DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District South   Type    Agricultural
 
County Collier   Status    OPEN
 
ID 9811590   Latitude    26° 18' 9.8963
 
Name PF 8
15000 CR 858 E
Longitude    81° 18' 24.9605
  IMMOKALEE, FL 34142 LL Method    DPHO
 
Contact WADE PURVIS   LL Status    REVIEWED
 
Phone (239) 398-3303   Status Date    09/20/2010
 
Account Owner Information
 
Name PURVIS FARMS LLC
PO BOX 3447
IMMOKALEE, FL 34143
Effective Date    06/25/2021
 
Contact WADE PURVIS
 
Phone (239) 398-3303
 
Email WPURVIS@ALLIANCE-PACKING.COM
  Placard # / Date    705473 - 04/02/2025
Property Owner Information
 
Name PURVIS FARMS LLC
PO BOX 3447
IMMOKALEE, FL 34143
Effective Date    06/25/2021
 
Contact WADE PURVIS
 
Phone (239) 398-3303
 
Email WPURVIS@ALLIANCE-PACKING.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 2000 Vehicular Diesel (D) 08/01/2009 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(Q) DEP approved protection
(R) Double wall - tank jacket
  (X) No piping associated w/tank (F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   01/01/2019 01/01/2022 ILLINOIS UNION INSURANCE COMPANY
INSURANCE   01/01/2016 01/01/2019 ILLINOIS UNION INSURANCE COMPANY
INSURANCE   08/15/2015 08/15/2016 COMMERCE & INDUSTRY
INSURANCE   08/15/2014 08/15/2015 COMMERCE & INDUSTRY
INSURANCE   08/15/2013 08/15/2014 COMMERCE & INDUSTRY
INSURANCE   08/15/2012 08/15/2013 COMMERCE & INDUSTRY
INSURANCE   08/15/2010 08/15/2011 COMMERCE & INDUSTRY
INSURANCE   08/28/2009 08/15/2010 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 03/24/2025 Accepted STANDIFORD_JA Enforcement
 
Letter 12/02/2024 Satisfied STANDIFORD_JA Compliance Assistance
 
Site Inspection 11/25/2024 Minor Out of Compliance STANDIFORD_JA 1/0 Routine Compliance
 
Site Inspection 04/23/2021 In Compliance JENSEN_NJ_1 1/0 Routine Compliance
 
Letter 04/23/2021 Satisfied JENSEN_NJ_1 Routine Compliance
 
Electronic Communication 04/06/2021 Satisfied JENSEN_NJ_1 Routine Compliance
 
Site Inspection 05/31/2018 In Compliance STANDIFORD_JA_2 1/0 Routine Compliance
 
Site Inspection 06/14/2017 In Compliance STANDIFORD_JA_2 1/0 Non-Compliance
 
Letter 01/04/2016 Satisfied STANDIFORD_JA_2 Non-Compliance
 
Site Inspection 12/30/2015 Minor Out of Compliance STANDIFORD_JA_2 1/0 Routine Compliance
 
Site Inspection 07/28/2014 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Site Inspection 02/28/2013 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Site Inspection 06/29/2011 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Site Inspection 09/11/2009 In Compliance SNYDERBURN_PJ_2 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/21/2024 7011 Minor 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. Within 90 days of the Inspection date, please email the current storage tank pollution liability insurance policy and previous annual policies going back three years (with FDEP Forms C/D and P) to the Inspector.
 
11/21/2024 7064 Minor 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Within 90 days of the Inspection date please provide current MVI/release detection records and associated records going back three years to the Inspector via email. If associated records cannot be located, please perform two months worth of MVI's and email the MVI log to the Inspector within the same time frame.
 
11/21/2024 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Within 90 days of the Inspection date please locate previous annual testing records and repair the Krueger level gauge. Please perform operability testing on the unit at replacement/installation and record findings on the provided Krueger gauge testing record. Please email previous testing records (documented on MVI logs) if located and the newly completed Krueger gauge testing record (attached) to the Inspector within the same time frame.
 
11/21/2024 6005 Minor 2.4 Registration fees not paid (not receiving fuel). Within 90 days of the Inspection date, please renew the storage tank registration fee online through FDEP's ESSA business portal and email a copy of the issued placard to the Inspector within the same time frame. The link to the registration website is https://floridadep.gov/waste/permitting-compliance-assistance/content/storage-tank-facility-registration
 
 
 
No Discharges Found