Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Manatee | Status | OPEN | ||||||||
ID | 9806520 | Latitude | 27° 23' 30.425 | ||||||||
Name |
LAKEWOOD RANCH MEDICAL CTR 8330 LAKEWOOD RANCH BLVD |
Longitude | 82° 26' 9.8046 | ||||||||
BRADENTON, FL 34202 | LL Method | DPHO | |||||||||
Contact | WALTER CARTER | LL Status | REVIEWED | ||||||||
Phone | (941) 782-2711 | Status Date | 07/14/2004 | ||||||||
Account Owner Information | |||||||||||
Name | LAKEWOOD RANCH MEDICAL CTR 8330 LAKEWOOD RANCH BLVD BRADENTON, FL 34202 |
Effective Date | 04/08/2004 | ||||||||
Contact | WALTER CARTER | ||||||||||
Phone | (941) 783-2711 | ||||||||||
WALTER.CARTER@LWRMC.COM | |||||||||||
Placard # / Date | 702286 - 10/17/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | LAKEWOOD RANCH MEDICAL CTR 8330 LAKEWOOD RANCH BLVD BRADENTON, FL 34202 |
Effective Date | 04/08/2004 | ||||||||
Contact | WALTER CARTER | ||||||||||
Phone | (941) 783-2711 | ||||||||||
WALTER.CARTER@LWRMC.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 6000 | Emerg Generator Diesel (G) | 10/01/2003 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (I) Suction piping system (N) Approved synthetic material |
(F) Monitor dbl wall tank space (I) Not required (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8300 | Emerg Generator Diesel (G) | 12/01/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(X) No piping associated w/tank | (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 04/30/2024 | 04/30/2025 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/30/2023 | 04/30/2024 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/30/2022 | 04/30/2023 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/30/2021 | 04/30/2022 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 12/30/2020 | 12/30/2021 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 12/30/2019 | 12/30/2020 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 12/23/2018 | 12/23/2019 | ADMIRAL INSURANCE COMPANY | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2018 | 01/01/2019 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2017 | 01/01/2018 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2016 | 01/01/2017 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2014 | 01/01/2015 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2012 | 01/01/2013 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2011 | 01/01/2012 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2010 | 01/01/2011 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2009 | 01/01/2010 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 09/29/2005 | 09/29/2005 | IN-COMPLIANCE | MARK TRETHEWEY | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 09/01/2005 | 09/13/2005 | MINOR OUT-OF-COMPLIANCE | MARK TRETHEWEY | 0/1 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/07/2025 | Satisfied | SHANBERG_VJ_1 | Compliance Assistance | |||||||
Site Inspection | 03/07/2025 | Major Out of Compliance | SHANBERG_VJ_1 | 1/1 | Routine Compliance | ||||||
Issue Document | 02/27/2025 | Satisfied | SHANBERG_VJ_1 | Routine Compliance | |||||||
Record Document | 05/26/2023 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Issue Document | 05/01/2023 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Letter | 05/01/2023 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Site Inspection | 05/01/2023 | Major Out of Compliance | TRETHEWEY_MB_1 | 1/1 | Routine Compliance | ||||||
Enforcement Referral | 05/06/2021 | Accepted | TRETHEWEY_MB_1 | Enforcement | |||||||
Record Document | 04/28/2021 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Meeting | 04/28/2021 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Electronic Communication | 04/28/2021 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Issue Document | 11/25/2020 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Site Inspection | 11/25/2020 | Minor Out of Compliance | TRETHEWEY_MB_1 | 1/1 | Routine Compliance | ||||||
Letter | 11/25/2020 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Phone Conversation | 11/25/2020 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Issue Document | 02/08/2019 | Satisfied | TRETHEWEY_MB_1 | Installation | |||||||
Site Inspection | 02/08/2019 | In Compliance | TRETHEWEY_MB_1 | 1/0 | Installation | ||||||
Issue Document | 03/30/2018 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Issue Document | 03/30/2018 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Site Inspection | 03/30/2018 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 03/18/2016 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Issue Document | 03/18/2016 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Site Inspection | 03/18/2016 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 03/20/2014 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Site Inspection | 03/20/2014 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/30/2012 | In Compliance | MASON_RS_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/10/2011 | In Compliance | MASON_RS_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 02/26/2010 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Record Document | 03/05/2009 | Satisfied | TRETHEWEY_MB_1 | Non-Compliance | |||||||
Site Inspection | 01/14/2009 | Minor Out of Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Letter | 01/14/2009 | Satisfied | TRETHEWEY_MB_1 | Non-Compliance | |||||||
Site Inspection | 01/18/2008 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 01/29/2007 | In Compliance | TRETHEWEY_MB_1 | 0/1 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/07/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Submit 03/2025 and 04/2025 records to Manatee County NRD for review. | |||||||
03/07/2025 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Obtain Class A, B and C operator training certificates and submit copies of certificates to Manatee County NRD upon completion. | |||||||
03/07/2025 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Conduct and record integrity testing of your pipping sump and send documentation to Manatee County NRD for review. | |||||||
03/07/2025 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Conduct and record overfill operability testing and send documentation to Manatee County NRD for review. | |||||||
05/01/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide Manatee County PNRD with copies of the required tests. | |||||||
05/01/2023 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide Manatee County NRD with copies of the next two months records for review. | |||||||
05/01/2023 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Provide Manatee County NRD with Current Proof of Financial Responsibility | |||||||
05/01/2023 | 6024 | Minor | 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. | Have the required tests performed and provide Manatee County NRD with copies of the results | |||||||
05/01/2023 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Provide Manatee County NRD with copies of the required tests. | |||||||
No Discharges Found |