DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District South   Type    Marine/Coastal Fuel Storage
 
County Collier   Status    OPEN
 
ID 9811753   Latitude    25° 52' 3.007
 
Name EVERGLADES ISLE MARINA
803 N COLLIER BLVD
Longitude    81° 23' .6225
  EVERGLADES CITY, FL 34139 LL Method    DPHO
 
Contact MARK HELSEL   LL Status    REVIEWED
 
Phone (239) 695-2600   Status Date    09/20/2010
 
Account Owner Information
 
Name BARRON RIVER MARKER #55 LLC
PO BOX 729
BELLEVILLE, MI 48112
Effective Date    04/08/2019
 
Contact JAMES A MOSKAL
 
Phone (734) 547-9237
 
Email JMOSKAL@CORBYENERGY.COM
  Placard # / Date    683169 - 06/05/2024
Property Owner Information
 
Name OUR 2ND HALF LLC
PO BOX 729
BELLEVILLE, MI 48112
Effective Date    04/08/2019
 
Contact JAMES A MOSKAL
 
Phone (734) 547-9237
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 3000 Unleaded Gas (B) 10/01/2009 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   01/11/2022 04/10/2023 AXIS SURPLUS INSURANCE COMPANY
INSURANCE   01/11/2021 01/11/2022 AXIS SURPLUS INSURANCE COMPANY
INSURANCE   04/16/2020 04/16/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   04/16/2019 04/16/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/27/2018 10/27/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/27/2017 10/27/2018 COMMERCE & INDUSTRY
INSURANCE   10/27/2016 10/27/2017 COMMERCE & INDUSTRY
INSURANCE   10/27/2015 10/27/2016 COMMERCE & INDUSTRY
INSURANCE   10/27/2014 10/27/2015 COMMERCE & INDUSTRY
INSURANCE   10/27/2013 10/27/2014 COMMERCE & INDUSTRY
INSURANCE   10/27/2012 10/27/2013 COMMERCE & INDUSTRY
INSURANCE   10/27/2010 10/27/2011 COMMERCE & INDUSTRY
INSURANCE   11/18/2009 11/18/2010 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/06/2024 Accepted STANDIFORD_JA Enforcement
 
Letter 03/24/2023 Satisfied STANDIFORD_JA Compliance Assistance
 
Site Inspection 03/24/2023 Major Out of Compliance STANDIFORD_JA 1/0 Routine Compliance
 
Electronic Communication 03/06/2023 Satisfied STANDIFORD_JA Routine Compliance
 
Letter 06/26/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 06/26/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 06/17/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 06/12/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 05/22/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 05/11/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Site Inspection 04/21/2020 Major Out of Compliance HERNANDEZ_N_5 1/0 Routine Compliance
 
Letter 04/21/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 04/21/2020 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Letter 05/21/2018 Satisfied BATES_TD_1 Compliance Assistance
 
Site Inspection 05/18/2018 In Compliance BATES_TD_1 1/0 Compliance Assistance
 
Record Document 04/12/2018 Satisfied BATES_TD_1 Compliance Assistance
 
Letter 02/28/2018 Satisfied BATES_TD_1 Compliance Assistance
 
Site Inspection 02/27/2018 Major Out of Compliance BATES_TD_1 1/0 Routine Compliance
 
Letter 07/21/2017 Satisfied BATES_TD_1 Compliance Assistance
 
Site Inspection 07/19/2017 In Compliance BATES_TD_1 1/0 Compliance Assistance
 
Meeting 06/28/2017 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Letter 06/26/2015 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 06/25/2015 Minor Out of Compliance BATES_TD_1 1/0 Routine Compliance
 
Site Inspection 06/17/2014 Minor Out of Compliance SNYDERBURN_PJ_2 1/0 Routine Compliance
 
Letter 06/17/2014 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 07/16/2013 In Compliance SNYDERBURN_PJ_2 1/0 Non-Compliance
 
Letter 07/08/2013 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 06/29/2013 Minor Out of Compliance SNYDERBURN_PJ_2 1/0 Routine Compliance
 
Site Inspection 06/24/2011 In Compliance SPARKS_JD_1 1/0 Routine Compliance
 
Site Inspection 12/27/2009 In Compliance SNYDERBURN_PJ_2 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/14/2023 7064 Minor 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. The facility must perform monthly visual inspections of the storage tank exterior, spill bucket, steel ASWP, piping transition sumps, dispenser sump, double walled piping in sumps, dispenser hose, and Krueger interstitial gauge monthly not to exceed 35 days. These records must be continually maintained for a period of three years. Please provide two months worth of MVI's for March and April 2023 to the inspector via e-mail to James.Standiford@colliercountyfl.gov within 90 days of the inspection date.
 
03/14/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please designate which device is the primary overfill prevention device (OPD) of the storage tank system and have operability testing performed. Please ensure operability testing is scheduled and a completed test record is emailed to the inspector within 90 days of the inspection date to James.Standiford@colliercountyfl.gov. The facility has an overfill prevention valve present in the fill port and a Morrison Brothers 818 fuel level clock gauge with Morrison Brothers 918S overfill audible alarm. It is recommended that all OPD's be tested annually, since they are present on the AST.
 
03/14/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Please perform AO testing on the Krueger interstitial gauge and ensure AO testing is performed annually not to exceed 12 months or 365 days. Please note the manufacturer recommends operability testing be performed twice a calendar year or every six months (January and July). Please provide a photo documenting the Kruger interstitial gauge float and metal components have been inspected and tested to ensure the level indicator raises within 90 days of the inspection date to James.Standiford@colliercountyfl.gov.
 
03/14/2023 7055 SNC-B 3.3 Pressurized piping not installed with line leak detectors or does not meet requirements of paragraph 62-762.601(4)(b). Please provide line leak detection testing records for 2021 and 2022 to the inspector and if records cannot be located please schedule line leak detection testing and provide the completed test record within 90 days of the inspection date to the inspector at James.Standiford@colliercountyfl.gov.
 
03/14/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Please have the water removed. Once removed, please take pictures of each piping transition sump and dispenser sump and email them to James.Standiford@colliergov.net within 90 days of the inspection date. Please ensure that additional photos are provided documenting the underground piping interstice is open in each transition sump and dispenser sump.
 
 
 
No Discharges Found