DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Bay   Status    OPEN
 
ID 9804977   Latitude    30° 11' 25.0706
 
Name CHEVRON FOOD MART-PC
1409N US HWY 231
Longitude    85° 38' 24.5335
  PANAMA CITY, FL 32401 LL Method    DPHO
 
Contact PAUL BAISCH   LL Status    REVIEWED
 
Phone (850) 774-5172   Status Date    02/07/2023
 
Account Owner Information
 
Name NORTH US 231 CENTER LLC
PO BOX 1565
LAWRENCEVILLE, GA 30046
Effective Date    06/10/2011
 
Contact SCOTT A MOON
 
Phone (770) 338-2620
 
Email PENNY@MAJORSMGMT.COM
  Placard # / Date    699093 - 07/09/2024
Property Owner Information
 
Name NORTH US 231 CENTER LLC
PO BOX 1565
LAWRENCEVILLE, GA 30046
Effective Date    06/10/2011
 
Contact SCOTT A MOON
 
Phone (770) 338-2620
 
Email PENNY@MAJORSMGMT.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 12000 Unleaded Gas (B) 07/01/2002 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 12000 Unleaded Gas (B) 07/01/2002 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   12/31/2023 12/31/2024 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2021 12/30/2022 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2020 12/31/2021 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2017 12/31/2018 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2017 12/31/2018 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2015 12/31/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2013 12/31/2014 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2012 12/31/2013 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/15/2012 12/31/2012 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/15/2011 04/15/2012 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   11/01/2010 11/01/2011 NAUTILUS INSURANCE COMPANY
INSURANCE   11/11/2009 11/11/2010 ZURICH-AMERICAN
INSURANCE   11/11/2009 11/11/2010 ZURICH-AMERICAN
INSURANCE   11/11/2007 11/11/2008 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 01/18/2006 01/19/2006 MINOR OUT-OF-COMPLIANCE KHAN 0/2 COMPLIANCE ASSURANCE
 
RRBD 01/28/2005 02/01/2005 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
TCI 01/20/2005 01/24/2005 MINOR OUT-OF-COMPLIANCE KHAN 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: APT DW
 
TCR 04/27/2004 05/04/2004 IN-COMPLIANCE KHAN 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: APT DW
 
RRBD 04/22/2004 04/23/2004 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
TCI 02/13/2004 02/16/2004 MINOR OUT-OF-COMPLIANCE PINKOVSKY 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: APT DW
 
TIN 12/20/2002 01/02/2003 IN-COMPLIANCE KHAN/PINKOVSKY 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 03/25/2025 Accepted GARTIN_D Enforcement
 
Electronic Communication 03/11/2025 Satisfied GARTIN_D Compliance Assistance
 
Enforcement Tracking 03/04/2025 Closed With Enforcement BRISTOL_S Enforcement
 
Letter 01/07/2025 Satisfied GARTIN_D Compliance Assistance
 
Site Inspection 12/20/2024 Major Out of Compliance GARTIN_D 0/2 Routine Compliance
 
Meeting 12/13/2024 Satisfied GARTIN_D Routine Compliance
 
Electronic Communication 12/13/2024 Satisfied GARTIN_D Routine Compliance
 
Letter 11/25/2024 Satisfied ELLIOTT_EV_1 Component Closure
 
TCAR 11/22/2024 Satisfied ELLIOTT_EV_1 Component Closure
 
Document Management 11/22/2024 Satisfied ELLIOTT_EV_1 Component Closure
 
Electronic Communication 06/06/2024 Satisfied BONDS_M Enforcement
 
Electronic Communication 06/06/2024 Satisfied BONDS_M Enforcement
 
Electronic Communication 06/14/2023 Satisfied MATHERLY_H Enforcement
 
Letter 04/05/2023 Satisfied MATHERLY_H Enforcement
 
Enforcement Referral 03/22/2023 Accepted KHAN_MR_1 Enforcement
 
Letter 12/22/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Phone Conversation 12/21/2022 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 12/21/2022 Major Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 03/07/2022 Satisfied WILSON_ML_1 Component Installation
 
Issue Document 03/07/2022 Satisfied WILSON_ML_1 Component Installation
 
Issue Document 02/14/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 02/14/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 02/10/2022 In Compliance KHAN_MR_1 0/2 Component Installation
 
