Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | State Government | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 9811560 | Latitude | 27° 39' 56.4107 | ||||||||
Name |
HIGHLANDS YOUTH ACADEMY 242 SOUTH BLVD |
Longitude | 81° 22' 6.1494 | ||||||||
AVON PARK, FL 33825-9200 | LL Method | DPHO | |||||||||
Contact | LATOYA WILLIAMS | LL Status | REVIEWED | ||||||||
Phone | (863) 559-3780 | Status Date | 09/20/2023 | ||||||||
Account Owner Information | |||||||||||
Name | STCM ADMIN - OWNER UNKNOWN 2600 BLAIR STONE RD TALLAHASSEE, FL 32399-2400 |
Effective Date | 10/17/2024 | ||||||||
Contact | STORAGE TANK REGISTRATION | ||||||||||
Phone | (850) 245-2450 | ||||||||||
TANKREGISTRATION@DEP.STATE.FL.US | |||||||||||
Placard # / Date | |||||||||||
Property Owner Information | |||||||||||
Name | FL DEPT OF JUVENILE JUSTICE 2737 CENTERVIEW DR KNIGHT BLDG RM2205 TALLAHASSEE, FL 32399-998 |
Effective Date | 07/28/2009 | ||||||||
Contact | NATOSHA GRAVES | ||||||||||
Phone | (850) 717-2543 | ||||||||||
NATOSHA.GRAVES@FLDJJ.GOV | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2000 | Emerg Generator Diesel (G) | 07/01/2009 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system (N) Approved synthetic material |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | |||||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 01/01/2021 | 12/31/2021 | |||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 01/01/2018 | 01/01/2019 | |||||||||
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY | 07/01/2009 | 07/01/2010 | |||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 05/19/2021 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 05/19/2021 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Site Inspection | 05/19/2021 | Major Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 05/15/2021 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Phone Conversation | 05/15/2021 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Meeting | 10/11/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/11/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/11/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/11/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 05/07/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Letter | 05/07/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Site Inspection | 05/07/2018 | Minor Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 05/05/2018 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 05/05/2018 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 05/05/2018 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Phone Conversation | 05/05/2018 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Site Inspection | 08/25/2015 | In Compliance | MERRYMAN_DT_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 08/25/2015 | Satisfied | MERRYMAN_DT_1 | Routine Compliance | |||||||
Issue Document | 10/08/2013 | Satisfied | WINN_JP_1 | Routine Compliance | |||||||
Site Inspection | 10/08/2013 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/26/2013 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Issue Document | 06/26/2013 | Satisfied | WINN_JP_1 | Routine Compliance | |||||||
Site Inspection | 04/30/2012 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 09/29/2011 | Closed Without Enforcement | PEDIGO_L | Enforcement | |||||||
Enforcement Referral | 09/01/2011 | Accepted | PEDIGO_L | Enforcement | |||||||
Phone Conversation | 08/23/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 08/11/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 08/03/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||||||
Letter | 07/25/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||||||
Phone Conversation | 07/13/2011 | Satisfied | BELL_JM_1 | Routine Compliance | |||||||
Letter | 06/03/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||||||
Site Inspection | 06/03/2011 | Major Out of Compliance | BELL_JM_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 10/02/2009 | In Compliance | SLAPPEY_WR_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/19/2021 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Either the missing test records must be provided, or the test performed immediately with the test results submitted to the Department. | |||||||
05/19/2021 | 5005 | SNC-B | 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. | A copy of the registration placard must be posted or otherwise available on site for review by the fuel delivery drivers prior to pumping fuel into the tank with a copy submitted to the Department. | |||||||
05/19/2021 | 5127 | Minor | 3.17 Exterior Coatings not maintained to prevent corrosion for shop fabricated storage tank systems. | Corrosion must be addressed and the Department contacted for inspection. | |||||||
05/19/2021 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Copies of the next two (June and July 2021) monthly release detection inspection records must be submitted to the Department as the inspections are performed. | |||||||
05/19/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | An overfill protection device approved by/registered with FDEP must be installed and the Department contacted for inspection. | |||||||
05/05/2018 | 5168 | Minor | 1.2 Storage tank system equipment not registered with the Department. | Per the rule revision, the Rochester fuel level site gauge is no longer accepted as an overfill prevention device effective January 11, 2018; therefore, it can only be utilized as a fuel level indicator and an approved, overfill prevention device must be installed. | |||||||
No Discharges Found |