Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Polk | Status | CLOSED | ||||||||
ID | 9810694 | Latitude | 28° 1' 44.829 | ||||||||
Name |
DSM TECH CONSULTANTS LLC 6810 NEW TAMPA HWY #600 |
Longitude | 82° 2' 43.842 | ||||||||
LAKELAND, FL 33815 | LL Method | DPHO | |||||||||
Contact | KARL MUEHLBERGER | LL Status | REVIEWED | ||||||||
Phone | (863) 802-8888 | Status Date | 05/17/2011 | ||||||||
Account Owner Information | |||||||||||
Name | DSM TECH CONSULTANTS LLC PO BOX 93160 LAKELAND, FL 33804 |
Effective Date | 02/14/2014 | ||||||||
Contact | KARL MUEHLBERGER | ||||||||||
Phone | (863) 802-8888 | ||||||||||
ONOC@DSM.NET | |||||||||||
Placard # / Date | 551603 - 05/23/2019 | ||||||||||
Property Owner Information | |||||||||||
Name | DSM TECH CONSULTANTS LLC PO BOX 93160 LAKELAND, FL 33804 |
Effective Date | 02/14/2014 | ||||||||
Contact | KARL MUEHLBERGER | ||||||||||
Phone | (863) 802-8888 | ||||||||||
ONOC@DSM.NET | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
648632 | 2000 | Emerg Generator Diesel (G) | 08/01/2006 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system (N) Approved synthetic material |
(1) Continuous electronic sensing (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/22/2018 | 09/22/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/22/2015 | 09/22/2016 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/22/2014 | 09/22/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/22/2011 | 09/22/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/22/2010 | 09/22/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/22/2009 | 09/22/2010 | COMMERCE & INDUSTRY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 11/21/2018 | Major Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 11/21/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Letter | 11/21/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 08/10/2016 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Site Inspection | 08/10/2016 | In Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 08/01/2016 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 02/18/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Issue Document | 11/21/2014 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Site Inspection | 11/21/2014 | Major Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Issue Document | 11/21/2014 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Letter | 11/21/2014 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Site Inspection | 10/28/2011 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 04/25/2011 | Closed With Enforcement | BROCK_L | Enforcement | |||||||
Issue Document | 04/25/2011 | Satisfied | BROCK_L | Enforcement | |||||||
Site Inspection | 10/22/2010 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 10/29/2009 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 10/29/2009 | Satisfied | WINN_JP_1 | Routine Compliance | |||||||
Enforcement Referral | 09/08/2009 | Accepted | MARSH_L | Enforcement | |||||||
Record Document | 11/21/2008 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Record Document | 11/21/2008 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Letter | 10/09/2008 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Site Inspection | 10/09/2008 | Major Out of Compliance | SLAPPEY_WR_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
11/21/2018 | 5168 | Minor | 1.2 Storage tank system equipment not registered with the Department. | Therefore, the gauge can only be utilized as a fuel level indicator and a FDEP approved/registered, overfill prevention device must be installed. - Documentation must be provided to the Department indicating an approved device has been installed. | |||||||
11/21/2018 | 5097 | SNC-B | 3.5 Electronic release detection devices not inspected monthly for shop fabricated storage tank systems. | Copies of the next two monthly release detection inspection records must be submitted to the Department as the inspections are performed and documented. | |||||||
11/21/2018 | 5005 | SNC-B | 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. | As a reminder, if the registration fees are not paid and a copy of the placard is not available on-site, fuel deliveries cannot be received; therefore, copies of the fuel tickets for any fuel deliveries received between July 1, 2018 and 10/03/2018 must be provided to the Department. | |||||||
11/21/2018 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Either the test records must be located and provided to the Department or the test must be performed immediately with the test results submitted to the Department. | |||||||
11/21/2018 | 5145 | Minor | 1.8 Records not kept until closure of system. | Completed copies of the CFRs for these coverage periods must be provided to the Department. | |||||||
11/21/2018 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Copies of the next two monthly release detection inspection records must be submitted to the Department as the inspections are performed and documented. | |||||||
11/21/2018 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | However, no documentation was provided for the coverage periods of 09/22/2016 to 09/22/2017 & 09/22/2017 to 09/22/2018; proof of financial responsibility for these time periods must be provided to the Department. | |||||||
11/21/2018 | 5046 | Minor | 3.25 Dispensers not installed and maintained according to standards for shop fabricated tank systems. | A breakaway device must be installed on the dispenser hose with documentation provided to the Department indicating the device has been installed. | |||||||
11/21/2018 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | A FDEP approved/registered device must be installed and tested with the test results submitted to the Department. | |||||||
No Discharges Found |