Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Fuel user/Non-retail | ||||
County | Polk | Status | OPEN | ||||
ID | 9807387 | Latitude | 28° 10' 6.8724 | ||||
Name |
ORLAMPA, INC. 1400 BROADWAY BLVD SE |
Longitude | 81° 48' 33.557 | ||||
POLK CITY, FL 33868-9109 | LL Method | DPHO | |||||
Contact | EDITH TINGLEY | LL Status | REVIEWED | ||||
Phone | (863) 874-5406 | Status Date | 06/28/2021 | ||||
Account Owner Information | |||||||
Name | ORLAMPA, INC 1400 BROADWAY BLVD SE POLK CITY, FL 33868 |
Effective Date | 06/13/2005 | ||||
Contact | SARA JO SMITH | ||||||
Phone | (863) 874-5406 | ||||||
SSMITH@FANTASYOFFLIGHT.COM | |||||||
Placard # / Date | 702277 - 10/16/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 2000 | Aviation Gas (E) | 06/01/2005 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | COMMERCE & INDUSTRY | ||||||
INSURANCE | 12/06/2017 | 12/06/2018 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 12/06/2015 | 12/06/2016 | AIG | ||||
INSURANCE | 12/06/2014 | 12/06/2015 | COMMERCE & INDUSTRY | ||||
INSURANCE | 12/06/2011 | 12/06/2012 | COMMERCE & INDUSTRY | ||||
INSURANCE | 12/06/2010 | 12/06/2011 | COMMERCE & INDUSTRY | ||||
INSURANCE | 12/06/2009 | 12/06/2010 | AIG | ||||
INSURANCE | 12/06/2008 | 12/06/2009 | COMMERCE & INDUSTRY | ||||
No Legacy Data Found | |||||||
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Site Inspection | 06/01/2021 | Major Out of Compliance | CASSELS_CR_2 | 1/0 | Routine Compliance | ||
Electronic Communication | 06/01/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||
Electronic Communication | 06/01/2021 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||
Electronic Communication | 06/01/2021 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||
Letter | 06/01/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||
Electronic Communication | 10/12/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 10/12/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Letter | 10/12/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 10/11/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 10/04/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Electronic Communication | 09/18/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Letter | 09/18/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||
Site Inspection | 09/18/2018 | Major Out of Compliance | WILLIAMSON_KE_1 | 1/0 | Routine Compliance | ||
Electronic Communication | 08/16/2018 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||
Site Inspection | 08/11/2016 | In Compliance | GLENN_LE_1 | 1/0 | Routine Compliance | ||
Electronic Communication | 08/11/2016 | Satisfied | GLENN_LE_1 | Routine Compliance | |||
Electronic Communication | 06/24/2015 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||
Electronic Communication | 06/24/2015 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||
Electronic Communication | 06/24/2015 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||
Electronic Communication | 05/18/2015 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||
Site Inspection | 03/18/2015 | Major Out of Compliance | MERRYMAN_DT_1 | 1/0 | Routine Compliance | ||
Letter | 03/18/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||
Site Inspection | 12/30/2011 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||
Site Inspection | 01/18/2011 | In Compliance | SLAPPEY_WR_1 | 1/0 | Routine Compliance | ||
Site Inspection | 02/12/2010 | In Compliance | CASSELS_CR_1 | 1/0 | Non-Compliance | ||
Electronic Communication | 02/10/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Letter | 12/23/2009 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Site Inspection | 12/23/2009 | Major Out of Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||
Phone Conversation | 12/18/2009 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||
Site Inspection | 01/28/2009 | In Compliance | DERY_WC_1 | 1/0 | Routine Compliance | ||
Phone Conversation | 01/22/2009 | Satisfied | DERY_WC_1 | Routine Compliance | |||
Enforcement Tracking | 10/20/2008 | Closed With Enforcement | MARSH_L | Enforcement | |||
Record Document | 03/12/2008 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||
Phone Conversation | 03/05/2008 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||
Letter | 02/21/2008 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||
Site Inspection | 02/21/2008 | Minor Out of Compliance | NEWBERG_DR_1 | 1/0 | Routine Compliance | ||
Enforcement Referral | 01/31/2008 | Accepted | MARSH_L | Enforcement | |||
Record Document | 09/14/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Meeting | 07/20/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Letter | 07/13/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Letter | 07/13/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Site Inspection | 04/17/2007 | In Compliance | CASSELS_CR_1 | 1/0 | Non-Compliance | ||
Phone Conversation | 04/10/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Issue Document | 03/14/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Record Document | 02/26/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Record Document | 01/18/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Issue Document | 01/18/2007 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Enforcement Referral Activity - OLD | 12/04/2006 | Terminated | CULBRETH_L | Enforcement | |||
Site Inspection | 12/01/2006 | Major Out of Compliance | CASSELS_CR_1 | 1/0 | Installation | ||
Site Inspection | 12/01/2006 | Major Out of Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||
Record Document | 11/09/2006 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Issue Document | 11/09/2006 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||
Phone Conversation | 11/03/2006 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
05/03/2021 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Copies of all required documents, which includes the full policy and the appropriate DEP Form Part completed by an authorized representative of the insurance company for the type of FR mechanism used, of each policy for the 2018-2019, 2019-2020, and 2020-2021 periods, must be submitted to the Department. | |||
05/03/2021 | 5003 | Minor | 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. | The information can be updated using DEP's electronic self-service application portal here: https://floridadep.gov/waste/permitting-compliance-assistance/content/storage-tank-facility-registration. Or alternatively, a Storage Tank Facility Registration Form can be completed with the updated information and submitted to TankRegistration@FloridaDEP.gov. Submit information showing updates when completed. | |||
05/03/2021 | 5127 | Minor | 3.17 Exterior Coatings not maintained to prevent corrosion for shop fabricated storage tank systems. | The peeling paint and corrosion should be cleaned and removed, and the areas re-coated with a rust inhibitive paint to maintain corrosion protection. The Department must be notified when the work is completed. | |||
05/03/2021 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | The spill containment tray must be liquid tight. A liquid tight, petroleum resistant, plug or valve must be installed in the hole in the spill containment tray, and the Department notified. | |||
05/03/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | If any records are available, copies must be submitted to the Department. If the test has not been performed, the test must be performed immediately with a copy of the results submitted to the Department. Please note, the designated primary overfill protection equipment must be tested for operability annually at intervals not exceeding 12 months to ensure proper operation. | |||
05/03/2021 | 5012 | Minor | 1.7 Incomplete documentation demonstrating financial responsibility. | A DEP Certification of Financial Responsibility (CFR) Form Part P must be completed by facility personnel for each policy period of the Financial Responsibility. A CFR Form Part P must be completed for the 2018-2019, 2019-2020, and 2020-2021 policy periods and copies submitted to the Department. | |||
No Discharges Found |