DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Polk   Status    CLOSED
 
ID 9810694   Latitude    28° 1' 44.829
 
Name DSM TECH CONSULTANTS LLC
6810 NEW TAMPA HWY #600
Longitude    82° 2' 43.842
  LAKELAND, FL 33815 LL Method    DPHO
 
Contact KARL MUEHLBERGER   LL Status    REVIEWED
 
Phone (863) 802-8888   Status Date    05/17/2011
 
Account Owner Information
 
Name DSM TECH CONSULTANTS LLC
PO BOX 93160
LAKELAND, FL 33804
Effective Date    02/14/2014
 
Contact KARL MUEHLBERGER
 
Phone (863) 802-8888
 
Email ONOC@DSM.NET
  Placard # / Date    551603 - 05/23/2019
Property Owner Information
 
Name DSM TECH CONSULTANTS LLC
PO BOX 93160
LAKELAND, FL 33804
Effective Date    02/14/2014
 
Contact KARL MUEHLBERGER
 
Phone (863) 802-8888
 
Email ONOC@DSM.NET
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
648632 2000 Emerg Generator Diesel (G) 08/01/2006 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(N) Approved synthetic material
(1) Continuous electronic sensing
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   09/22/2018 09/22/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   09/22/2015 09/22/2016 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   09/22/2014 09/22/2015 COMMERCE & INDUSTRY
INSURANCE   09/22/2011 09/22/2012 COMMERCE & INDUSTRY
INSURANCE   09/22/2010 09/22/2011 COMMERCE & INDUSTRY
INSURANCE   09/22/2009 09/22/2010 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 11/21/2018 Major Out of Compliance JARRETT_SE_1 1/0 Routine Compliance
 
Electronic Communication 11/21/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Letter 11/21/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 08/10/2016 Satisfied JARRETT_SE_1 Routine Compliance
 
Site Inspection 08/10/2016 In Compliance JARRETT_SE_1 1/0 Routine Compliance
 
Electronic Communication 08/01/2016 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 02/18/2015 Satisfied JARRETT_SE_1 Non-Compliance
 
Issue Document 11/21/2014 Satisfied JARRETT_SE_1 Non-Compliance
 
Site Inspection 11/21/2014 Major Out of Compliance JARRETT_SE_1 1/0 Routine Compliance
 
Issue Document 11/21/2014 Satisfied JARRETT_SE_1 Non-Compliance
 
Letter 11/21/2014 Satisfied JARRETT_SE_1 Non-Compliance
 
Site Inspection 10/28/2011 In Compliance WINN_JP_1 1/0 Routine Compliance
 
Enforcement Tracking 04/25/2011 Closed With Enforcement BROCK_L Enforcement
 
Issue Document 04/25/2011 Satisfied BROCK_L Enforcement
 
Site Inspection 10/22/2010 In Compliance CASSELS_CR_1 1/0 Routine Compliance
 
Site Inspection 10/29/2009 In Compliance WINN_JP_1 1/0 Routine Compliance
 
Phone Conversation 10/29/2009 Satisfied WINN_JP_1 Routine Compliance
 
Enforcement Referral 09/08/2009 Accepted MARSH_L Enforcement
 
Record Document 11/21/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Record Document 11/21/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Letter 10/09/2008 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 10/09/2008 Major Out of Compliance SLAPPEY_WR_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/21/2018 5168 Minor 1.2 Storage tank system equipment not registered with the Department. Therefore, the gauge can only be utilized as a fuel level indicator and a FDEP approved/registered, overfill prevention device must be installed. - Documentation must be provided to the Department indicating an approved device has been installed.
 
11/21/2018 5097 SNC-B 3.5 Electronic release detection devices not inspected monthly for shop fabricated storage tank systems. Copies of the next two monthly release detection inspection records must be submitted to the Department as the inspections are performed and documented.
 
11/21/2018 5005 SNC-B 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. As a reminder, if the registration fees are not paid and a copy of the placard is not available on-site, fuel deliveries cannot be received; therefore, copies of the fuel tickets for any fuel deliveries received between July 1, 2018 and 10/03/2018 must be provided to the Department.
 
11/21/2018 5102 Minor 3.3 Shop fabricated storage tank system release detection devices not tested annually. Either the test records must be located and provided to the Department or the test must be performed immediately with the test results submitted to the Department.
 
11/21/2018 5145 Minor 1.8 Records not kept until closure of system. Completed copies of the CFRs for these coverage periods must be provided to the Department.
 
11/21/2018 5094 SNC-B 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. Copies of the next two monthly release detection inspection records must be submitted to the Department as the inspections are performed and documented.
 
11/21/2018 5011 SNC-B 1.6 Failure to maintain and demonstrate financial responsibility. However, no documentation was provided for the coverage periods of 09/22/2016 to 09/22/2017 & 09/22/2017 to 09/22/2018; proof of financial responsibility for these time periods must be provided to the Department.
 
11/21/2018 5046 Minor 3.25 Dispensers not installed and maintained according to standards for shop fabricated tank systems. A breakaway device must be installed on the dispenser hose with documentation provided to the Department indicating the device has been installed.
 
11/21/2018 5042 SNC-B 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. A FDEP approved/registered device must be installed and tested with the test results submitted to the Department.
 
 
 
No Discharges Found