Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Agricultural | ||||||||
County | Collier | Status | OPEN | ||||||||
ID | 9811590 | Latitude | 26° 18' 9.8963 | ||||||||
Name |
PF 8 15000 CR 858 E |
Longitude | 81° 18' 24.9605 | ||||||||
IMMOKALEE, FL 34142 | LL Method | DPHO | |||||||||
Contact | WADE PURVIS | LL Status | REVIEWED | ||||||||
Phone | (239) 398-3303 | Status Date | 09/20/2010 | ||||||||
Account Owner Information | |||||||||||
Name | PURVIS FARMS LLC PO BOX 3447 IMMOKALEE, FL 34143 |
Effective Date | 06/25/2021 | ||||||||
Contact | WADE PURVIS | ||||||||||
Phone | (239) 398-3303 | ||||||||||
WPURVIS@ALLIANCE-PACKING.COM | |||||||||||
Placard # / Date | 705473 - 04/02/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | PURVIS FARMS LLC PO BOX 3447 IMMOKALEE, FL 34143 |
Effective Date | 06/25/2021 | ||||||||
Contact | WADE PURVIS | ||||||||||
Phone | (239) 398-3303 | ||||||||||
WPURVIS@ALLIANCE-PACKING.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2000 | Vehicular Diesel (D) | 08/01/2009 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket (Q) DEP approved protection (R) Double wall - tank jacket |
(X) No piping associated w/tank | (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 01/01/2019 | 01/01/2022 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 01/01/2016 | 01/01/2019 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 08/15/2015 | 08/15/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 08/15/2014 | 08/15/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 08/15/2013 | 08/15/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 08/15/2012 | 08/15/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 08/15/2010 | 08/15/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 08/28/2009 | 08/15/2010 | COMMERCE & INDUSTRY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 03/24/2025 | Accepted | STANDIFORD_JA | Enforcement | |||||||
Letter | 12/02/2024 | Satisfied | STANDIFORD_JA | Compliance Assistance | |||||||
Site Inspection | 11/25/2024 | Minor Out of Compliance | STANDIFORD_JA | 1/0 | Routine Compliance | ||||||
Site Inspection | 04/23/2021 | In Compliance | JENSEN_NJ_1 | 1/0 | Routine Compliance | ||||||
Letter | 04/23/2021 | Satisfied | JENSEN_NJ_1 | Routine Compliance | |||||||
Electronic Communication | 04/06/2021 | Satisfied | JENSEN_NJ_1 | Routine Compliance | |||||||
Site Inspection | 05/31/2018 | In Compliance | STANDIFORD_JA_2 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/14/2017 | In Compliance | STANDIFORD_JA_2 | 1/0 | Non-Compliance | ||||||
Letter | 01/04/2016 | Satisfied | STANDIFORD_JA_2 | Non-Compliance | |||||||
Site Inspection | 12/30/2015 | Minor Out of Compliance | STANDIFORD_JA_2 | 1/0 | Routine Compliance | ||||||
Site Inspection | 07/28/2014 | In Compliance | SPARKS_JD_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 02/28/2013 | In Compliance | SPARKS_JD_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/29/2011 | In Compliance | SPARKS_JD_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 09/11/2009 | In Compliance | SNYDERBURN_PJ_2 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
11/21/2024 | 7011 | Minor | 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. | Within 90 days of the Inspection date, please email the current storage tank pollution liability insurance policy and previous annual policies going back three years (with FDEP Forms C/D and P) to the Inspector. | |||||||
11/21/2024 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Within 90 days of the Inspection date please provide current MVI/release detection records and associated records going back three years to the Inspector via email. If associated records cannot be located, please perform two months worth of MVI's and email the MVI log to the Inspector within the same time frame. | |||||||
11/21/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Within 90 days of the Inspection date please locate previous annual testing records and repair the Krueger level gauge. Please perform operability testing on the unit at replacement/installation and record findings on the provided Krueger gauge testing record. Please email previous testing records (documented on MVI logs) if located and the newly completed Krueger gauge testing record (attached) to the Inspector within the same time frame. | |||||||
11/21/2024 | 6005 | Minor | 2.4 Registration fees not paid (not receiving fuel). | Within 90 days of the Inspection date, please renew the storage tank registration fee online through FDEP's ESSA business portal and email a copy of the issued placard to the Inspector within the same time frame. The link to the registration website is https://floridadep.gov/waste/permitting-compliance-assistance/content/storage-tank-facility-registration | |||||||
No Discharges Found |