Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Retail Station | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9807300 | Latitude | 25° 52' 13.9374 | ||||||||
Name |
U SHOP MEDLEY VALERO 10201 NW 116TH WAY |
Longitude | 80° 21' 54.8631 | ||||||||
MEDLEY, FL 33178-1172 | LL Method | DPHO | |||||||||
Contact | FREDDY LAVERDE | LL Status | REVIEWED | ||||||||
Phone | (305) 888-4611 | Status Date | 02/14/2024 | ||||||||
Account Owner Information | |||||||||||
Name | TROPIC OIL CO 10002 NW 89th Ave Medley, FL 33178-1409 |
Effective Date | 12/16/2021 | ||||||||
Contact | FREDDY LAVERDE / MARK BUMGARDNER | ||||||||||
Phone | (305) 888-4611 | ||||||||||
FREDDY.LAVERDE@PARKLANDUSA.COM | |||||||||||
Placard # / Date | 680828 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | TROPIC OIL CO 10002 NW 89th Ave Medley, FL 33178-1409 |
Effective Date | 12/16/2021 | ||||||||
Contact | FREDDY LAVERDE / MARK BUMGARDNER | ||||||||||
Phone | (305) 888-4611 | ||||||||||
FREDDY.LAVERDE@PARKLANDUSA.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 15000 | Vehicular Diesel (D) | 01/01/2005 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (8) Manually sampled wells (F) Monitor dbl wall tank space (H) Mechanical line leak detector (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 15000 | Ethanol E10 (8) | 01/01/2005 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 15000 | Ethanol E10 (8) | 01/01/2005 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (H) Mechanical line leak detector |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
SURETY BOND | 03/12/2024 | 03/12/2025 | |||||||||
INSURANCE | 01/01/2023 | 01/01/2024 | SCOTTSDALE INSURANCE COMPANY | ||||||||
INSURANCE | 01/01/2022 | 01/01/2023 | SCOTTSDALE INSURANCE COMPANY | ||||||||
INSURANCE | 03/01/2021 | 03/01/2022 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 03/01/2020 | 03/01/2021 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 03/01/2019 | 03/01/2020 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 03/01/2018 | 03/01/2019 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 02/23/2017 | 02/23/2018 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 02/23/2015 | 02/23/2016 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 02/23/2013 | 02/23/2014 | ILLINOIS UNION | ||||||||
INSURANCE | 02/23/2012 | 02/23/2013 | ILLINOIS UNION | ||||||||
INSURANCE | 02/23/2010 | 02/23/2011 | ILLINOIS UNION | ||||||||
INSURANCE | 02/23/2009 | 02/23/2010 | ILLINOIS NATIONAL | ||||||||
INSURANCE | 02/23/2008 | 02/23/2009 | ILLINOIS NATIONAL | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/17/2006 | 04/24/2006 | MINOR OUT-OF-COMPLIANCE | PADRON, J | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 04/19/2005 | 08/10/2005 | IN-COMPLIANCE | PADRON, J | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 01/07/2005 | 08/10/2005 | IN-COMPLIANCE | PADRON, J | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
TCAR | 09/10/2024 | Satisfied | MAS_JR_1 | Closure | |||||||
TCAR | 08/19/2024 | Incomplete | MAS_JR_1 | Closure | |||||||
Site Inspection | 07/02/2024 | Major Out of Compliance | MATUTERODRIGUEZ_MA_1 | 0/3 | Component Closure | ||||||
Letter | 10/31/2023 | Satisfied | MATUTERODRIGUEZ_MA_1 | Compliance Assistance | |||||||
Site Inspection | 10/31/2023 | Major Out of Compliance | MATUTERODRIGUEZ_MA_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 10/25/2023 | Satisfied | MATUTERODRIGUEZ_MA_1 | Routine Compliance | |||||||
Site Inspection | 06/10/2022 | In Compliance | RODRIGUEZ_F | 0/3 | Compliance Assistance | ||||||
Letter | 06/10/2022 | Satisfied | RODRIGUEZ_F | Compliance Assistance | |||||||
Site Inspection | 11/30/2021 | Major Out of Compliance | RODRIGUEZ_F | 0/3 | Routine Compliance | ||||||
Letter | 11/30/2021 | Satisfied | RODRIGUEZ_F | Compliance Assistance | |||||||
Electronic Communication | 11/29/2021 | Satisfied | RODRIGUEZ_F | Routine Compliance | |||||||
Site Inspection | 12/22/2020 | In Compliance | SANPEDRO_A_2 | 0/3 | Compliance Assistance | ||||||
Electronic Communication | 12/22/2020 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Letter | 12/22/2020 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Letter | 01/31/2020 | Satisfied | SANPEDRO_A_2 | Compliance Assistance | |||||||
