DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District South   Type    Retail Station
 
County Lee   Status    OPEN
 
ID 9812350   Latitude    26° 41' 48.101
 
Name SUNSHINE#291
1625 KISMET PKWY E
Longitude    81° 56' 22.176
  CAPE CORAL, FL 33909-4735 LL Method    DPHO
 
Contact MAXIMO ALVAREZ   LL Status    REVIEWED
 
Phone (305) 477-5800   Status Date    05/17/2011
 
Account Owner Information
 
Name SUNSHINE GASOLINE DISTRIBUTORS INC
1650 NW 87TH AVE
Doral, FL 33172-2614
Effective Date    09/26/2022
 
Contact MARIO ZAMORA / VANESSA PALACIOS/BARBIE RUIZ
 
Phone (786) 606-0917
 
Email MZAMORA@SUNSHINEGASOLINE.COM
  Placard # / Date    694753 - 06/25/2024
Property Owner Information
 
Name SUNSHINE DADE INVESTMENTS LLC
1650 NW 87 AVE
DORAL, FL 33172
Effective Date    09/26/2022
 
Contact MAX ALVAREZ
 
Phone (305) 477-5800
 
Email NGARCIA@SUNSHINEGASOLINE.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 12000 Unleaded Gas (B) 08/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
(T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
2 12000 Unleaded Gas (B) 08/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
(T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
3 12000 Vehicular Diesel (D) 08/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
(T) Annual tightness test/Inventory
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   09/25/2023 09/25/2024 NAUTILUS INSURANCE COMPANY
INSURANCE   03/01/2022 03/01/2023 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/08/2017 10/08/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/08/2016 10/08/2017 COMMERCE & INDUSTRY
INSURANCE   10/08/2015 10/08/2016 COMMERCE & INDUSTRY
INSURANCE   10/08/2013 10/08/2014 COMMERCE & INDUSTRY
INSURANCE   10/08/2012 10/08/2013 COMMERCE & INDUSTRY
INSURANCE   10/08/2011 10/08/2012 COMMERCE & INDUSTRY
INSURANCE   10/08/2010 10/08/2011 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 01/09/2024 Satisfied KLEINMANN_K_1 Routine Compliance
 
Site Inspection 01/09/2024 Major Out of Compliance KLEINMANN_K_1 0/3 Routine Compliance
 
Phone Conversation 10/24/2022 Satisfied KLEINMANN_K_1 Routine Compliance
 
Letter 10/24/2022 Satisfied KLEINMANN_K_1 Compliance Assistance
 
Letter 06/24/2022 Satisfied KLEINMANN_K_1 Compliance Assistance
 
Electronic Communication 06/10/2022 Satisfied KLEINMANN_K_1 Routine Compliance
 
Site Inspection 06/10/2022 Minor Out of Compliance KLEINMANN_K_1 0/3 Routine Compliance
 
Letter 04/27/2020 Satisfied KLEINMANN_K_1 Compliance Assistance
 
Site Inspection 04/24/2020 Minor Out of Compliance KLEINMANN_K_1 0/3 Routine Compliance
 
Site Inspection 11/15/2017 In Compliance ZIMMERMAN_CA_1 0/3 Routine Compliance
 
Site Inspection 03/22/2017 In Compliance JOHNSON_SG_1 0/3 Installation
 
Site Inspection 01/22/2016 In Compliance JOHNSON_SG_1 0/3 Non-Compliance
 
Site Inspection 10/23/2015 Major Out of Compliance JOHNSON_SG_1 0/3 Routine Compliance
 
Letter 10/23/2015 Satisfied JOHNSON_SG_1 Non-Compliance
 
Record Document 02/21/2014 Satisfied JOHNSON_SG_1 Non-Compliance
 
Site Inspection 11/15/2013 Major Out of Compliance JOHNSON_SG_1 0/3 Routine Compliance
 
Emergency Preparedness Information 11/15/2013 Satisfied JOHNSON_SG_1 Routine Compliance
 
Letter 11/15/2013 Satisfied JOHNSON_SG_1 Non-Compliance
 
Site Inspection 02/22/2013 In Compliance JOHNSON_SG_1 0/3 Non-Compliance
 
Site Inspection 11/20/2012 Major Out of Compliance JOHNSON_SG_1 0/3 Routine Compliance
 
Letter 11/20/2012 Satisfied JOHNSON_SG_1 Non-Compliance
 
Emergency Preparedness Information 11/14/2012 Satisfied ZIMMERMAN_CA_1 Routine Compliance
 
Enforcement Referral 06/11/2012 Cancelled JOHNSON_SG_1 Enforcement
 
Site Inspection 03/13/2012 In Compliance JOHNSON_SG_1 0/3 Non-Compliance
 
Site Inspection 12/06/2011 Major Out of Compliance JOHNSON_SG_1 0/3 Routine Compliance
 
Letter 11/23/2011 Satisfied JOHNSON_SG_1 Non-Compliance
 
Emergency Preparedness Information 11/22/2011 Satisfied JOHNSON_SG_1 Routine Compliance
 
Site Inspection 11/04/2010 In Compliance ZIMMERMAN_CA_1 0/3 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
01/05/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Tighten all and maintain all loose shear valves.
 
01/05/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Replace sensor.
 
01/05/2024 6021 SNC-B 4.1 Failure of secondary containment to meet standards including: impervious spill containment, liners, allowing for release detection, allow for monitoring point, and hydrant pit secondary containment. Hydrostatic testing will need to be performed within 15 days and repairs made to STP sumps if recommended by testing.
 
01/05/2024 6075 Minor 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. At least one person on site per shift will need to have an operator certificate.
 
 
 
No Discharges Found