Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 9810698 | Latitude | 28° 8' 8.7253 | ||||||||
Name |
DUFF SHELL 2993 DUFF RD |
Longitude | 82° 0' 23.2044 | ||||||||
LAKELAND, FL 33810-2188 | LL Method | DPHO | |||||||||
Contact | ANILKUMAR RATNANI | LL Status | REVIEWED | ||||||||
Phone | (863) 513-3611 | Status Date | 02/16/2023 | ||||||||
Account Owner Information | |||||||||||
Name | RATNAM USA INC 2993 DUFF RD Lakeland, FL 33810 |
Effective Date | 12/22/2008 | ||||||||
Contact | ANIL RATNANI | ||||||||||
Phone | (863) 858-6711 | ||||||||||
ANILRATNANI@YAHOO.COM | |||||||||||
Placard # / Date | 698828 - 07/03/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | RATNAM USA INC 2993 DUFF RD Lakeland, FL 33810 |
Effective Date | 03/18/2009 | ||||||||
Contact | ANIL RATNANI | ||||||||||
Phone | (863) 858-6711 | ||||||||||
ANILRATNANI@YAHOO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 12000 | Unleaded Gas (B) | 08/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 12000 | Vehicular Diesel (D) | 08/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 04/07/2023 | 04/07/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 04/25/2017 | 04/25/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/25/2016 | 04/25/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/25/2015 | 04/25/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/13/2013 | 04/13/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/13/2012 | 04/25/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/06/2011 | 02/06/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/06/2010 | 02/06/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/06/2009 | 02/06/2010 | ZURICH-AMERICAN | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 08/18/2023 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 08/18/2023 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 08/18/2023 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Site Inspection | 07/31/2023 | Major Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 04/23/2020 | Major Out of Compliance | JARRETT_SE_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 04/23/2020 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Letter | 04/23/2020 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Phone Conversation | 04/21/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 04/21/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 04/21/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Issue Document | 08/02/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Enforcement Tracking | 08/02/2019 | Closed Without Enforcement | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 07/19/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 07/19/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Letter | 07/03/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 07/03/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Document Management | 07/03/2019 | Satisfied | GLENN_LE_1 | Incident | |||||||
Document Management | 07/03/2019 | Satisfied | GLENN_LE_1 | Incident | |||||||
Electronic Communication | 07/03/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Document Management | 07/03/2019 | Satisfied | GLENN_LE_1 | Incident | |||||||
Incident | 07/03/2019 | Has not led to Discharge | GLENN_LE_1 | Incident | |||||||
Electronic Communication | 07/03/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Incident | 07/03/2019 | Has not led to Discharge | GLENN_LE_1 | Incident | |||||||
Incident | 07/03/2019 | Has not led to Discharge | GLENN_LE_1 | Incident | |||||||
Meeting | 06/21/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 06/20/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/20/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/20/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Issue Document | 05/21/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 05/21/2019 | Satisfied | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 04/18/2019 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 12/27/2018 | Satisfied | KENNEDY_S | Enforcement | |||||||
Electronic Communication | 11/06/2017 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 09/06/2017 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Enforcement Referral | 08/22/2017 | Accepted | GLENN_LE_1 | Enforcement | |||||||
Letter | 08/15/2017 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 08/15/2017 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 08/14/2017 | Minor Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 07/25/2017 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Meeting | 03/27/2017 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Meeting | 03/11/2017 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Site Inspection | 12/31/2015 | Minor Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 12/31/2015 | Satisfied | GLENN_LE_1 | Non-Compliance | |||||||
Letter | 12/31/2015 | Satisfied | GLENN_LE_1 | Non-Compliance | |||||||
Electronic Communication | 11/19/2013 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 11/19/2013 | Minor Out of Compliance | WINN_JP_1 | 0/2 | Routine Compliance | ||||||
Letter | 11/19/2013 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 04/27/2012 | In Compliance | NEWBERG_DR_1 | 0/2 | Routine Compliance | ||||||
Record Document | 09/06/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 08/26/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Letter | 08/26/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 08/26/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 08/08/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Letter | 07/06/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 07/06/2011 | Minor Out of Compliance | CASSELS_CR_1 | 0/2 | Non-Compliance | ||||||
Electronic Communication | 06/21/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 06/20/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Electronic Communication | 06/20/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 06/20/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 05/20/2011 | Major Out of Compliance | CASSELS_CR_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/20/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 05/10/2010 | Minor Out of Compliance | SLAPPEY_WR_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/10/2010 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Site Inspection | 03/10/2009 | In Compliance | NEWBERG_DR_1 | 0/2 | Installation | ||||||
Site Inspection | 12/09/2008 | In Compliance | BELL_JM_1 | 0/2 | Installation | ||||||
Phone Conversation | 10/06/2008 | Satisfied | CASSELS_CR_1 | Installation | |||||||
Phone Conversation | 09/04/2008 | Satisfied | CASSELS_CR_1 | Installation | |||||||
Record Document | 09/03/2008 | Satisfied | CASSELS_CR_1 | Installation | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
07/31/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | PCW must be removed, disposed of properly and the Department notified. | |||||||
07/31/2023 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Either the FDEP Storage Tank Insurance Endorsement – Part C Form or the FDEP Storage Tank Certificate of Insurance – Part D Form (but not both) usually found as last few pages in full policy packet, must be provided to the Department. | |||||||
07/31/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Water must be removed and the Department notified. | |||||||
07/31/2023 | 6060 | SNC-B | 4.11 Release detection methods do not meet monitoring requirements. | Sensors must be placed in the proper position and the Department notified. | |||||||
04/23/2020 | 4001 | Minor | 2.2 Operator certification requirements not met. | Copies of the Class A and B Operator training certifications must be provided to the Department. | |||||||
04/23/2020 | 4014 | SNC-B | 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. | Proof of financial responsibility from 04/25/2018 to the present must be provided to the Department. | |||||||
04/23/2020 | 4012 | Minor | 2.3 For an incident, notification not received in a timely manner. | Incident Notification Forms (INFs) must be submitted to the Department for these alarms. | |||||||
04/23/2020 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | The premium/diesel interstice must be checked to determine the cause of the alarm with the investigation results submitted to the Department. - An Incident Notification Form (INF) must also be submitted to the Department. | |||||||
04/23/2020 | 4077 | Minor | 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. | Liners must be cleaned with the Department contacted for inspection. | |||||||
04/23/2020 | 4051 | Minor | 4.26 Dispenser sumps not installed to allow for release detection. | Therefore, deflector plating must be installed to direct any possible leakage into the liners and the Department contacted for inspection. | |||||||
04/23/2020 | 4015 | Minor | 2.10 Incomplete documentation demonstrating financial responsibility. | Completed Part P Forms for each coverage period that renewed after 04/25/2018 to the present must be provided to the Department. | |||||||
04/23/2020 | 4068 | Minor | 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. | Corrosion must be addressed with appropriate documentation provided to the Department. | |||||||
04/23/2020 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | Investigation results for the causes of the alarms must be submitted to the Department. | |||||||
04/23/2020 | 4062 | SNC-B | 4.6 Electronic release detection devices not inspected monthly. | Copies of the May and June 2020 inspection records must be provided to the Department as the inspections are performed including the Veeder Root panel status, liquid status, and the “L” sensor alarm histories. | |||||||
No Discharges Found |