DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 9807647   Latitude    27° 58' 40.6915
 
Name MURPHY USA # 7282
7450 CYPERSS CARDEN
Longitude    81° 38' 46.8052
  WINTER HAVEN, FL 33880 LL Method    DPHO
 
Contact STORE MANAGER   LL Status    REVIEWED
 
Phone (863) 324-4750   Status Date    09/26/2023
 
Account Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    09/22/2005
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
  Placard # / Date    679982 - 06/05/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 20000 Unleaded Gas (B) 09/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 20000 Unleaded Gas (B) 09/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2019 04/30/2020
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2018 04/30/2019
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2017 04/30/2018
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2016 04/30/2017
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2015 04/30/2016
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2013 04/30/2014
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2012 04/30/2013
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2011 04/30/2012
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2010 04/30/2011
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2009 04/30/2010
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
LTR 04/06/2006 04/06/2006 SLAPPY_W 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NCLI FOLLOW UP LETTER.
 
RRBD 02/27/2006 03/01/2006 SLAPPEY_W 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED LETTER STATING WELLS WILL BE CLOSED BY MARCH 4 AND REQUESTING A LIST OF CONTRACTORS.
 
NCLI 02/02/2006 02/08/2006 SLAPPEY_W 0/2 COMPLIANCE ASSURANCE
 
TIN 01/20/2006 02/08/2006 MINOR OUT-OF-COMPLIANCE SLAPPEY_W 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes THREE PHOTOS. INSTALLED: TWO 20,000 GALLON DW FIBERGLASS CONTAINMENT SOLUTIONS; PIPING; DISPENSER LINERS; STP SUMPS; SPILL BUCKETS; DROP TUBES WITH OVERFILL PROTECTION VALVES; VALVE VENT LINE BALL CHECK VALVES; LINE LEAK DETECTORS; VEEDER ROOT.
 
SV 11/07/2005 02/02/2006 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 1 PHOTO TAKEN. HYDROSTATIC TESTING OF PIPING SUMPS AND SPILL BUCKETS. ALL BUCKETS AND SUMPS PASSED.
 
SV 09/22/2005 10/18/2005 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 8 PHOTOS TAKEN. OBSERVE INSTALLATION OF 2 UST'S ANCHORING.
 
SV 09/21/2005 10/18/2005 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 9 PHOTOS TAKEN. TANK INTERSTICE PRESSURE TEST AND SETTING TANK IN EXCAVATION & ANCHORING. ALL TESTING PASSED.
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 10/26/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Site Inspection 10/26/2019 Major Out of Compliance JARRETT_SE_1 0/2 Routine Compliance
 
Electronic Communication 10/26/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Letter 10/26/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Enforcement Tracking 02/14/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Electronic Communication 02/09/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Letter 02/09/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 02/08/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 02/05/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 12/20/2017 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 12/18/2017 Accepted WILLIAMSON_KE_1 Enforcement
 
Electronic Communication 12/14/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Phone Conversation 12/07/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 10/27/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Letter 09/19/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 09/19/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Site Inspection 09/19/2017 Major Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Electronic Communication 12/30/2015 Satisfied WILLIAMSON_KE_1 Routine Compliance
 
Site Inspection 12/30/2015 Minor Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Letter 12/30/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 12/14/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Incident 10/07/2014 Has not led to Discharge NEWBERG_DR_1 Incident
 
Incident 10/07/2014 Has not led to Discharge NEWBERG_DR_1 Incident
 
Letter 12/30/2013 Satisfied WINN_JP_1 Non-Compliance
 
Site Inspection 12/30/2013 Minor Out of Compliance WINN_JP_1 0/2 Routine Compliance
 
Electronic Communication 12/30/2013 Satisfied WINN_JP_1 Non-Compliance
 
Incident 05/03/2013 Has not led to Discharge DERY_WC_1 Incident
 
Incident 04/11/2013 Has not led to Discharge NEWBERG_DR_1 Incident
 
Document Management 04/11/2013 Complete NEWBERG_DR_1 Incident
 
Incident 03/26/2013 Has not led to Discharge NEWBERG_DR_1 Incident
 
Document Management 03/26/2013 Complete NEWBERG_DR_1 Incident
 
Letter 01/02/2013 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 01/02/2013 Minor Out of Compliance NEWBERG_DR_1 0/2 Non-Compliance
 
