Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 03/19/2025 Last Data Refresh: 03/18/2025 Report Generated from DOPPLER | |||||||
District | Northeast | Type | Retail Station | ||||
County | Clay | Status | OPEN | ||||
ID | 9804186 | Latitude | 30° 6' 5.7731 | ||||
Name |
MURPHY USA #6686 1495 CR 220 |
Longitude | 81° 42' 26.3781 | ||||
ORANGE PARK, FL 32003 | LL Method | DGPS | |||||
Contact | STORE MGR | LL Status | REVIEWED | ||||
Phone | (904) 541-0221 | Status Date | 11/04/2003 | ||||
Account Owner Information | |||||||
Name | MURPHY OIL USA INC 200 PEACH ST El Dorado, AR 71730 |
Effective Date | 08/28/2001 | ||||
Contact | KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE | ||||||
Phone | (870) 677-6116 | ||||||
KRYSTAL.TERRELL@MURPHYUSA.COM | |||||||
Placard # / Date | 679936 - 06/05/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 21000 | Unleaded Gas (B) | 07/01/2001 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 21000 | Unleaded Gas (B) | 07/01/2001 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 04/30/2023 | 04/30/2025 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2021 | 04/30/2023 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2018 | 05/01/2021 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2017 | 04/30/2018 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2016 | 04/30/2017 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2015 | 04/30/2016 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2014 | 04/30/2015 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2013 | 04/30/2014 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2012 | 04/30/2013 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/11/2011 | 04/30/2012 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2010 | 04/30/2011 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2009 | 04/30/2010 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2008 | 04/30/2009 | |||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 09/27/2005 | 10/05/2005 | IN-COMPLIANCE | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes LINE/LD TESTG 11/05/04 4/4 PASS | |||||||
TCI | 03/31/2004 | 04/13/2004 | IN-COMPLIANCE | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes LINE/LD TEST 12/30/03 4/4 LINES AND 3/3 LD PASS ANNUAL OPERABILITY 12/31/03 | |||||||
RRBD | 03/27/2003 | 03/27/2003 | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | ||
Completion Notes ANNUAL OPERABILITY 3/6/03 | |||||||
RRBD | 01/15/2003 | 03/27/2003 | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | ||
Completion Notes LEAK DETECTOR TEST 10/5/02 SENSOR OPERABILTIY TEST 10/5/02 | |||||||
TCI | 11/22/2002 | 12/09/2002 | MINOR OUT-OF-COMPLIANCE | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes DOUBLEWALL SYSTEM | |||||||
TIN | 08/02/2001 | 11/07/2001 | IN-COMPLIANCE | BARNETT_P | 0/2 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Enforcement Referral | 03/17/2025 | Accepted | HARRINGTON_RD_1 | Enforcement | |||
Electronic Communication | 03/11/2025 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||
Site Inspection | 11/25/2024 | Major Out of Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 11/25/2024 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Letter | 11/25/2024 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||
Letter | 04/28/2023 | Satisfied | RAMSEY_TH_1 | Closure | |||
Document Management | 04/28/2023 | Satisfied | RAMSEY_TH_1 | Closure | |||
TCAR | 04/28/2023 | Satisfied | RAMSEY_TH_1 | Closure | |||
Site Inspection | 04/27/2023 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Letter | 04/27/2023 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Electronic Communication | 04/27/2023 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Incident | 04/13/2023 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Document Management | 01/22/2023 | Satisfied | HARRINGTON_RD_1 | Incident | |||
Letter | 03/31/2022 | Satisfied | GOODMAN_TA_1 | Discharge | |||
Discharge Reporting | 03/31/2022 | Satisfied | GOODMAN_TA_1 | Discharge | |||
Document Management | 03/31/2022 | Satisfied | MACK_BT | Discharge | |||
Electronic Communication | 03/31/2022 | Satisfied | GOODMAN_TA_1 | Discharge | |||
Document Management | 03/31/2022 | Satisfied | GOODMAN_TA_1 | Discharge | |||
Letter | 01/31/2021 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Record Document | 01/31/2021 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Electronic Communication | 01/31/2021 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Electronic Communication | 01/31/2021 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||
Site Inspection | 01/31/2021 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
TCAR | 03/23/2020 | Satisfied | RAMSEY_TH_1 | Closure | |||
Electronic Communication | 03/23/2020 | Satisfied | RAMSEY_TH_1 | Closure | |||
Letter | 03/23/2020 | Satisfied | RAMSEY_TH_1 | Closure | |||
