DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pasco   Status    OPEN
 
ID 9810303   Latitude    28° 11' 22.8161
 
Name MOBIL STATION
2144 CORPORATE CTR DR
Longitude    82° 37' 35.464
  ODESSA, FL 33556 LL Method    DPHO
 
Contact PAUL JALLO   LL Status    REVIEWED
 
Phone (727) 773-6744   Status Date    02/01/2024
 
Account Owner Information
 
Name PAUL & MICHELLE ENTERPRISES LLC
16055 STATE ROAD 52 #201
LAND O LAKES, FL 34638
Effective Date    11/29/2011
 
Contact PAUL JALLO
 
Phone (813) 406-4813
 
Email PJALLO@GMAIL.COM
  Placard # / Date    702356 - 10/18/2024
Property Owner Information
 
Name PAUL & MICHELLE ENTERPRISES LLC
16055 STATE ROAD 52 #201
LAND O LAKES, FL 34638
Effective Date    11/29/2011
 
Contact PAUL JALLO
 
Phone (813) 406-4813
 
Email PJALLO@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 30000 Unleaded Gas (B) 04/01/2008 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(L) Compartmented
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   03/11/2025 03/11/2026 LLOYD'S UNDERWRITERS
INSURANCE   10/24/2018 10/24/2019 ACE
INSURANCE   10/19/2015 10/19/2016 ACE
INSURANCE   10/19/2014 10/19/2015 ACE
INSURANCE   10/19/2013 10/19/2014 ADMIRAL INSURANCE COMPANY
INSURANCE   10/19/2012 10/19/2013 ADMIRAL INSURANCE COMPANY
INSURANCE   06/04/2011 06/04/2012 ENDURANCE AMERICAN SPECIALTY INS CO
INSURANCE   06/04/2010 06/04/2011 ENDURANCE AMERICAN SPECIALTY INS CO
INSURANCE   10/15/2009 10/15/2010 ENDURANCE AMERICAN SPECIALTY INS CO
INSURANCE   06/06/2009 06/06/2010 ZURICH-AMERICAN
INSURANCE   10/30/2008 06/06/2009 ZURICH-AMERICAN
INSURANCE   10/30/2008 06/06/2009 ZURICH-AMERICAN
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 05/06/2025 Accepted MUSLIC_A_1 Enforcement
 
Electronic Communication 03/27/2025 Satisfied MUSLIC_A_1 Compliance Assistance
 
Site Inspection 03/27/2025 Major Out of Compliance MUSLIC_A_1 0/1 Routine Compliance
 
Electronic Communication 12/30/2024 Satisfied MUSLIC_A_1 Routine Compliance
 
Electronic Communication 12/27/2024 Satisfied REIS_A Enforcement
 
Enforcement Tracking 11/21/2024 Closed Without Enforcement PEDIGO_L Enforcement
 
Letter 09/17/2024 Satisfied REIS_A Enforcement
 
Enforcement Referral 06/16/2023 Accepted JUARISTIC_GK_1 Enforcement
 
Site Inspection 05/16/2023 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Electronic Communication 05/08/2023 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 01/15/2021 Satisfied PEDIGO_L Enforcement
 
Letter 01/15/2021 Satisfied PEDIGO_L Enforcement
 
Enforcement Referral 01/08/2021 Accepted JUARISTIC_GK_1 Enforcement
 
Letter 12/23/2020 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 12/23/2020 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Electronic Communication 12/23/2020 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 12/04/2020 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Enforcement Tracking 04/10/2019 Closed Without Enforcement PEDIGO_L Enforcement
 
Issue Document 04/10/2019 Satisfied PEDIGO_L Enforcement
 
Letter 03/05/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 03/05/2019 In Compliance JUARISTIC_GK_1 0/1 Compliance Assistance
 
Electronic Communication 03/04/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Letter 12/27/2018 Satisfied KENNEDY_S Enforcement
 
Site Inspection 09/07/2018 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Letter 09/07/2018 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 08/13/2018 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Enforcement Referral 08/22/2017 Accepted JUARISTIC_GK_1 Enforcement
 
