Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Marine/Coastal Fuel Storage | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9809115 | Latitude | 27° 42' 55.26 | ||||||||
Name |
MHC ST PETE LLC 5821 32ND WAY S |
Longitude | 82° 40' 44.17 | ||||||||
SAINT PETERSBURG, FL 33712 | LL Method | DPHO | |||||||||
Contact | WILFREDO NIEVES | LL Status | REVIEWED | ||||||||
Phone | (727) 867-2600 | Status Date | 06/15/2007 | ||||||||
Account Owner Information | |||||||||||
Name | EQUITY LIFESTYLE PROPERTIES INC 2 N RIVERSIDE PLAZA #800 CHICAGO, IL 60606 |
Effective Date | 05/20/2024 | ||||||||
Contact | HENRY LUE | ||||||||||
Phone | (312) 279-1400 | ||||||||||
PERMITS_LICENSES@EQUITYLIFESTYLE.COM | |||||||||||
Placard # / Date | 701431 - 09/17/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | MHC ST PETE LLC 5821 32ND WAY S ST PETERSBURG, FL 33712 |
Effective Date | 02/14/2023 | ||||||||
Contact | JORGE RODRIGUEZ | ||||||||||
Phone | (727) 867-2600 | ||||||||||
JORGE_RODRIGUEZ@EQUITYLIFESTYLE.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 12000 | Vehicular Diesel (D) | 10/01/2006 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 12000 | Unleaded Gas (B) | 09/01/2024 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(B) Steel/galvanized metal (C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 12000 | Unleaded Gas (B) | 10/01/2006 | UNDERGROUND | Closed In Place (A) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 04/01/2020 | 04/01/2021 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 04/01/2019 | 04/01/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 04/01/2018 | 04/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 03/28/2017 | 04/17/2018 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 04/29/2015 | 04/29/2017 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 04/29/2014 | 04/29/2015 | HUDSON SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 04/29/2013 | 04/29/2014 | HUDSON SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 04/29/2011 | 04/29/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/29/2010 | 04/29/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 12/02/2008 | 12/02/2009 | ILLINOIS UNION | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 06/10/2024 | Satisfied | VIXAYO_A | Enforcement | |||||||
Enforcement Referral | 03/30/2023 | Accepted | COLSON_NJ_1 | Enforcement | |||||||
Electronic Communication | 02/27/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 02/27/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 02/27/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 02/17/2023 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 02/17/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 11/13/2022 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Site Inspection | 04/08/2021 | Major Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 04/08/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 02/18/2021 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
TCAR | 09/19/2018 | Satisfied | COLSON_NJ_1 | Closure | |||||||
Letter | 06/19/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Record Document | 06/19/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 05/08/2018 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/08/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 04/09/2018 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Issue Document | 12/04/2017 | Satisfied | COLSON_NJ_1 | Installation | |||||||
Site Inspection | 12/04/2017 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Installation | ||||||
Letter | 11/01/2017 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 11/01/2017 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Closure | ||||||
Issue Document | 12/18/2015 | Satisfied | CULBRETH_L | Routine Compliance | |||||||
Issue Document | 08/21/2015 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Site Inspection | 08/21/2015 | In Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 07/30/2015 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Issue Document | 09/19/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 09/19/2013 | In Compliance | STRAUSS_RH_1 | 0/2 | Non-Compliance | ||||||
Letter | 07/15/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 07/11/2013 | Minor Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 08/25/2011 | In Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Enforcement Tracking | 03/24/2011 | Closed With Enforcement | MEETZE_A | Enforcement | |||||||
Incident | 03/22/2011 | Has not led to Discharge | STRAUSS_RH_1 | Incident | |||||||
Issue Document | 02/02/2011 | Satisfied | MEETZE_A | Enforcement | |||||||
Record Document | 01/24/2011 | Satisfied | MEETZE_A | Enforcement | |||||||
Electronic Communication | 12/29/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Electronic Communication | 12/29/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Record Document | 12/08/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Electronic Communication | 12/08/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Electronic Communication | 12/08/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Enforcement Referral | 12/02/2010 | Accepted | MEETZE_A | Enforcement | |||||||
Letter | 11/29/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Record Document | 08/27/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Issue Document | 08/24/2010 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 08/23/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 08/23/2010 | Major Out of Compliance | STRAUSS_RH_1 | 0/2 | Non-Compliance | ||||||
Record Document | 08/23/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 07/19/2010 | Major Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Letter | 07/19/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
TCAR | 09/29/2009 | Satisfied | SOWERS_JA_1 | Closure | |||||||
Letter | 08/27/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 08/27/2009 | Major Out of Compliance | STRAUSS_RH_1 | 0/2 | Non-Compliance | ||||||
Site Inspection | 07/28/2009 | Minor Out of Compliance | ROGGELIN_EM_1 | 0/1 | Closure | ||||||
Site Inspection | 07/28/2009 | Minor Out of Compliance | ROGGELIN_EM_1 | 0/1 | Installation | ||||||
Site Inspection | 07/16/2009 | Minor Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Letter | 07/16/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 07/14/2008 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Site Inspection | 07/14/2008 | Minor Out of Compliance | BARNETT_JX | 0/2 | Routine Compliance | ||||||
Site Inspection | 01/16/2008 | In Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 07/06/2007 | In Compliance | ROGGELIN_EM_1 | 0/2 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/17/2023 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Submit the historical documentation of storage tank insurance for 04/01/2021 to 04/01/2022. | |||||||
04/08/2021 | 4077 | Minor | 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. | Remove the accumulated water from the Rec 90 tank interstice. Then have the integrity of the tank interstice tested. Submit test results to this office for review. | |||||||
04/08/2021 | 4076 | Minor | 4.11 Failure to conduct required periodic containment and interstitial integrity testing. | Be sure to have piping sump & dispenser containment integrity testing performed at least once every 36 months. Submit current integrity (hydro) test results to this office for review. | |||||||
04/08/2021 | 4057 | Minor | 4.31 Overfill protection devices not registered or tested annually. | Submit current operability test results for the overfill protection devices. | |||||||
No Discharges Found |