DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 9806446   Latitude    28° 3' 27.7465
 
Name MURPHY USA #7072
2118 HWY 92 W
Longitude    81° 48' 54.0295
  AUBURNDALE, FL 33823 LL Method    DPHO
 
Contact STORE MGR   LL Status    REVIEWED
 
Phone (870) 862-6411   Status Date    01/25/2024
 
Account Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    03/25/2004
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
  Placard # / Date    679969 - 06/05/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 20000 Unleaded Gas (B) 03/01/2004 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(Z) DEP approved piping
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(A) Site Suitability Plan
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 20000 Unleaded Gas (B) 03/01/2004 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(Z) DEP approved piping
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(A) Site Suitability Plan
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   01/01/2021 04/30/2022
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2019 04/30/2020
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2016 04/30/2017
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2015 04/30/2016
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2014 04/30/2015
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2012 04/30/2013
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2011 04/30/2012
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2010 04/30/2011
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2009 04/30/2010
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 01/13/2005 02/10/2005 IN-COMPLIANCE CROWELL_M 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: PETRO TECHNIK UPP D/W SEMI-RIGID SYNTHETIC EQ-297.
 
RRBD 06/17/2004 06/21/2004 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED REQUESTED PAPERWORK FOR WELL. RESOLVES VIOLATION #92.
 
RRBD 05/10/2004 05/10/2004 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED DEP LETTER FOR APPROVAL OF THE UNIVERSAL 39-04 OVERFILL PROTECTION VALVE EQ-579.
 
NCLI 05/10/2004 05/10/2004 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
RRBD 05/07/2004 05/10/2004 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED RDRL. RESOLVES VIOLATION #118.
 
TIN 04/29/2004 05/10/2004 MINOR OUT-OF-COMPLIANCE JENKINS_N 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes 5 PHOTOS TAKEN. 4 FEPETRO STP-MLD MECHANICAL LLD EQ-335. 3 UNIVERSAL VENT LINE BALL CHECK VALVE MOD #37-206016, EQ-300. 3 UNIVERSAL DROP TUBE FLAPPER MOD #39-0710. 3 UNIVERSAL SPILL BUCKET MOD #69RT-1212FM NO EQ. VEEDER ROOT TLS 350 CONSOLE EQ-197.
 
SV 03/26/2004 04/05/2004 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes HYDRO-PRIMARY SECONDARY PIPING. 4 SUMPS-ADVANCED PLOYMER TECHNOLOGY ULC 13397. 10 DISPENSER LINERS-UPP. PIPING-UPP FLEX DOUBLE WALL EQ 297.
 
SV 03/01/2004 03/25/2004 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 1 PHOTO TAKEN. 2 20,000 GAL D/W FIBERGLASS CONTAINMENT SOLUTIONS MODEL DWT-6 TYPE II UST, EQ-191. UL65118 SINGLE COMPARTMENT (NORTH) REGULAR. UL65130 TWIN COMPARTMENT (SOUTH) 12K DIESEL & 8K PREMIUM.
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 07/15/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 07/15/2022 Satisfied CASSELS_CR_2 Routine Compliance
 
Letter 07/15/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Site Inspection 07/13/2022 Major Out of Compliance CASSELS_CR_2 0/2 Routine Compliance
 
Electronic Communication 08/13/2019 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 07/23/2019 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 07/13/2019 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 06/05/2019 Satisfied GLENN_LE_1 Routine Compliance
 
Letter 06/05/2019 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 06/05/2019 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 06/05/2019 Satisfied GLENN_LE_1 Routine Compliance
 
Site Inspection 06/04/2019 Major Out of Compliance GLENN_LE_1 0/2 Routine Compliance
 
Electronic Communication 01/05/2018 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 01/05/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 01/05/2018 Satisfied BROWNLEE_S Enforcement
 
Letter 01/05/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 01/05/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 01/05/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Enforcement Tracking 01/05/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Enforcement Referral 01/04/2018 Accepted WILLIAMSON_KE_1 Enforcement
 
Electronic Communication 12/27/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 12/20/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Discharge Reporting 05/11/2017 Satisfied JARRETT_SE_1 Discharge
 
Document Management 05/11/2017 Satisfied JARRETT_SE_1 Discharge
 
Discharge Reporting 05/11/2017 Satisfied JARRETT_SE_1 Discharge
 
Record Document 05/11/2017 Satisfied JARRETT_SE_1 Discharge
 
Electronic Communication 04/06/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Letter 03/29/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 03/29/2017 Major Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Electronic Communication 03/29/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 07/10/2015 In Compliance WILLIAMSON_KE_1 0/2 Non-Compliance
 
Electronic Communication 07/10/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 06/30/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Letter 03/13/2015 Satisfied JARRETT_SE_1 Non-Compliance
 
Electronic Communication 03/03/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 02/28/2015 Minor Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Site Inspection 01/03/2013 In Compliance NEWBERG_DR_1 0/2 Non-Compliance
 
Letter 10/17/2012 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 10/17/2012 Minor Out of Compliance NEWBERG_DR_1 0/2 Routine Compliance
 
Electronic Communication 06/11/2012 Satisfied DERY_WC_1 Discharge
 
TCAR 05/29/2012 Incomplete BELL_JM_1 Closure
 
Letter 05/10/2012 Satisfied BELL_JM_1 Discharge
 
Document Management 05/10/2012 Complete BELL_JM_1 Discharge
 
Record Document 05/10/2012 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 05/08/2012 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 04/30/2012 Satisfied DERY_WC_1 Closure
 
Electronic Communication 04/30/2012 Satisfied DERY_WC_1 Non-Compliance
 
Letter 04/16/2012 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 04/16/2012 Minor Out of Compliance DERY_WC_1 0/2 Installation
 
