Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Marine/Coastal Fuel Storage | ||||||||
County | Collier | Status | OPEN | ||||||||
ID | 9811753 | Latitude | 25° 52' 3.007 | ||||||||
Name |
EVERGLADES ISLE MARINA 803 N COLLIER BLVD |
Longitude | 81° 23' .6225 | ||||||||
EVERGLADES CITY, FL 34139 | LL Method | DPHO | |||||||||
Contact | MARK HELSEL | LL Status | REVIEWED | ||||||||
Phone | (239) 695-2600 | Status Date | 09/20/2010 | ||||||||
Account Owner Information | |||||||||||
Name | BARRON RIVER MARKER #55 LLC PO BOX 729 BELLEVILLE, MI 48112 |
Effective Date | 04/08/2019 | ||||||||
Contact | JAMES A MOSKAL | ||||||||||
Phone | (734) 547-9237 | ||||||||||
JMOSKAL@CORBYENERGY.COM | |||||||||||
Placard # / Date | 683169 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | OUR 2ND HALF LLC PO BOX 729 BELLEVILLE, MI 48112 |
Effective Date | 04/08/2019 | ||||||||
Contact | JAMES A MOSKAL | ||||||||||
Phone | (734) 547-9237 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 3000 | Unleaded Gas (B) | 10/01/2009 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 01/11/2022 | 04/10/2023 | AXIS SURPLUS INSURANCE COMPANY | ||||||||
INSURANCE | 01/11/2021 | 01/11/2022 | AXIS SURPLUS INSURANCE COMPANY | ||||||||
INSURANCE | 04/16/2020 | 04/16/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/16/2019 | 04/16/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/27/2018 | 10/27/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/27/2017 | 10/27/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2016 | 10/27/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2015 | 10/27/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2014 | 10/27/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2013 | 10/27/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2012 | 10/27/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/27/2010 | 10/27/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/18/2009 | 11/18/2010 | COMMERCE & INDUSTRY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 11/06/2024 | Accepted | STANDIFORD_JA | Enforcement | |||||||
Letter | 03/24/2023 | Satisfied | STANDIFORD_JA | Compliance Assistance | |||||||
Site Inspection | 03/24/2023 | Major Out of Compliance | STANDIFORD_JA | 1/0 | Routine Compliance | ||||||
Electronic Communication | 03/06/2023 | Satisfied | STANDIFORD_JA | Routine Compliance | |||||||
Letter | 06/26/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 06/26/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 06/17/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 06/12/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 05/22/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 05/11/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Site Inspection | 04/21/2020 | Major Out of Compliance | HERNANDEZ_N_5 | 1/0 | Routine Compliance | ||||||
Letter | 04/21/2020 | Satisfied | HERNANDEZ_N_5 | Compliance Assistance | |||||||
Electronic Communication | 04/21/2020 | Satisfied | HERNANDEZ_N_5 | Routine Compliance | |||||||
Letter | 05/21/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Site Inspection | 05/18/2018 | In Compliance | BATES_TD_1 | 1/0 | Compliance Assistance | ||||||
Record Document | 04/12/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Letter | 02/28/2018 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Site Inspection | 02/27/2018 | Major Out of Compliance | BATES_TD_1 | 1/0 | Routine Compliance | ||||||
Letter | 07/21/2017 | Satisfied | BATES_TD_1 | Compliance Assistance | |||||||
Site Inspection | 07/19/2017 | In Compliance | BATES_TD_1 | 1/0 | Compliance Assistance | ||||||
Meeting | 06/28/2017 | Satisfied | STANDIFORD_JA_2 | Compliance Assistance | |||||||
Letter | 06/26/2015 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 06/25/2015 | Minor Out of Compliance | BATES_TD_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/17/2014 | Minor Out of Compliance | SNYDERBURN_PJ_2 | 1/0 | Routine Compliance | ||||||
Letter | 06/17/2014 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 07/16/2013 | In Compliance | SNYDERBURN_PJ_2 | 1/0 | Non-Compliance | ||||||
Letter | 07/08/2013 | Satisfied | SNYDERBURN_PJ_2 | Non-Compliance | |||||||
Site Inspection | 06/29/2013 | Minor Out of Compliance | SNYDERBURN_PJ_2 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/24/2011 | In Compliance | SPARKS_JD_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 12/27/2009 | In Compliance | SNYDERBURN_PJ_2 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/14/2023 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | The facility must perform monthly visual inspections of the storage tank exterior, spill bucket, steel ASWP, piping transition sumps, dispenser sump, double walled piping in sumps, dispenser hose, and Krueger interstitial gauge monthly not to exceed 35 days. These records must be continually maintained for a period of three years. Please provide two months worth of MVI's for March and April 2023 to the inspector via e-mail to James.Standiford@colliercountyfl.gov within 90 days of the inspection date. | |||||||
03/14/2023 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Please designate which device is the primary overfill prevention device (OPD) of the storage tank system and have operability testing performed. Please ensure operability testing is scheduled and a completed test record is emailed to the inspector within 90 days of the inspection date to James.Standiford@colliercountyfl.gov. The facility has an overfill prevention valve present in the fill port and a Morrison Brothers 818 fuel level clock gauge with Morrison Brothers 918S overfill audible alarm. It is recommended that all OPD's be tested annually, since they are present on the AST. | |||||||
03/14/2023 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Please perform AO testing on the Krueger interstitial gauge and ensure AO testing is performed annually not to exceed 12 months or 365 days. Please note the manufacturer recommends operability testing be performed twice a calendar year or every six months (January and July). Please provide a photo documenting the Kruger interstitial gauge float and metal components have been inspected and tested to ensure the level indicator raises within 90 days of the inspection date to James.Standiford@colliercountyfl.gov. | |||||||
03/14/2023 | 7055 | SNC-B | 3.3 Pressurized piping not installed with line leak detectors or does not meet requirements of paragraph 62-762.601(4)(b). | Please provide line leak detection testing records for 2021 and 2022 to the inspector and if records cannot be located please schedule line leak detection testing and provide the completed test record within 90 days of the inspection date to the inspector at James.Standiford@colliercountyfl.gov. | |||||||
03/14/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Please have the water removed. Once removed, please take pictures of each piping transition sump and dispenser sump and email them to James.Standiford@colliergov.net within 90 days of the inspection date. Please ensure that additional photos are provided documenting the underground piping interstice is open in each transition sump and dispenser sump. | |||||||
No Discharges Found |