DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    Retail Station
 
County Miami-Dade   Status    OPEN
 
ID 9807300   Latitude    25° 52' 13.9374
 
Name U SHOP MEDLEY VALERO
10201 NW 116TH WAY
Longitude    80° 21' 54.8631
  MEDLEY, FL 33178-1172 LL Method    DPHO
 
Contact FREDDY LAVERDE   LL Status    REVIEWED
 
Phone (305) 888-4611   Status Date    02/14/2024
 
Account Owner Information
 
Name TROPIC OIL CO
10002 NW 89th Ave
Medley, FL 33178-1409
Effective Date    12/16/2021
 
Contact FREDDY LAVERDE / MARK BUMGARDNER
 
Phone (305) 888-4611
 
Email FREDDY.LAVERDE@PARKLANDUSA.COM
  Placard # / Date    680828 - 06/05/2024
Property Owner Information
 
Name TROPIC OIL CO
10002 NW 89th Ave
Medley, FL 33178-1409
Effective Date    12/16/2021
 
Contact FREDDY LAVERDE / MARK BUMGARDNER
 
Phone (305) 888-4611
 
Email FREDDY.LAVERDE@PARKLANDUSA.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 15000 Vehicular Diesel (D) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(8) Manually sampled wells
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 15000 Ethanol E10 (8) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
3 15000 Ethanol E10 (8) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SURETY BOND   03/12/2024 03/12/2025
INSURANCE   01/01/2023 01/01/2024 SCOTTSDALE INSURANCE COMPANY
INSURANCE   01/01/2022 01/01/2023 SCOTTSDALE INSURANCE COMPANY
INSURANCE   03/01/2021 03/01/2022 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   03/01/2020 03/01/2021 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   03/01/2019 03/01/2020 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   03/01/2018 03/01/2019 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   02/23/2017 02/23/2018 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   02/23/2015 02/23/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   02/23/2013 02/23/2014 ILLINOIS UNION
INSURANCE   02/23/2012 02/23/2013 ILLINOIS UNION
INSURANCE   02/23/2010 02/23/2011 ILLINOIS UNION
INSURANCE   02/23/2009 02/23/2010 ILLINOIS NATIONAL
INSURANCE   02/23/2008 02/23/2009 ILLINOIS NATIONAL
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 04/17/2006 04/24/2006 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TIN 04/19/2005 08/10/2005 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TIN 01/07/2005 08/10/2005 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
TCAR 09/10/2024 Satisfied MAS_JR_1 Closure
 
TCAR 08/19/2024 Incomplete MAS_JR_1 Closure
 
Site Inspection 07/02/2024 Major Out of Compliance MATUTERODRIGUEZ_MA_1 0/3 Component Closure
 
Letter 10/31/2023 Satisfied MATUTERODRIGUEZ_MA_1 Compliance Assistance
 
Site Inspection 10/31/2023 Major Out of Compliance MATUTERODRIGUEZ_MA_1 0/3 Routine Compliance
 
Electronic Communication 10/25/2023 Satisfied MATUTERODRIGUEZ_MA_1 Routine Compliance
 
Site Inspection 06/10/2022 In Compliance RODRIGUEZ_F 0/3 Compliance Assistance
 
Letter 06/10/2022 Satisfied RODRIGUEZ_F Compliance Assistance
 
Site Inspection 11/30/2021 Major Out of Compliance RODRIGUEZ_F 0/3 Routine Compliance
 
Letter 11/30/2021 Satisfied RODRIGUEZ_F Compliance Assistance
 
Electronic Communication 11/29/2021 Satisfied RODRIGUEZ_F Routine Compliance
 
Site Inspection 12/22/2020 In Compliance SANPEDRO_A_2 0/3 Compliance Assistance
 
Electronic Communication 12/22/2020 Satisfied SANPEDRO_A_2 Compliance Assistance
 
Letter 12/22/2020 Satisfied SANPEDRO_A_2 Compliance Assistance
 
Letter 01/31/2020 Satisfied SANPEDRO_A_2 Compliance Assistance
 
Site Inspection 01/31/2020 Minor Out of Compliance SANPEDRO_A_2 0/3 Routine Compliance
 