Site Inspection | 01/31/2020 | Minor Out of Compliance | SANPEDRO_A_2 | 0/3 | Routine Compliance | ||||||
Site Inspection | 01/04/2018 | In Compliance | CRUZ_I_2 | 0/3 | Compliance Assistance | ||||||
Letter | 01/04/2018 | Satisfied | CRUZ_I_2 | Compliance Assistance | |||||||
Site Inspection | 11/07/2017 | Minor Out of Compliance | CRUZ_I_2 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 11/07/2017 | Satisfied | CRUZ_I_2 | Compliance Assistance | |||||||
Letter | 11/07/2017 | Satisfied | CRUZ_I_2 | Compliance Assistance | |||||||
Electronic Communication | 10/25/2017 | Satisfied | CRUZ_I_2 | Routine Compliance | |||||||
Electronic Communication | 10/10/2017 | Satisfied | CRUZ_I_2 | Routine Compliance | |||||||
Site Inspection | 02/12/2016 | In Compliance | CRUZ_I_2 | 0/3 | Non-Compliance | ||||||
Site Inspection | 08/27/2015 | Minor Out of Compliance | HOSU_C_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/27/2015 | Satisfied | HOSU_C_1 | Routine Compliance | |||||||
Letter | 08/27/2015 | Satisfied | HOSU_C_1 | Non-Compliance | |||||||
Electronic Communication | 08/11/2015 | Satisfied | HOSU_C_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/12/2013 | Satisfied | RUNTE_C_3 | Routine Compliance | |||||||
Site Inspection | 09/12/2013 | In Compliance | RUNTE_C_3 | 0/3 | Routine Compliance | ||||||
Site Inspection | 06/25/2013 | Minor Out of Compliance | RUNTE_C_3 | 0/3 | Non-Compliance | ||||||
Incident | 10/24/2012 | Has not led to Discharge | RUNTE_C_3 | Incident | |||||||
Emergency Preparedness Information | 10/24/2012 | Satisfied | RUNTE_C_3 | Routine Compliance | |||||||
Letter | 10/24/2012 | Satisfied | RUNTE_C_3 | Non-Compliance | |||||||
Site Inspection | 10/24/2012 | Minor Out of Compliance | RUNTE_C_3 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 10/05/2012 | Satisfied | RUNTE_C_3 | Routine Compliance | |||||||
Site Inspection | 05/10/2012 | In Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 05/04/2012 | Minor Out of Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
Emergency Preparedness Information | 01/09/2012 | Satisfied | PADRON_JE_1 | Routine Compliance | |||||||
Site Inspection | 01/09/2012 | Major Out of Compliance | PADRON_JE_1 | 0/3 | Routine Compliance | ||||||
Letter | 01/09/2012 | Satisfied | PADRON_JE_1 | Non-Compliance | |||||||
Site Inspection | 11/19/2010 | In Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
Letter | 09/10/2010 | Satisfied | PADRON_JE_1 | Non-Compliance | |||||||
Site Inspection | 09/10/2010 | Minor Out of Compliance | PADRON_JE_1 | 0/3 | Routine Compliance | ||||||
Letter | 01/12/2010 | Satisfied | PADRON_JE_1 | Non-Compliance | |||||||
Site Inspection | 01/08/2010 | In Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 12/10/2009 | Minor Out of Compliance | PADRON_JE_1 | 0/3 | Routine Compliance | ||||||
Enforcement Tracking | 05/01/2009 | Closed With Enforcement | PADRON_JE_1 | Enforcement | |||||||
Site Inspection | 05/01/2009 | In Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
Letter | 01/09/2009 | Satisfied | PADRON_JE_1 | Non-Compliance | |||||||
Issue Document | 01/09/2009 | Satisfied | PADRON_JE_1 | Enforcement | |||||||
Site Inspection | 01/09/2009 | Minor Out of Compliance | PADRON_JE_1 | 0/3 | Routine Compliance | ||||||
Enforcement Referral | 01/09/2009 | Accepted | PADRON_JE_1 | Enforcement | |||||||
Emergency Preparedness Information | 05/21/2007 | Satisfied | DASHTAKI_K_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 02/06/2007 | Satisfied | PADRON_JE_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/22/2006 | Satisfied | PADRON_JE_1 | Routine Compliance | |||||||
Site Inspection | 06/21/2006 | In Compliance | PADRON_JE_1 | 0/3 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/27/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Provide current and passing tests: - Integrity test of diesel double-walled fill port spill bucket - Integrity test of diesel STP sump | |||||||
10/26/2023 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Make appropriate repairs to the Veeder Root TLS-350 to properly monitor a missing L3 diesel STP sump sensor. Provide a liquid status report with all sensors and functions normal when complete. | |||||||
No Discharges Found |