Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Retail Station | ||||
County | Polk | Status | OPEN | ||||
ID | 9806446 | Latitude | 28° 3' 27.7465 | ||||
Name |
MURPHY USA #7072 2118 HWY 92 W |
Longitude | 81° 48' 54.0295 | ||||
AUBURNDALE, FL 33823 | LL Method | DPHO | |||||
Contact | STORE MGR | LL Status | REVIEWED | ||||
Phone | (870) 862-6411 | Status Date | 01/25/2024 | ||||
Account Owner Information | |||||||
Name | MURPHY OIL USA INC 200 PEACH ST El Dorado, AR 71730 |
Effective Date | 03/25/2004 | ||||
Contact | KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE | ||||||
Phone | (870) 677-6116 | ||||||
KRYSTAL.TERRELL@MURPHYUSA.COM | |||||||
Placard # / Date | 679969 - 06/05/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 20000 | Unleaded Gas (B) | 03/01/2004 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (Z) DEP approved piping |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (A) Site Suitability Plan (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 20000 | Unleaded Gas (B) | 03/01/2004 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (Z) DEP approved piping |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (A) Site Suitability Plan (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2021 | 04/30/2022 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2019 | 04/30/2020 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2016 | 04/30/2017 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2015 | 04/30/2016 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2014 | 04/30/2015 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2012 | 04/30/2013 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2011 | 04/30/2012 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2010 | 04/30/2011 | |||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2009 | 04/30/2010 | |||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 01/13/2005 | 02/10/2005 | IN-COMPLIANCE | CROWELL_M | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes NO PHOTOS TAKEN. PIPING: PETRO TECHNIK UPP D/W SEMI-RIGID SYNTHETIC EQ-297. | |||||||
RRBD | 06/17/2004 | 06/21/2004 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes RECEIVED REQUESTED PAPERWORK FOR WELL. RESOLVES VIOLATION #92. | |||||||
RRBD | 05/10/2004 | 05/10/2004 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes RECEIVED DEP LETTER FOR APPROVAL OF THE UNIVERSAL 39-04 OVERFILL PROTECTION VALVE EQ-579. | |||||||
NCLI | 05/10/2004 | 05/10/2004 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||
RRBD | 05/07/2004 | 05/10/2004 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes RECEIVED RDRL. RESOLVES VIOLATION #118. | |||||||
TIN | 04/29/2004 | 05/10/2004 | MINOR OUT-OF-COMPLIANCE | JENKINS_N | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes 5 PHOTOS TAKEN. 4 FEPETRO STP-MLD MECHANICAL LLD EQ-335. 3 UNIVERSAL VENT LINE BALL CHECK VALVE MOD #37-206016, EQ-300. 3 UNIVERSAL DROP TUBE FLAPPER MOD #39-0710. 3 UNIVERSAL SPILL BUCKET MOD #69RT-1212FM NO EQ. VEEDER ROOT TLS 350 CONSOLE EQ-197. | |||||||
SV | 03/26/2004 | 04/05/2004 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes HYDRO-PRIMARY SECONDARY PIPING. 4 SUMPS-ADVANCED PLOYMER TECHNOLOGY ULC 13397. 10 DISPENSER LINERS-UPP. PIPING-UPP FLEX DOUBLE WALL EQ 297. | |||||||
SV | 03/01/2004 | 03/25/2004 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes 1 PHOTO TAKEN. 2 20,000 GAL D/W FIBERGLASS CONTAINMENT SOLUTIONS MODEL DWT-6 TYPE II UST, EQ-191. UL65118 SINGLE COMPARTMENT (NORTH) REGULAR. UL65130 TWIN COMPARTMENT (SOUTH) 12K DIESEL & 8K PREMIUM. | |||||||
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Electronic Communication | 07/15/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||
Electronic Communication | 07/15/2022 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||
Letter | 07/15/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||
Site Inspection | 07/13/2022 | Major Out of Compliance | CASSELS_CR_2 | 0/2 | Routine Compliance | ||
Electronic Communication | 08/13/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||
Electronic Communication | 07/23/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||
Electronic Communication | 07/13/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||
Electronic Communication | 06/05/2019 | Satisfied | GLENN_LE_1 | Routine Compliance | |||
Letter | 06/05/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||
Electronic Communication | 06/05/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||
Electronic Communication | 06/05/2019 | Satisfied | GLENN_LE_1 | Routine Compliance | |||
Site Inspection | 06/04/2019 | Major Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 01/05/2018 | Satisfied | BROWNLEE_S | Enforcement | |||
Electronic Communication | 01/05/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 01/05/2018 | Satisfied | BROWNLEE_S | Enforcement | |||