Letter 04/09/2012 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 04/09/2012 Minor Out of Compliance BELL_JM_1 0/2 Closure
 
Electronic Communication 03/28/2012 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 03/22/2012 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 01/31/2012 Satisfied BELL_JM_1 Non-Compliance
 
Letter 01/09/2012 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 12/21/2011 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 12/07/2011 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 11/22/2011 Minor Out of Compliance BELL_JM_1 0/2 Routine Compliance
 
Letter 11/22/2011 Satisfied BELL_JM_1 Non-Compliance
 
Electronic Communication 11/22/2011 Satisfied BELL_JM_1 Non-Compliance
 
Incident 11/22/2011 Has not led to Discharge BELL_JM_1 Incident
 
Phone Conversation 11/04/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Letter 11/04/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Record Document 09/24/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Letter 08/30/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 08/30/2010 Minor Out of Compliance CASSELS_CR_1 0/2 Routine Compliance
 
Site Inspection 09/24/2009 In Compliance DERY_WC_1 0/2 Non-Compliance
 
Record Document 09/21/2009 Satisfied DERY_WC_1 Non-Compliance
 
Letter 09/08/2009 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 09/08/2009 Minor Out of Compliance DERY_WC_1 0/2 Routine Compliance
 
Phone Conversation 07/27/2009 Satisfied DERY_WC_1 Routine Compliance
 
Phone Conversation 02/25/2009 Satisfied BELL_JM_1 Routine Compliance
 
Record Document 02/11/2009 Satisfied BELL_JM_1 Non-Compliance
 
Issue Document 02/06/2009 Satisfied BELL_JM_1 Non-Compliance
 
Issue Document 02/04/2009 Satisfied BELL_JM_1 Non-Compliance
 
Record Document 01/16/2009 Satisfied BELL_JM_1 Non-Compliance
 
Record Document 12/24/2008 Satisfied BELL_JM_1 Closure
 
Record Document 12/24/2008 Satisfied BELL_JM_1 Closure
 
Record Document 12/17/2008 Satisfied BELL_JM_1 Closure
 
Letter 12/09/2008 Satisfied BELL_JM_1 Non-Compliance
 
TCAR 12/08/2008 Satisfied BELL_JM_1 Closure
 
TCAR 11/12/2008 Satisfied BELL_JM_1 Closure
 
Letter 11/12/2008 Satisfied BELL_JM_1 Non-Compliance
 
Record Document 11/12/2008 Satisfied BELL_JM_1 Closure
 
Site Inspection 11/10/2008 Minor Out of Compliance BELL_JM_1 0/2 Routine Compliance
 
Letter 10/28/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 10/28/2008 Minor Out of Compliance CASSELS_CR_1 0/1 Installation
 
Letter 10/22/2008 Satisfied BELL_JM_1 Discharge
 
Letter 10/22/2008 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 10/22/2008 Minor Out of Compliance BELL_JM_1 0/2 Closure
 
Record Document 06/10/2008 Satisfied DERY_WC_1 Non-Compliance
 
Letter 04/28/2008 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 04/28/2008 Minor Out of Compliance DERY_WC_1 0/2 Routine Compliance
 
Phone Conversation 04/02/2008 Satisfied DERY_WC_1 Routine Compliance
 
Emergency Preparedness Information 05/22/2007 Satisfied COOK_JH_1 Routine Compliance
 
Emergency Preparedness Information 02/14/2007 Satisfied COOK_JH_1 Routine Compliance
 
Emergency Preparedness Information 02/14/2007 Satisfied COOK_JH_1 Routine Compliance
 
Site Inspection 11/28/2006 In Compliance NEWBERG_DR_1 0/2 Routine Compliance
 
Phone Conversation 11/28/2006 Satisfied NEWBERG_DR_1 Routine Compliance
 
Emergency Preparedness Information 10/02/2006 Satisfied COOK_JH_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
07/13/2022 6048 SNC-B 4.4 Dispenser sumps not installed to allow for release detection. The dispenser liner footprint must be large enough to encompass all dispenser mechanisms above it, in case of leakage, or a device must be installed to divert any leaking product into the liner, and the Department notified.
 
07/13/2022 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Any leaking component in the Regular East STP sump must be repaired and the PCW removed from the sump and the Department notified.
 
07/13/2022 6060 SNC-B 4.11 Release detection methods do not meet monitoring requirements. The double-walled piping secondary boot jumper tubes either have to be connected on both sides to maintain continuity back to the STP sump, or open in the dispenser liners, to avoid isolating any portion of the piping from either the dispenser sump or the STP sump, for interstitial monitoring.
 
05/31/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. An Incident Notification Form (INF) must be completed and provided to the Department.
 
05/31/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. An investigation must be performed to determine the cause of the failure with the results and repair documentation sent to the Department.
 
05/30/2019 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. Financial Responsibility Mechanism Part A must be completed by the Financial Officer and a CFR-Part P form completed by facility personnel for the 05/01/2017 to 05/01/2019 coverage period and copies provided to the Department.
 
05/30/2019 4014 SNC-B 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. Proof of Financial Responsibility for the 05/01/2017 to 05/01/2019 coverage period must be provided to the Department.
 
05/30/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. Documentation must be provided or an Incident Notification Form (INF) completed and provided to the Department for each alarm.
 
05/30/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Documentation must be provided or an Incident Notification Form (INF) completed and an investigation performed to determine the cause of the alarms with the results sent to the Department.
 
05/30/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Dirt, debris and liquid must be removed from all dispenser sumps to ensure a thorough inspection and the Department notified.
 
05/30/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Corrosion must be removed and the STPs and associated metal components treated to maintain corrosion protection.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
05/09/2012   COMPLETED 30
 
10/15/2008   COMPLETED