Site Inspection 01/04/2018 In Compliance CRUZ_I_2 0/3 Compliance Assistance
 
Letter 01/04/2018 Satisfied CRUZ_I_2 Compliance Assistance
 
Site Inspection 11/07/2017 Minor Out of Compliance CRUZ_I_2 0/3 Routine Compliance
 
Electronic Communication 11/07/2017 Satisfied CRUZ_I_2 Compliance Assistance
 
Letter 11/07/2017 Satisfied CRUZ_I_2 Compliance Assistance
 
Electronic Communication 10/25/2017 Satisfied CRUZ_I_2 Routine Compliance
 
Electronic Communication 10/10/2017 Satisfied CRUZ_I_2 Routine Compliance
 
Site Inspection 02/12/2016 In Compliance CRUZ_I_2 0/3 Non-Compliance
 
Site Inspection 08/27/2015 Minor Out of Compliance HOSU_C_1 0/3 Routine Compliance
 
Emergency Preparedness Information 08/27/2015 Satisfied HOSU_C_1 Routine Compliance
 
Letter 08/27/2015 Satisfied HOSU_C_1 Non-Compliance
 
Electronic Communication 08/11/2015 Satisfied HOSU_C_1 Routine Compliance
 
Emergency Preparedness Information 09/12/2013 Satisfied RUNTE_C_3 Routine Compliance
 
Site Inspection 09/12/2013 In Compliance RUNTE_C_3 0/3 Routine Compliance
 
Site Inspection 06/25/2013 Minor Out of Compliance RUNTE_C_3 0/3 Non-Compliance
 
Incident 10/24/2012 Has not led to Discharge RUNTE_C_3 Incident
 
Emergency Preparedness Information 10/24/2012 Satisfied RUNTE_C_3 Routine Compliance
 
Letter 10/24/2012 Satisfied RUNTE_C_3 Non-Compliance
 
Site Inspection 10/24/2012 Minor Out of Compliance RUNTE_C_3 0/3 Routine Compliance
 
Electronic Communication 10/05/2012 Satisfied RUNTE_C_3 Routine Compliance
 
Site Inspection 05/10/2012 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Site Inspection 05/04/2012 Minor Out of Compliance PADRON_JE_1 0/3 Non-Compliance
 
Emergency Preparedness Information 01/09/2012 Satisfied PADRON_JE_1 Routine Compliance
 
Site Inspection 01/09/2012 Major Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Letter 01/09/2012 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 11/19/2010 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Letter 09/10/2010 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 09/10/2010 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Letter 01/12/2010 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 01/08/2010 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Site Inspection 12/10/2009 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Enforcement Tracking 05/01/2009 Closed With Enforcement PADRON_JE_1 Enforcement
 
Site Inspection 05/01/2009 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Letter 01/09/2009 Satisfied PADRON_JE_1 Non-Compliance
 
Issue Document 01/09/2009 Satisfied PADRON_JE_1 Enforcement
 
Site Inspection 01/09/2009 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Enforcement Referral 01/09/2009 Accepted PADRON_JE_1 Enforcement
 
Emergency Preparedness Information 05/21/2007 Satisfied DASHTAKI_K_1 Routine Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied PADRON_JE_1 Routine Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied PADRON_JE_1 Routine Compliance
 
Site Inspection 06/21/2006 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/27/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide current and passing tests: - Integrity test of diesel double-walled fill port spill bucket - Integrity test of diesel STP sump
 
10/26/2023 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Make appropriate repairs to the Veeder Root TLS-350 to properly monitor a missing L3 diesel STP sump sensor. Provide a liquid status report with all sensors and functions normal when complete.
 
 
 
No Discharges Found