Site Inspection | 04/29/2018 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Letter | 04/29/2018 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Electronic Communication | 04/29/2018 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Phone Conversation | 03/08/2016 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Site Inspection | 03/08/2016 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 03/08/2016 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Incident | 04/23/2014 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Site Inspection | 01/03/2014 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Emergency Preparedness Information | 01/03/2014 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Electronic Communication | 01/03/2014 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Incident | 12/03/2013 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Incident | 11/06/2013 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Incident | 10/28/2013 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Incident | 09/24/2013 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Issue Document | 12/14/2012 | Satisfied | DEFALCO_L | Enforcement | |||
Enforcement Tracking | 12/14/2012 | Closed Without Enforcement | DEFALCO_L | Enforcement | |||
TCAR | 11/08/2012 | Satisfied | RAMSEY_TH_1 | Closure | |||
Letter | 11/08/2012 | Satisfied | RAMSEY_TH_1 | Closure | |||
Enforcement Referral | 10/17/2012 | Accepted | DEFALCO_L | Enforcement | |||
Incident | 10/15/2012 | Has not led to Discharge | HARRINGTON_RD_1 | Incident | |||
Letter | 10/10/2012 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Site Inspection | 10/05/2012 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/2 | Installation | ||
Record Document | 10/03/2012 | Satisfied | HARRINGTON_RD_1 | Installation | |||
Emergency Preparedness Information | 03/02/2012 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Site Inspection | 03/02/2012 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Site Inspection | 04/26/2011 | In Compliance | HARRINGTON_RD_1 | 0/2 | Routine Compliance | ||
Record Document | 10/29/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Phone Conversation | 05/14/2010 | Satisfied | DEFALCO_L | Enforcement | |||
Letter | 04/21/2010 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||
Site Inspection | 04/21/2010 | Minor Out of Compliance | BARNETT_PC_1 | 0/2 | Routine Compliance | ||
Record Document | 04/30/2009 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||
Site Inspection | 12/10/2008 | In Compliance | BROWN_JZ | 0/2 | Non-Compliance | ||
Letter | 10/14/2008 | Satisfied | BROWN_JZ | Non-Compliance | |||
Site Inspection | 10/14/2008 | Minor Out of Compliance | BROWN_JZ | 0/2 | Routine Compliance | ||
Issue Document | 10/19/2007 | Satisfied | DEFALCO_L | Enforcement | |||
Record Document | 10/19/2007 | Satisfied | DEFALCO_L | Enforcement | |||
Enforcement Tracking | 10/19/2007 | Closed Without Enforcement | DEFALCO_L | Enforcement | |||
Record Document | 10/19/2007 | Satisfied | DEFALCO_L | Non-Compliance | |||
Site Inspection | 09/27/2007 | Major Out of Compliance | DEFALCO_L | 0/2 | Enforcement | ||
Enforcement Referral | 09/11/2007 | Accepted | DEFALCO_L | Enforcement | |||
Record Document | 05/03/2007 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||
Letter | 03/14/2007 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||
Emergency Preparedness Information | 02/07/2007 | Satisfied | BARNETT_PC_1 | Routine Compliance | |||
Site Inspection | 01/16/2007 | Major Out of Compliance | DOHANEY_T | 0/2 | QA/QC | ||
Site Inspection | 01/12/2007 | Major Out of Compliance | BARNETT_PC_1 | 0/2 | Routine Compliance | ||
Letter | 01/12/2007 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||
Emergency Preparedness Information | 09/21/2006 | Satisfied | BARNETT_PC_1 | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
11/25/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Provide updated RUL2 line leak detector test result documentation. | |||
11/25/2024 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | Provide Incident Report and incident investigation results in regards to the failed tests of the RUL2 and PUL spill buckets. | |||
11/25/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Make necessary repairs and provide updated spill bucket tests. Provide notification if the spill buckets will be replaced. Provide post repair tests of the spill buckets. | |||
11/19/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Open the piping test boot in the 87 stp sump. | |||
11/19/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Replace missing or loose shear valve anchor bolts in Dispensers 3/4 and 7/8. Provide verification. | |||
11/19/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Repair or replace the damaged entry boots in the 87 and 93 STP sumps. Provide post-repair hydrostatic test documentation. | |||
11/19/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Address the corrosion on both 87 STP sumps. Provide verification. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
11/30/2021 | INACTIVE | ||||||