Letter | 01/05/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 01/05/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 01/05/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Enforcement Tracking | 01/05/2018 | Closed Without Enforcement | BROWNLEE_S | Enforcement | |||
Enforcement Referral | 01/04/2018 | Accepted | WILLIAMSON_KE_1 | Enforcement | |||
Electronic Communication | 12/27/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 12/20/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Discharge Reporting | 05/11/2017 | Satisfied | JARRETT_SE_1 | Discharge | |||
Document Management | 05/11/2017 | Satisfied | JARRETT_SE_1 | Discharge | |||
Discharge Reporting | 05/11/2017 | Satisfied | JARRETT_SE_1 | Discharge | |||
Record Document | 05/11/2017 | Satisfied | JARRETT_SE_1 | Discharge | |||
Electronic Communication | 04/06/2017 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Letter | 03/29/2017 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Site Inspection | 03/29/2017 | Major Out of Compliance | WILLIAMSON_KE_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 03/29/2017 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Site Inspection | 07/10/2015 | In Compliance | WILLIAMSON_KE_1 | 0/2 | Non-Compliance | ||
Electronic Communication | 07/10/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Electronic Communication | 06/30/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Letter | 03/13/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||
Electronic Communication | 03/03/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||
Site Inspection | 02/28/2015 | Minor Out of Compliance | WILLIAMSON_KE_1 | 0/2 | Routine Compliance | ||
Site Inspection | 01/03/2013 | In Compliance | NEWBERG_DR_1 | 0/2 | Non-Compliance | ||
Letter | 10/17/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||
Site Inspection | 10/17/2012 | Minor Out of Compliance | NEWBERG_DR_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 06/11/2012 | Satisfied | DERY_WC_1 | Discharge | |||
TCAR | 05/29/2012 | Incomplete | BELL_JM_1 | Closure | |||
Letter | 05/10/2012 | Satisfied | BELL_JM_1 | Discharge | |||
Document Management | 05/10/2012 | Complete | BELL_JM_1 | Discharge | |||
Record Document | 05/10/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 05/08/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 04/30/2012 | Satisfied | DERY_WC_1 | Closure | |||
Electronic Communication | 04/30/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Letter | 04/16/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Site Inspection | 04/16/2012 | Minor Out of Compliance | DERY_WC_1 | 0/2 | Installation | ||
Letter | 04/09/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Site Inspection | 04/09/2012 | Minor Out of Compliance | BELL_JM_1 | 0/2 | Closure | ||
Electronic Communication | 03/28/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 03/22/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 01/31/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Letter | 01/09/2012 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 12/21/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 12/07/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Site Inspection | 11/22/2011 | Minor Out of Compliance | BELL_JM_1 | 0/2 | Routine Compliance | ||
Letter | 11/22/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Electronic Communication | 11/22/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Incident | 11/22/2011 | Has not led to Discharge | BELL_JM_1 | Incident | |||
Phone Conversation | 11/04/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Letter | 11/04/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Record Document | 09/24/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Letter | 08/30/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Site Inspection | 08/30/2010 | Minor Out of Compliance | CASSELS_CR_1 | 0/2 | Routine Compliance | ||
Site Inspection | 09/24/2009 | In Compliance | DERY_WC_1 | 0/2 | Non-Compliance | ||
Record Document | 09/21/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Letter | 09/08/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Site Inspection | 09/08/2009 | Minor Out of Compliance | DERY_WC_1 | 0/2 | Routine Compliance | ||
Phone Conversation | 07/27/2009 | Satisfied | DERY_WC_1 | Routine Compliance | |||
Phone Conversation | 02/25/2009 | Satisfied | BELL_JM_1 | Routine Compliance | |||
Record Document | 02/11/2009 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Issue Document | 02/06/2009 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Issue Document | 02/04/2009 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Record Document | 01/16/2009 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Record Document | 12/24/2008 | Satisfied | BELL_JM_1 | Closure | |||
