DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Southwest   Type    State Government
 
County Polk   Status    OPEN
 
ID 9811560   Latitude    27° 39' 56.4107
 
Name HIGHLANDS YOUTH ACADEMY
242 SOUTH BLVD
Longitude    81° 22' 6.1494
  AVON PARK, FL 33825-9200 LL Method    DPHO
 
Contact LATOYA WILLIAMS   LL Status    REVIEWED
 
Phone (863) 559-3780   Status Date    09/20/2023
 
Account Owner Information
 
Name STCM ADMIN - OWNER UNKNOWN
2600 BLAIR STONE RD
TALLAHASSEE, FL 32399-2400
Effective Date    10/17/2024
 
Contact STORAGE TANK REGISTRATION
 
Phone (850) 245-2450
 
Email TANKREGISTRATION@DEP.STATE.FL.US
  Placard # / Date   
Property Owner Information
 
Name FL DEPT OF JUVENILE JUSTICE
2737 CENTERVIEW DR KNIGHT BLDG RM2205
TALLAHASSEE, FL 32399-998
Effective Date    07/28/2009
 
Contact NATOSHA GRAVES
 
Phone (850) 717-2543
 
Email NATOSHA.GRAVES@FLDJJ.GOV
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 2000 Emerg Generator Diesel (G) 07/01/2009 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY   01/01/2021 12/31/2021
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY   01/01/2018 01/01/2019
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY   07/01/2009 07/01/2010
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 05/19/2021 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 05/19/2021 Satisfied JARRETT_SE_1 Compliance Assistance
 
Site Inspection 05/19/2021 Major Out of Compliance JARRETT_SE_1 1/0 Routine Compliance
 
Electronic Communication 05/15/2021 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/15/2021 Satisfied JARRETT_SE_1 Routine Compliance
 
Meeting 10/11/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 10/11/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 10/11/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 10/11/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Electronic Communication 05/07/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Letter 05/07/2018 Satisfied JARRETT_SE_1 Compliance Assistance
 
Site Inspection 05/07/2018 Minor Out of Compliance JARRETT_SE_1 1/0 Routine Compliance
 
Electronic Communication 05/05/2018 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 05/05/2018 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 05/05/2018 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/05/2018 Satisfied JARRETT_SE_1 Routine Compliance
 
Site Inspection 08/25/2015 In Compliance MERRYMAN_DT_1 1/0 Routine Compliance
 
Electronic Communication 08/25/2015 Satisfied MERRYMAN_DT_1 Routine Compliance
 
Issue Document 10/08/2013 Satisfied WINN_JP_1 Routine Compliance
 
Site Inspection 10/08/2013 In Compliance WINN_JP_1 1/0 Routine Compliance
 
Site Inspection 06/26/2013 In Compliance WINN_JP_1 1/0 Routine Compliance
 
Issue Document 06/26/2013 Satisfied WINN_JP_1 Routine Compliance
 
Site Inspection 04/30/2012 In Compliance CASSELS_CR_1 1/0 Routine Compliance
 
Enforcement Tracking 09/29/2011 Closed Without Enforcement PEDIGO_L Enforcement
 
Enforcement Referral 09/01/2011 Accepted PEDIGO_L Enforcement
 
Phone Conversation 08/23/2011 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 08/11/2011 Satisfied DERY_WC_1 Non-Compliance
 
Record Document 08/03/2011 Satisfied BELL_JM_1 Non-Compliance
 
Letter 07/25/2011 Satisfied BELL_JM_1 Non-Compliance
 
Phone Conversation 07/13/2011 Satisfied BELL_JM_1 Routine Compliance
 
Letter 06/03/2011 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 06/03/2011 Major Out of Compliance BELL_JM_1 1/0 Routine Compliance
 
Site Inspection 10/02/2009 In Compliance SLAPPEY_WR_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/19/2021 5102 Minor 3.3 Shop fabricated storage tank system release detection devices not tested annually. Either the missing test records must be provided, or the test performed immediately with the test results submitted to the Department.
 
05/19/2021 5005 SNC-B 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. A copy of the registration placard must be posted or otherwise available on site for review by the fuel delivery drivers prior to pumping fuel into the tank with a copy submitted to the Department.
 
05/19/2021 5127 Minor 3.17 Exterior Coatings not maintained to prevent corrosion for shop fabricated storage tank systems. Corrosion must be addressed and the Department contacted for inspection.
 
05/19/2021 5094 SNC-B 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. Copies of the next two (June and July 2021) monthly release detection inspection records must be submitted to the Department as the inspections are performed.
 
05/19/2021 5042 SNC-B 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. An overfill protection device approved by/registered with FDEP must be installed and the Department contacted for inspection.
 
05/05/2018 5168 Minor 1.2 Storage tank system equipment not registered with the Department. Per the rule revision, the Rochester fuel level site gauge is no longer accepted as an overfill prevention device effective January 11, 2018; therefore, it can only be utilized as a fuel level indicator and an approved, overfill prevention device must be installed.
 
 
 
No Discharges Found