TCAR 02/08/2022 Satisfied WILSON_ML_1 Component Closure
 
Document Management 02/08/2022 Satisfied WILSON_ML_1 Component Closure
 
Issue Document 02/08/2022 Satisfied WILSON_ML_1 Component Closure
 
Letter 02/08/2022 Satisfied WILSON_ML_1 Component Closure
 
Document Management 01/11/2022 Satisfied WILSON_ML_1 Component Closure
 
Letter 01/11/2022 Satisfied WILSON_ML_1 Component Closure
 
Issue Document 01/11/2022 Satisfied WILSON_ML_1 Component Closure
 
Issue Document 01/10/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 01/10/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 05/03/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 05/03/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 04/29/2021 Satisfied KHAN_MR_1 Compliance Assistance
 
Record Document 03/16/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 02/01/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 02/01/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 01/29/2021 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Phone Conversation 01/14/2021 Satisfied KHAN_MR_1 Routine Compliance
 
Enforcement Tracking 08/19/2019 Closed Without Enforcement BRISTOL_S Enforcement
 
Enforcement Referral 05/22/2019 Accepted KHAN_MR_1 Enforcement
 
Site Inspection 10/23/2018 Minor Out of Compliance BROCK_SN_1 0/2 Complaint
 
Issue Document 10/01/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 10/01/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 09/28/2018 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Document Management 08/16/2018 Satisfied KHAN_MR_1 Discharge
 
Discharge Reporting 08/15/2018 Satisfied KHAN_MR_1 Discharge
 
Letter 08/13/2018 Satisfied WILSON_ML_1 Discharge
 
Site Inspection 08/13/2018 In Compliance KHAN_MR_1 0/2 Discharge
 
Record Document 06/15/2016 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 03/28/2016 Satisfied WILSON_ML_1 Non-Compliance
 
Letter 02/29/2016 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 02/26/2016 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 04/25/2014 Satisfied DAURIA_KL_1 Closure
 
TCAR 04/25/2014 Satisfied DAURIA_KL_1 Closure
 
Record Document 04/24/2014 Satisfied FOXWORTH_S_1 Closure
 
Document Management 04/21/2014 Complete DAURIA_KL_1 Closure
 
Enforcement Tracking 02/28/2014 Closed Without Enforcement BRISTOL_S Enforcement
 
Site Inspection 02/28/2014 In Compliance KHAN_MR_1 0/2 Installation
 
Site Inspection 02/28/2014 In Compliance KHAN_MR_1 0/2 Closure
 
Letter 01/10/2014 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 01/10/2014 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 01/10/2014 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Enforcement Referral 10/30/2013 Cancelled BRISTOL_S Enforcement
 
Phone Conversation 10/15/2013 Satisfied BRISTOL_S Enforcement
 
Electronic Communication 09/09/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 07/24/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 07/23/2013 Minor Out of Compliance KHAN_MR_1 0/2 Non-Compliance
 
Record Document 06/11/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Record Document 01/24/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Emergency Preparedness Information 12/21/2012 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 12/21/2012 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 12/21/2012 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 12/19/2012 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 03/15/2012 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Emergency Preparedness Information 03/15/2012 Satisfied KHAN_MR_1 Routine Compliance
 
Enforcement Tracking 08/24/2011 Closed Without Enforcement GILLMAN_M Enforcement
 
Site Inspection 08/24/2011 In Compliance GILLMAN_M 0/2 Enforcement
 
Site Inspection 08/23/2011 In Compliance BRAZILE_DO_1 0/2 Non-Compliance
 
Document Management 07/03/2011 Complete BRAZILE_DO_1 Closure
 
Document Management 06/06/2011 Complete BRAZILE_DO_1 Non-Compliance
 
Site Inspection 05/14/2011 Minor Out of Compliance KHAN_MR_1 0/2 Closure
 
Site Inspection 05/14/2011 Minor Out of Compliance KHAN_MR_1 0/2 Installation
 
Record Document 10/29/2010 Satisfied BRISTOL_S Enforcement
 
Electronic Communication 10/29/2010 Satisfied BRISTOL_S Enforcement
 
Phone Conversation 10/29/2010 Satisfied BRISTOL_S Enforcement
 
Letter 10/11/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 09/24/2010 Minor Out of Compliance BRAZILE_DO_1 0/2 Routine Compliance
 