Record Document | 12/24/2008 | Satisfied | BELL_JM_1 | Closure | |||
Record Document | 12/17/2008 | Satisfied | BELL_JM_1 | Closure | |||
Letter | 12/09/2008 | Satisfied | BELL_JM_1 | Non-Compliance | |||
TCAR | 12/08/2008 | Satisfied | BELL_JM_1 | Closure | |||
TCAR | 11/12/2008 | Satisfied | BELL_JM_1 | Closure | |||
Letter | 11/12/2008 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Record Document | 11/12/2008 | Satisfied | BELL_JM_1 | Closure | |||
Site Inspection | 11/10/2008 | Minor Out of Compliance | BELL_JM_1 | 0/2 | Routine Compliance | ||
Letter | 10/28/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Site Inspection | 10/28/2008 | Minor Out of Compliance | CASSELS_CR_1 | 0/1 | Installation | ||
Letter | 10/22/2008 | Satisfied | BELL_JM_1 | Discharge | |||
Letter | 10/22/2008 | Satisfied | BELL_JM_1 | Non-Compliance | |||
Site Inspection | 10/22/2008 | Minor Out of Compliance | BELL_JM_1 | 0/2 | Closure | ||
Record Document | 06/10/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Letter | 04/28/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||
Site Inspection | 04/28/2008 | Minor Out of Compliance | DERY_WC_1 | 0/2 | Routine Compliance | ||
Phone Conversation | 04/02/2008 | Satisfied | DERY_WC_1 | Routine Compliance | |||
Emergency Preparedness Information | 05/22/2007 | Satisfied | COOK_JH_1 | Routine Compliance | |||
Emergency Preparedness Information | 02/14/2007 | Satisfied | COOK_JH_1 | Routine Compliance | |||
Emergency Preparedness Information | 02/14/2007 | Satisfied | COOK_JH_1 | Routine Compliance | |||
Site Inspection | 11/28/2006 | In Compliance | NEWBERG_DR_1 | 0/2 | Routine Compliance | ||
Phone Conversation | 11/28/2006 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||
Emergency Preparedness Information | 10/02/2006 | Satisfied | COOK_JH_1 | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
07/13/2022 | 6048 | SNC-B | 4.4 Dispenser sumps not installed to allow for release detection. | The dispenser liner footprint must be large enough to encompass all dispenser mechanisms above it, in case of leakage, or a device must be installed to divert any leaking product into the liner, and the Department notified. | |||
07/13/2022 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Any leaking component in the Regular East STP sump must be repaired and the PCW removed from the sump and the Department notified. | |||
07/13/2022 | 6060 | SNC-B | 4.11 Release detection methods do not meet monitoring requirements. | The double-walled piping secondary boot jumper tubes either have to be connected on both sides to maintain continuity back to the STP sump, or open in the dispenser liners, to avoid isolating any portion of the piping from either the dispenser sump or the STP sump, for interstitial monitoring. | |||
05/31/2019 | 4012 | Minor | 2.3 For an incident, notification not received in a timely manner. | An Incident Notification Form (INF) must be completed and provided to the Department. | |||
05/31/2019 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | An investigation must be performed to determine the cause of the failure with the results and repair documentation sent to the Department. | |||
05/30/2019 | 4015 | Minor | 2.10 Incomplete documentation demonstrating financial responsibility. | Financial Responsibility Mechanism Part A must be completed by the Financial Officer and a CFR-Part P form completed by facility personnel for the 05/01/2017 to 05/01/2019 coverage period and copies provided to the Department. | |||
05/30/2019 | 4014 | SNC-B | 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. | Proof of Financial Responsibility for the 05/01/2017 to 05/01/2019 coverage period must be provided to the Department. | |||
05/30/2019 | 4012 | Minor | 2.3 For an incident, notification not received in a timely manner. | Documentation must be provided or an Incident Notification Form (INF) completed and provided to the Department for each alarm. | |||
05/30/2019 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | Documentation must be provided or an Incident Notification Form (INF) completed and an investigation performed to determine the cause of the alarms with the results sent to the Department. | |||
05/30/2019 | 4077 | Minor | 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. | Dirt, debris and liquid must be removed from all dispenser sumps to ensure a thorough inspection and the Department notified. | |||
05/30/2019 | 4068 | Minor | 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. | Corrosion must be removed and the STPs and associated metal components treated to maintain corrosion protection. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
05/09/2012 | COMPLETED | 30 | |||||
10/15/2008 | COMPLETED | ||||||