Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Southeast | Type | State Government | ||||
County | Monroe | Status | OPEN | ||||
ID | 9810951 | Latitude | 24° 39' 29.4539 | ||||
Name |
BAHIA HONDA STATE PARK 36850 OVERSEAS HWY |
Longitude | 81° 16' 34.3353 | ||||
BIG PINE KEY, FL 33043 | LL Method | DPHO | |||||
Contact | DONALD BERGERON | LL Status | REVIEWED | ||||
Phone | (305) 872-3897 | Status Date | 09/18/2024 | ||||
Account Owner Information | |||||||
Name | BAHIA HONDA STATE PARK 36850 OVERSEAS HWY BIG PINE KEY, FL 33043 |
Effective Date | 12/29/2008 | ||||
Contact | DONNA.CHURCH | ||||||
Phone | (305) 872-3897 | ||||||
DONNA.CHURCH@FLORIDADEP.GOV | |||||||
Placard # / Date | 698413 - 07/01/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 1000 | Unleaded Gas (B) | 05/01/2008 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (L) Compartmented (M) Spill containment bucket (Q) DEP approved protection (R) Double wall - tank jacket |
(X) No piping associated w/tank | (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 01/01/2020 | 01/01/2030 | |||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 03/09/2009 | 03/09/2012 | |||||
No Legacy Data Found | |||||||
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Enforcement Referral | 08/08/2023 | Accepted | SHANBERG_V | Enforcement | |||
Letter | 08/08/2023 | Satisfied | SHANBERG_V | Compliance Assistance | |||
Site Inspection | 05/24/2023 | Major Out of Compliance | SHANBERG_V | 1/0 | Routine Compliance | ||
Site Inspection | 04/29/2020 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||
Letter | 04/29/2020 | Satisfied | WINKLER_MG_1 | Routine Compliance | |||
Letter | 12/15/2017 | Satisfied | WINKLER_MG_1 | Routine Compliance | |||
Site Inspection | 12/15/2017 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||
Site Inspection | 03/06/2015 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||
Site Inspection | 12/18/2012 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||
Site Inspection | 12/20/2011 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||
Letter | 08/06/2010 | Satisfied | LICHTLER_GB_1 | Non-Compliance | |||
Site Inspection | 08/06/2010 | Minor Out of Compliance | LICHTLER_GB_1 | 1/0 | Routine Compliance | ||
Site Inspection | 08/04/2009 | Minor Out of Compliance | SMITH_RR | 1/0 | Routine Compliance | ||
Letter | 08/04/2009 | Satisfied | SMITH_RR | Non-Compliance | |||
Site Inspection | 03/10/2009 | In Compliance | SMITH_RR | 1/0 | Installation | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
05/18/2023 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide annual operability testing documentation for overfill protection device for 2021, 202, and 2023 to the Department. | |||
05/18/2023 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide to the Department missing annual operability testing of release detection system documentation for release detection device for 2021, 2022, and 2023 | |||
05/18/2023 | 7040 | SNC-B | 3.8 Overfill protection not provided. Fuel transfer not monitored. Alarms not installed. | Install overfill protection for the facility's AST and provide installation and photo documentation to the Department. | |||
05/18/2023 | 7043 | Minor | 1.11 Fillbox covers not marked according to requirements. | Add an API color-symbol on the two (2) fill box covers for Diesel and Gasoline fuel. Send Photo documentation to the Department. | |||
No Discharges Found |