Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 9811044   Latitude    27° 54' 54.4354
 
Name LARGO DIAGNOSTICS
1301 2ND AVE SW
Longitude    82° 48' 7.128
  LARGO, FL 33770-3120 LL Method    DPHO
 
Contact JULIE MYERS   LL Status    REVIEWED
 
Phone (813) 321-2266   Status Date    06/03/2009
 
Account Owner Information
 
Name HTA-LARGO MEDICAL CENTER MOB LLC
17 DAVIS BOULEVARD SUITE 309
TAMPA, FL 33606
Effective Date    04/20/2023
 
Contact JULIE MYERS
 
Phone (813) 321-2266
 
Email JMYERS@HEALTHCAREREALTY.COM
  Placard # / Date    701230 - 09/03/2024
Property Owner Information
 
Name HTA-LARGO MEDICAL CENTER MOB LLC
17 DAVIS BOULEVARD SUITE 309
TAMPA, FL 33606
Effective Date    04/20/2023
 
Contact JULIE MYERS
 
Phone (813) 321-2266
 
Email JMYERS@HEALTHCAREREALTY.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 660 Emerg Generator Diesel (G) 04/01/2009 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(6) External piping monitoring
(F) Monitor dbl wall tank space
(R) Monitor tank bottom space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   08/28/2019 08/28/2020 ADMIRAL INSURANCE COMPANY
INSURANCE   08/28/2018 08/28/2019 ADMIRAL INSURANCE COMPANY
INSURANCE   04/08/2017 04/08/2018 ADMIRAL INSURANCE COMPANY
INSURANCE   04/08/2016 04/08/2017 ADMIRAL INSURANCE COMPANY
INSURANCE   04/08/2015 04/08/2016 ADMIRAL INSURANCE COMPANY
INSURANCE   09/01/2012 09/01/2013 ZURICH-AMERICAN
INSURANCE   09/01/2010 09/01/2011 ZURICH-AMERICAN
INSURANCE   09/01/2009 09/01/2010 ZURICH-AMERICAN
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 09/06/2024 Satisfied REIS_A Enforcement
 
Enforcement Referral 06/09/2023 Accepted SHOCK_E_1 Enforcement
 
Record Document 05/15/2023 Satisfied SHOCK_E_1 Routine Compliance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Routine Compliance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Record Document 05/12/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 05/12/2023 Satisfied SHOCK_E_1 Routine Compliance
 
Letter 01/06/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Site Inspection 01/05/2023 Major Out of Compliance SHOCK_E_1 1/0 Routine Compliance
 
Electronic Communication 12/12/2022 Satisfied SHOCK_E_1 Routine Compliance
 
Letter 04/09/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Record Document 04/09/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Letter 03/27/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Site Inspection 03/27/2020 Major Out of Compliance STRAUSS_RH_1 1/0 Routine Compliance
 
Electronic Communication 03/13/2020 Satisfied STRAUSS_RH_1 Routine Compliance
 
Letter 12/28/2017 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 12/28/2017 In Compliance STRAUSS_RH_1 1/0 Routine Compliance
 
Electronic Communication 12/14/2017 Satisfied STRAUSS_RH_1 Routine Compliance
 
Record Document 06/22/2015 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 06/22/2015 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 04/01/2015 Major Out of Compliance STRAUSS_RH_1 1/0 Routine Compliance
 
Letter 04/01/2015 Satisfied STRAUSS_RH_1 Non-Compliance
 
Electronic Communication 05/31/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Electronic Communication 05/17/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Electronic Communication 05/17/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Site Inspection 04/26/2013 Minor Out of Compliance ROGGELIN_EM_1 1/0 Routine Compliance
 
Letter 04/26/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Site Inspection 04/27/2011 In Compliance LONGEN_JL_1 1/0 Non-Compliance
 
Site Inspection 02/07/2011 Minor Out of Compliance LONGEN_JL_1 1/0 Routine Compliance
 
Letter 02/07/2011 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 02/22/2010 In Compliance ROGGELIN_EM_1 1/0 Installation
 
Issue Document 02/22/2010 Satisfied ROGGELIN_EM_1 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
01/02/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide current operability testing results for the Simplex remote fill/spill cabinet high level sensor alarm indicating the date the testing was performed and whether or not the device PASSED or FAILED.
 
01/02/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Log in visual inspection of the storage tank system conducted during this State inspection on 12/21/22, perform a visual monthly inspection for January 2023 and for February 2023, and provide a copy of the inspection log showing that the inspections are now being completed monthly, no more than 35 days apart.
 
01/02/2023 7004 Minor 1.4 Placard not displayed (or available upon request). Provide a copy of the current tank registration that expires 6/30/23, or a photography of the posted registration placard that expires 6/30/23.
 
01/02/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Provide current operability testing results for the Simplex remote fill/spill cabinet rupture basin / leak sensor alarm, or the Krueger leak gauge at the tank top, indicating the date the testing was performed and whether or not the device PASSED or FAILED.
 
01/02/2023 7011 Minor 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. Provide storage tank insurance documents showing coverage since 8/28/20. Also, complete, and provide a copy of, the current State of Florida Storage Tank Certification of Financial Responsible Part P form.
 
 
 
No Discharges Found