 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Letter 04/27/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 04/27/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Incident 04/13/2023 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Document Management 01/22/2023 Satisfied HARRINGTON_RD_1 Incident
 
Letter 03/31/2022 Satisfied GOODMAN_TA_1 Discharge
 
Discharge Reporting 03/31/2022 Satisfied GOODMAN_TA_1 Discharge
 
Document Management 03/31/2022 Satisfied MACK_BT Discharge
 
Electronic Communication 03/31/2022 Satisfied GOODMAN_TA_1 Discharge
 
Document Management 03/31/2022 Satisfied GOODMAN_TA_1 Discharge
 
Letter 01/31/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Record Document 01/31/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 01/31/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 01/31/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 01/31/2021 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
TCAR 03/23/2020 Satisfied RAMSEY_TH_1 Closure
 
Electronic Communication 03/23/2020 Satisfied RAMSEY_TH_1 Closure
 
Letter 03/23/2020 Satisfied RAMSEY_TH_1 Closure
 
Site Inspection 04/29/2018 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Letter 04/29/2018 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 04/29/2018 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Phone Conversation 03/08/2016 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 03/08/2016 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 03/08/2016 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Incident 04/23/2014 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Site Inspection 01/03/2014 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 01/03/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 01/03/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Incident 12/03/2013 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Incident 11/06/2013 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Incident 10/28/2013 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Incident 09/24/2013 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Issue Document 12/14/2012 Satisfied DEFALCO_L Enforcement
 
Enforcement Tracking 12/14/2012 Closed Without Enforcement DEFALCO_L Enforcement
 
TCAR 11/08/2012 Satisfied RAMSEY_TH_1 Closure
 
Letter 11/08/2012 Satisfied RAMSEY_TH_1 Closure
 
Enforcement Referral 10/17/2012 Accepted DEFALCO_L Enforcement
 
Incident 10/15/2012 Has not led to Discharge HARRINGTON_RD_1 Incident
 
Letter 10/10/2012 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 10/05/2012 Minor Out of Compliance HARRINGTON_RD_1 0/2 Installation
 
Record Document 10/03/2012 Satisfied HARRINGTON_RD_1 Installation
 
Emergency Preparedness Information 03/02/2012 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 03/02/2012 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Site Inspection 04/26/2011 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Record Document 10/29/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Phone Conversation 05/14/2010 Satisfied DEFALCO_L Enforcement
 
Letter 04/21/2010 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 04/21/2010 Minor Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
Record Document 04/30/2009 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 12/10/2008 In Compliance BROWN_JZ 0/2 Non-Compliance
 
Letter 10/14/2008 Satisfied BROWN_JZ Non-Compliance
 
Site Inspection 10/14/2008 Minor Out of Compliance BROWN_JZ 0/2 Routine Compliance
 
Issue Document 10/19/2007 Satisfied DEFALCO_L Enforcement
 
Record Document 10/19/2007 Satisfied DEFALCO_L Enforcement
 
Enforcement Tracking 10/19/2007 Closed Without Enforcement DEFALCO_L Enforcement
 
Record Document 10/19/2007 Satisfied DEFALCO_L Non-Compliance
 
Site Inspection 09/27/2007 Major Out of Compliance DEFALCO_L 0/2 Enforcement
 
Enforcement Referral 09/11/2007 Accepted DEFALCO_L Enforcement
 
Record Document 05/03/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 03/14/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Emergency Preparedness Information 02/07/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Site Inspection 01/16/2007 Major Out of Compliance DOHANEY_T 0/2 QA/QC
 
Site Inspection 01/12/2007 Major Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
Letter 01/12/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Emergency Preparedness Information 09/21/2006 Satisfied BARNETT_PC_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/25/2024 6066 Minor 4.4 Not repaired per applicable standards. Provide updated RUL2 line leak detector test result documentation.
 
11/25/2024 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. Provide Incident Report and incident investigation results in regards to the failed tests of the RUL2 and PUL spill buckets.
 
11/25/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Make necessary repairs and provide updated spill bucket tests. Provide notification if the spill buckets will be replaced. Provide post repair tests of the spill buckets.
 
11/19/2024 6066 Minor 4.4 Not repaired per applicable standards. Open the piping test boot in the 87 stp sump.
 
11/19/2024 6066 Minor 4.4 Not repaired per applicable standards. Replace missing or loose shear valve anchor bolts in Dispensers 3/4 and 7/8. Provide verification.
 
11/19/2024 6066 Minor 4.4 Not repaired per applicable standards. Repair or replace the damaged entry boots in the 87 and 93 STP sumps. Provide post-repair hydrostatic test documentation.
 
11/19/2024 6066 Minor 4.4 Not repaired per applicable standards. Address the corrosion on both 87 STP sumps. Provide verification.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
11/30/2021   INACTIVE