Issue Document 09/14/2010 Satisfied BRISTOL_S Enforcement
 
Record Document 09/07/2010 Satisfied BRISTOL_S Enforcement
 
Discharge Reporting 06/18/2010 Satisfied BRAZILE_DO_1 Discharge
 
Letter 06/17/2010 Satisfied BRAZILE_DO_1 Non-Compliance
 
Document Management 06/17/2010 Complete BRAZILE_DO_1 Discharge
 
Enforcement Referral 06/17/2010 Accepted BRISTOL_S Enforcement
 
TCAR 06/17/2010 Satisfied BRAZILE_DO_1 Closure
 
Site Inspection 06/16/2010 Minor Out of Compliance BRAZILE_DO_1 0/2 Discharge
 
Letter 06/16/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Letter 06/16/2010 Satisfied PIERCE_LL_1 Discharge
 
Site Inspection 02/22/2010 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 02/22/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 12/02/2009 In Compliance BRAZILE_DO_1 0/2 Installation
 
Site Inspection 11/19/2009 In Compliance BRAZILE_DO_1 0/2 Closure
 
Record Document 01/06/2009 Satisfied BRAZILE_DO_1 Non-Compliance
 
Letter 11/07/2008 Satisfied BRAZILE_DO_1 Non-Compliance
 
Enforcement Referral 11/03/2008 Accepted GILLMAN_M Enforcement
 
Site Inspection 10/30/2008 Minor Out of Compliance BRAZILE_DO_1 0/2 Routine Compliance
 
Emergency Preparedness Information 10/30/2008 Satisfied BRAZILE_DO_1 Routine Compliance
 
Record Document 10/24/2008 Satisfied KHAN_MR_1 Routine Compliance
 
Phone Conversation 10/23/2008 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 10/23/2008 In Compliance KHAN_MR_1 0/2 Non-Compliance
 
Emergency Preparedness Information 04/14/2008 Satisfied BRAZILE_DO_1 Routine Compliance
 
Letter 01/17/2008 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 12/07/2007 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Emergency Preparedness Information 05/21/2007 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 04/04/2007 In Compliance KHAN_MR_1 0/2 Routine Compliance
 
Emergency Preparedness Information 02/08/2007 Satisfied BRAZILE_DO_1 Routine Compliance
 
Emergency Preparedness Information 09/19/2006 Satisfied KHAN_MR_1 Routine Compliance
 
Record Document 06/23/2006 Satisfied BRAZILE_DO_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/20/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified contractor provide completed testing that shows the vacuum testing conducted passed for the double wall spill buckets.
 
12/20/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. A certified contractor must properly cap and seal electrical wires and conduits to prevent potential hazards posed by exposed wires. Submit associated information of detailed work invoice and photographs to Daniel.Gartin@flhealth.gov for resolving this violation.
 
12/20/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have the premium spill bucket gauge replaced by a certified contractor and submit associated testing of the gauge and a vacuum integrity testing of the premium spill bucket to Daniel.Gartin@flhealth.gov.
 
12/20/2024 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Have the registration updated to tank 1 and tank 2 to the proper content code of the fuel present in the tank. Send information to Daniel.Gartin@flhealth.gov showing the registration information is updated.
 
12/19/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. The liquid needs to be removed from the interstitial space of the premium and diesel spill bucket and determine if the bucket's integrity is compromised. Submit the integrity testing of the premium and diesel double wall spill bucket with photograph and the work invoice detailing the source of the liquid intrusion to Daniel.Gartin@flhealth.gov
 
12/19/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove the liquid from the double wall spill buckets and STP sump and submit a detailed work invoice or photograph showing liquid has been removed to Daniel.Gartin@flhealth.gov
 
12/18/2024 6002 Minor 2.1 Operator Training records not available. During the operation hours of a facility, at least a Class A, Class B, or Class C operator must be present during normal course of business. Provide Class C training to all individuals that may be left on shift and provide the copies of the Class C Operator Training Certificate to Daniel.Gartin@flhealth.gov.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
07/02/2018   COMPLETED
 
12/06/2009   COMPLETED 30