Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Collection Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 9805795 | Latitude | 28° 7' 6.7541 | ||||||||
Name |
WAL-MART SUPERCENTER #1245 5800 US 98 N |
Longitude | 81° 58' 36.1251 | ||||||||
LAKELAND, FL 33809 | LL Method | DPHO | |||||||||
Contact | DUSTIN NEWMAN | LL Status | REVIEWED | ||||||||
Phone | (863) 859-3626 | Status Date | 10/04/2023 | ||||||||
Account Owner Information | |||||||||||
Name | WAL-MART STORES EAST LP C/O APTIM 8725 Rosehill Rd Lenexa, KS 66215-4611 |
Effective Date | 06/04/2003 | ||||||||
Contact | LICENSING SUPPORT | ||||||||||
Phone | (877) 829-5505 | ||||||||||
WALMARTEPMSUPPORT@APTIM.COM | |||||||||||
Placard # / Date | 681408 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | WAL-MART STORES EAST LP C/O APTIM 8725 Rosehill Rd Lenexa, KS 66215-4611 |
Effective Date | 06/04/2003 | ||||||||
Contact | LICENSING SUPPORT | ||||||||||
Phone | (877) 829-5505 | ||||||||||
WALMARTEPMSUPPORT@APTIM.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 800 | Waste Oil (L) | 08/01/2000 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (F) Double wall (J) Pressurized piping system (N) Approved synthetic material |
(6) External piping monitoring (D) SPCC Plan (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
SG-1 | 1000 | Emerg Generator Diesel (G) | 02/01/2024 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(1) Continuous electronic sensing (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
SG-2 | 1000 | Emerg Generator Diesel (G) | 02/01/2024 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(1) Continuous electronic sensing (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
||||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 05/01/2019 | 05/01/2020 | INDIAN HARBOR INSURANCE COMPANY | ||||||||
INSURANCE | 05/01/2018 | 05/01/2019 | INDIAN HARBOR | ||||||||
INSURANCE | 05/01/2017 | 05/01/2018 | INDIAN HARBOR | ||||||||
INSURANCE | 05/30/2016 | 05/30/2017 | INDIAN HARBOR | ||||||||
INSURANCE | 05/30/2015 | 05/30/2016 | INDIAN HARBOR | ||||||||
INSURANCE | 05/30/2013 | 05/30/2014 | INDIAN HARBOR | ||||||||
INSURANCE | 05/30/2011 | 05/30/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 05/30/2010 | 05/30/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 05/30/2009 | 05/30/2010 | COMMERCE & INDUSTRY | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 06/23/2004 | 05/31/2005 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 05/03/2006 | 05/05/2006 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED PIPING PRESSURE TEST RESULTS, RESOLVES #58 & #2047. | |||||||||||
LTR | 04/05/2006 | 04/06/2006 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NCLI FOLLOW UP LETTER. | |||||||||||
NCLI | 12/09/2005 | 12/12/2005 | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: PRECISION TIGHTNESS TESTING, VISUAL INSPECTION DOCUMENTATION. | |||||||||||
NCLI | 12/09/2005 | 12/12/2005 | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: PRECISION TIGHTNESS TEST. | |||||||||||
TIN | 11/28/2005 | 12/12/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes FIVE PHOTOS. INSTALLED: DOUBLE-WALLED, ENCIRON GEOFLEX D (EQ #511) GREEN UNDERGROUND PIPING WAS INSTALLED. | |||||||||||
TCI | 11/28/2005 | 12/12/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 12 PHOTOS. PIPING: SINGLE-WALLED, ABOVE GROUND ,STEEL THAT CONNECTS TO A DOUBLE-WALLED UNDERGROUND ENVIRON GEO-FLEX D FLEX PIPING. VIOLATIONS RESOLVED: 1, 3, 4, 6, 111, 118, 171, 172. | |||||||||||
SV | 02/16/2005 | 02/21/2005 | GONZALEZ_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 4 PHOTOS TAKEN. PRESSURE TEST UG PIPING & INSTALL OF BOOTS. BOOTS WITH TRANSPARENT MONITORING PIPES FOR INTERSTITIAL MONITORING OF DW PIPING WERE INSTALLED ON 2 USED OIL LINES. PIPING: GEO-FLEX D (ENVIRON 1560). | |||||||||||
TCI | 01/10/2005 | 01/11/2005 | IN-COMPLIANCE | GONZALEZ_J | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 2 PHOTOS TAKEN. PIPING-SINGLE WALL STEEL ABOVE GROUND AND UNDERGROUND FLEX. RESOLVES VIOLATON #52. | |||||||||||