Letter 06/21/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 06/21/2016 Minor Out of Compliance JUARISTIC_GK_1 0/1 Non-Compliance
 
Phone Conversation 06/13/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Electronic Communication 06/03/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 06/03/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 04/15/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 04/15/2016 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Electronic Communication 03/24/2016 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 02/12/2014 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Site Inspection 02/11/2014 In Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Record Document 08/12/2013 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 05/22/2013 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 05/22/2013 Major Out of Compliance LONGEN_JL_1 0/1 Non-Compliance
 
Site Inspection 11/07/2012 Major Out of Compliance LONGEN_JL_1 0/1 Routine Compliance
 
Letter 11/07/2012 Satisfied LONGEN_JL_1 Non-Compliance
 
Emergency Preparedness Information 11/07/2012 Satisfied LONGEN_JL_1 Routine Compliance
 
Letter 11/30/2011 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 11/30/2011 Minor Out of Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Emergency Preparedness Information 11/30/2011 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Letter 10/18/2010 Satisfied BAUER_DR_1 Non-Compliance
 
Site Inspection 10/18/2010 Minor Out of Compliance BAUER_DR_1 0/1 Routine Compliance
 
Emergency Preparedness Information 10/15/2010 Satisfied BAUER_DR_1 Routine Compliance
 
Record Document 06/10/2010 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Emergency Preparedness Information 05/07/2010 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Letter 05/07/2010 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 05/07/2010 Major Out of Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Emergency Preparedness Information 05/29/2009 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Site Inspection 05/28/2009 Major Out of Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Letter 05/28/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 12/23/2008 In Compliance CONDOLEON_GJ_1 0/1 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/27/2025 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Submit UST training certificates, financial responsibility records from 10/24/2019 to 3/11/2025 and Part P from 10/24/2019 to present, monthly visual inspection records from December 2020 to June 2024, liquid status tapes from December 2020 to present, and training records from 2019 to present or acknowledge that they are unavailable.
 
03/27/2025 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Submit primary overfill device annual operability test results from August 2019 to present or acknowledge that they are unavailable. If test was not performed per schedule, perform overfill protection device operability test and submit test results to this office.
 
03/27/2025 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Submit integrity test results of Double-walled spill bucket (3), dispenser sump (5), and STP sump (3) from August 2021 to present of acknowledge that they are unavailable. If testing was not performed per schedule, perform the integrity tests and submit the test results to this office.
 
03/27/2025 6062 Minor 2.5 Release detection devices not tested annually. Submit line leak detector (3), Veeder-Root monitoring panel, and liquid sensor (4) operability tests from August 2019 to current or acknowledge that they are unavailable. If unavailable, complete line leak detector (3), Veeder-Root monitoring panel, and liquid sensor (4) operability tests and submit test results to this office.
 
03/27/2025 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Submit monthly visual inspection records from December 2020 to June 2024 or acknowledge that they are unavailable.
 
03/27/2025 6029 Minor 4.1 Any component(s) of the storage tank system not installed according to manufacturer's instructions. Install RUL and PUL STP sump sensors correctly, at the bottom of the sumps.
 
03/27/2025 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. Submit financial responsibility records from 10/24/2019 to present, including applicable DEP forms, to this office, or acknowledge that they are unavailable.
 
03/27/2025 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. Submit Incident Notification Form (INF) for the incidents to this office.
 
03/27/2025 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Submit financial responsibility records from 10/24/2019 to 3/11/2025, including applicable DEP forms, to this office.
 
03/27/2025 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Submit the records showing that the actions were taken within 24 hours of discovery to investigate the incidents.
 
03/27/2025 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. For each incident, submit the records showing that investigation of the incident was completed within 14 days of discovery of the incident to determine if a discharge has occurred.
 
03/27/2025 6017 Minor 4.4 All incident records, including test results not kept until storage tank system closure. Submit investigation records for the incidents. The following documentation must be included in investigation records: the cause of each incident, integrity test results of spill buckets, STP sumps, and dispenser sumps, records showing that water and petroleum contact water was removed from spill buckets, STP sumps, and dispenser sumps (water manifest or photo documentation).
 