Letter 10/17/2012 Satisfied NEWBERG_DR_1 Non-Compliance
 
Document Management 10/17/2012 Complete NEWBERG_DR_1 Incident
 
Document Management 10/17/2012 Complete NEWBERG_DR_1 Incident
 
Site Inspection 10/17/2012 Minor Out of Compliance NEWBERG_DR_1 0/2 Routine Compliance
 
Incident 10/17/2012 Has not led to Discharge BELL_JM_1 Incident
 
Incident 10/17/2012 Has not led to Discharge NEWBERG_DR_1 Incident
 
Incident 06/29/2012 Has not led to Discharge CASSELS_CR_1 Incident
 
Document Management 05/10/2012 Complete BELL_JM_1 Incident
 
Incident 04/27/2012 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 04/27/2012 Complete BELL_JM_1 Incident
 
Electronic Communication 03/28/2012 Satisfied BELL_JM_1 Non-Compliance
 
Letter 03/13/2012 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 03/12/2012 Minor Out of Compliance BELL_JM_1 0/2 Non-Compliance
 
Record Document 02/01/2012 Satisfied BELL_JM_1 Non-Compliance
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Incident 12/21/2011 Has not led to Discharge BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Document Management 12/21/2011 Complete BELL_JM_1 Incident
 
Site Inspection 11/30/2011 Minor Out of Compliance BELL_JM_1 0/2 Routine Compliance
 
Letter 11/30/2011 Satisfied BELL_JM_1 Non-Compliance
 
Letter 11/04/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Phone Conversation 11/03/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Record Document 09/24/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Record Document 09/24/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 08/26/2010 Minor Out of Compliance CASSELS_CR_1 0/2 Routine Compliance
 
Letter 08/26/2010 Satisfied CASSELS_CR_1 Non-Compliance
 
Incident 05/25/2010 Has not led to Discharge COOK_JH_1 Incident
 
Site Inspection 09/24/2009 In Compliance DERY_WC_1 0/2 Non-Compliance
 
Record Document 09/21/2009 Satisfied DERY_WC_1 Non-Compliance
 
Letter 09/08/2009 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 09/08/2009 Minor Out of Compliance DERY_WC_1 0/1 Routine Compliance
 
Phone Conversation 07/27/2009 Satisfied DERY_WC_1 Routine Compliance
 
Site Inspection 02/27/2009 Minor Out of Compliance BELL_JM_1 0/2 Non-Compliance
 
Letter 02/27/2009 Satisfied BELL_JM_1 Non-Compliance
 
Phone Conversation 02/25/2009 Satisfied BELL_JM_1 Routine Compliance
 
Record Document 12/03/2008 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 11/07/2008 Minor Out of Compliance BELL_JM_1 0/2 Routine Compliance
 
Letter 11/07/2008 Satisfied BELL_JM_1 Non-Compliance
 
Record Document 06/10/2008 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 04/28/2008 Minor Out of Compliance DERY_WC_1 0/2 Routine Compliance
 
Letter 04/28/2008 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 04/02/2008 Satisfied DERY_WC_1 Routine Compliance
 
Emergency Preparedness Information 05/22/2007 Satisfied WINN_JP_1 Routine Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied SLAPPEY_WR_1 Routine Compliance
 
Site Inspection 01/09/2007 In Compliance NEWBERG_DR_1 0/2 Routine Compliance
 
Phone Conversation 12/08/2006 Satisfied NEWBERG_DR_1 Routine Compliance
 
Emergency Preparedness Information 09/28/2006 Satisfied NEWBERG_DR_1 Routine Compliance
 
Record Document 05/15/2006 Satisfied SLAPPEY_WR_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/26/2019 4051 Minor 4.26 Dispenser sumps not installed to allow for release detection. Therefore, deflector plating must be installed with appropriate documentation provided to the Department.
 
10/26/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Leakage must be repaired with appropriate documentation provided to the Department.
 
10/26/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Liners must be cleaned with appropriate documentation provided to the Department.
 
10/26/2019 4012 Minor 2.3 For an incident, notification not received in a timely manner. Therefore, either containment test records matching the alarms must be provided or incident notification forms (INFs) must be provided to the Department for all alarms not corresponding to annual testing.
 
10/26/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Therefore, either containment test records matching the alarms must be provided or investigations must be performed for any alarms not corresponding to containment testing with the investigation results submitted to the Department.
 
10/26/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Leakage must be repaired with appropriate documentation provided to the Department.
 
10/26/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Either test records must be provided, or the tests performed immediately with the test results submitted to the Department.
 
 
 
No Discharges Found