NCLI | 05/23/2003 | 07/15/2003 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TIN | 05/15/2003 | 04/06/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | SACLARIDES_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 6 PHOTOS TAKEN. | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 07/30/2020 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 07/30/2020 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 07/30/2020 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Letter | 07/30/2020 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 07/29/2020 | Major Out of Compliance | GLENN_LE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 06/14/2019 | Satisfied | JARRETT_SE_1 | Complaint | |||||||
Site Inspection | 06/14/2019 | In Compliance | JARRETT_SE_1 | 1/0 | Complaint | ||||||
Issue Document | 06/14/2019 | Satisfied | JARRETT_SE_1 | Complaint | |||||||
Issue Document | 01/25/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 01/24/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 01/24/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Enforcement Referral | 01/24/2019 | Rejected | GLENN_LE_1 | Enforcement | |||||||
Electronic Communication | 01/18/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 01/17/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 11/21/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 07/03/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 06/01/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/01/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/01/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/01/2018 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Site Inspection | 05/25/2018 | Major Out of Compliance | GLENN_LE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 08/24/2015 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Site Inspection | 08/21/2015 | In Compliance | GLENN_LE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 12/20/2013 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Site Inspection | 12/20/2013 | In Compliance | NEWBERG_DR_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 06/25/2013 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Site Inspection | 06/25/2013 | In Compliance | NEWBERG_DR_1 | 1/0 | Routine Compliance | ||||||
Record Document | 08/23/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 07/29/2011 | Major Out of Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Letter | 07/29/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 10/26/2010 | In Compliance | SLAPPEY_WR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 07/29/2009 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 07/13/2009 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Record Document | 10/07/2008 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 09/30/2008 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 11/21/2007 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Letter | 06/07/2007 | Satisfied | CROWELL_MP | Non-Compliance | |||||||
Site Inspection | 03/19/2007 | In Compliance | DIXON_R | 1/0 | Routine Compliance | ||||||
Phone Conversation | 09/12/2006 | Satisfied | CROWELL_MP | Non-Compliance | |||||||
Site Inspection | 08/31/2006 | Minor Out of Compliance | CROWELL_MP | 1/0 | Installation | ||||||
Letter | 08/30/2006 | Satisfied | CROWELL_MP | Non-Compliance | |||||||
Site Inspection | 08/30/2006 | Minor Out of Compliance | CROWELL_MP | 1/0 | Routine Compliance | ||||||
Record Document | 08/28/2006 | Satisfied | CROWELL_MP | Installation | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
07/29/2020 | 5004 | Minor | 1.4 Registration fees not paid, placard not posted. | A copy of the registration placard must be obtained, posted at the facility and a copy submitted to this office. | |||||||
07/29/2020 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Proof of financial responsibility (a signed copy of the full policy – digital or hard copy) for the 2019 through 2021 coverage period must be provided to this office. | |||||||
07/29/2020 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Because all inspection records were available from January 2019 to present and performed once a month but not greater than 35 days apart, the violation will be resolved with the issuance of the Compliance Assistance Offer (CAO). | |||||||
07/29/2020 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Test records must be provided to this office or testing must be performed immediately with a copy of the results provided to this office. | |||||||
07/29/2020 | 5003 | Minor | 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. | Complete a Storage Tank Facility Registration Form and submit to this office. | |||||||
No Discharges Found |