DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District South   Type    Fuel user/Non-retail
 
County Collier   Status    OPEN
 
ID 9811504   Latitude    25° 58' 12.7557
 
Name PORT OF THE IS COMM IMPROVEMENT DIST WWTF
12600 UNION RD
Longitude    81° 30' 22.4323
  NAPLES, FL 34114-9623 LL Method    DPHO
 
Contact ROBERT CASEY   LL Status    REVIEWED
 
Phone (239) 642-9219   Status Date    09/20/2010
 
Account Owner Information
 
Name FLORIDA UTILITY SOLUTIONS
15275 COLLIER BLVD., SUITE 201-268
NAPLES, FL 34119
Effective Date    02/09/2018
 
Contact
 
Phone (239) 513-0445
 
Email ALANA@FLORIDAUTILITYSOLUTIONS.COM
  Placard # / Date    684402 - 06/06/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 1700 Emerg Generator Diesel (G) 05/01/2009 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (X) No piping associated w/tank (1) Continuous electronic sensing
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 750 Emerg Generator Diesel (G) 01/01/1993 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
  (X) No piping associated w/tank (Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/25/2021 06/25/2023 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   02/23/2020 02/23/2021 STARSTONE SPECIALTY INSURANCE COMPANY
INSURANCE   02/23/2019 02/23/2020 STARSTONE SPECIALTY INSURANCE COMPANY
INSURANCE   02/23/2018 02/23/2019 AUTO OWNERS INSURANCE COMPANY
INSURANCE   02/23/2017 02/23/2018 AUTO OWNERS INSURANCE COMPANY
INSURANCE   06/25/2014 06/25/2015 COMMERCE & INDUSTRY
INSURANCE   06/25/2012 06/25/2013 COMMERCE & INDUSTRY
INSURANCE   06/25/2011 06/25/2012 COMMERCE & INDUSTRY
INSURANCE   06/25/2009 06/25/2010 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/06/2024 Accepted STANDIFORD_JA Enforcement
 
Record Document 04/15/2024 Satisfied STANDIFORD_JA Compliance Assistance
 
Letter 03/24/2023 Satisfied STANDIFORD_JA Compliance Assistance
 
Site Inspection 03/22/2023 Minor Out of Compliance STANDIFORD_JA 1/0 Routine Compliance
 
Electronic Communication 03/06/2023 Satisfied STANDIFORD_JA Routine Compliance
 
Letter 05/12/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Letter 04/27/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Site Inspection 04/27/2020 Major Out of Compliance HERNANDEZ_N_5 1/0 Routine Compliance
 
Electronic Communication 04/17/2020 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Electronic Communication 02/27/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Letter 02/28/2018 Satisfied BATES_TD_1 Compliance Assistance
 
Site Inspection 02/27/2018 Major Out of Compliance BATES_TD_1 1/0 Routine Compliance
 
Site Inspection 03/30/2015 In Compliance BATES_TD_1 1/0 Routine Compliance
 
Site Inspection 04/08/2013 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Site Inspection 12/06/2011 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Record Document 12/06/2011 Satisfied SPARKS_JD_1 Routine Compliance
 
Record Document 09/01/2011 Satisfied SPARKS_JD_1 Routine Compliance
 
Letter 06/30/2011 Satisfied SPARKS_JD_1 Non-Compliance
 
Site Inspection 06/30/2011 Major Out of Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Document Management 12/21/2009 Complete SNYDERBURN_PJ_2 Closure
 
Site Inspection 11/08/2009 In Compliance SNYDERBURN_PJ_2 1/0 Closure
 
Letter 09/01/2009 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 09/01/2009 Major Out of Compliance SNYDERBURN_PJ_2 2/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/16/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Please instruct Cummins to perform annual testing on the rupture basin alarm as part of the regularly scheduled maintenance within 90 days of the inspection date and provide the completed test result to the inspector via email at James.Standiford@colliercountyfl.gov within the same time frame.
 
03/16/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please contact the facility's contractor to request documentation stating the OPD's were tested annually on or before 2/26/2020, 2/26/2021, 2/26/2022, and 2/26/2023 in accordance with the manufacturer's recommendation. Please submit the AO testing records via email to the inspector at James.Standiford@colliercountyfl.gov within 90 days of the inspection date. If these AO testing records cannot be located, please schedule AO testing of both devices within 90 days of the inspection date and provide documentation showing the devices were tested via email within the same time frame.
 
 
 
No Discharges Found