03/27/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of petroleum contact water (PCW) or water from: PUL spill bucket primary, all spill bucket secondaries, all STP sumps, and UDCs 1/2, 3/4, and 4/5. Submit proof of compliance (photo documentation and/or waste manifest).
 
03/27/2025 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair or replace inoperable liquid sensor, conduct sensor operability test, and submit test result to this office.
 
03/27/2025 6002 Minor 2.1 Operator Training records not available. Complete UST operator trainings and submit Class A/B and C operator training certificates to this office. Third-party Training Courses can be found online at https://floridadep.gov/waste/permitting-compliance-assistance/content/underground-storage-tank-operator-training
 
03/27/2025 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Properly install RUL and PUL STP sump liquid sensors on the bottom of the sump per manufacturers specification.
 
05/16/2023 6001 Minor 2.1 No reasonable access provided. Provide an authorized facility representative to unlock and open any covers, manways, and release detection equipment associated with the storage tank system or system component and demonstrate operational functionality of electronic equipment.
 
05/16/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide test results. If the tests haven't been conducted; schedule immediately and submit completed test results to this office immediately.
 
05/16/2023 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Provide the monthly release detection records from 12/2020 to present.
 
05/16/2023 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Provide requested release detection, training certification, testing, maintenance/repair, and financial responsibility records.
 
05/16/2023 6062 Minor 2.5 Release detection devices not tested annually. If testing isn’t current, schedule the tests immediately. Submit the annual operability test results to this office immediately.
 
05/16/2023 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Provide proof of financial responsibility from 10/24/2019.
 
05/16/2023 6002 Minor 2.1 Operator Training records not available. Provide at least one named individual for each class of operator – Class A, Class B, and Class C, for this facility.
 
05/16/2023 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. Provide appropriate Parts of Form 62-761.900(3), for demonstrating proof of financial responsibility.
 
05/16/2023 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. Provide an explanation for the following alarms: L1: RUL STP Sump Fuel Alarm on 1/22/2021 (assumed annual operability testing-provide test results) L2: Super STP Sump ‘Sensor Out Alarm” on 3/27 and 5/4/2022. L3: Diesel STP Sump (no alarms since 2018-either the sensor isn’t communicating with the Veeder Root or it hasn’t been tested in 5/years. L4: Interstice Annular Space Fuel Alarm on 1/22/2021 (assumed annual operability testing-provide test results) The positive response (Fuel Alarms and/or Sensor Out Alarms) of the release detection device is an incident, and shall be investigated in accordance with 62-761.430.
 
12/23/2020 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Replace the missing poppet in the RUL vapor recovery.
 
12/23/2020 4007 Minor 2.6 Registration fees not paid, placard not posted. Obtain the current placard, and display in plain view at the facility.
 
12/23/2020 4001 Minor 2.2 Operator certification requirements not met. Obtain the required training certificates from a registered Third-Party training course/provider. Provide the required Class C training certificates for onsite personnel.
 
12/23/2020 4019 Minor 2.3 All incident records, including test results not kept until storage tank system closure. Submit the incident investigation results for the Sensor Out Alarms.
 
12/23/2020 4014 SNC-B 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. Provide proof of financial responsibility.
 
12/23/2020 4067 Minor 4.2 Release detection devices not tested annually. Test the release detection devices, liquid sensors and monitoring panel, and submit the test results to this office.
 
12/23/2020 4031 Minor 4.9 Storage tank system component not installed according to manufacturer's instructions. Install the interstitial sensor correctly, at the bottom of the tank interstice.
 
12/23/2020 4078 Minor 2.6 Required records not available within 5 working days notice. Provide the requested records.
 
12/23/2020 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Have the shear valves tested and submit the test results to this office.
 
12/23/2020 4041 SNC-B 4.18 Shear valve not installed properly. This violation may lead to Placard Revocation and Delivery Prohibition. Remove the test adapters from the shear valves in UDC 1/2.
 
12/23/2020 4060 Minor 4.5 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Install the sensor at the bottom of the tank interstice.
 
12/23/2020 4067 Minor 4.2 Release detection devices not tested annually. Test the MLLDs, and submit the test results to this office.
 
 
 
No Discharges Found