Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 9812554 | Latitude | 27° 56' 49.8689 | ||||||||
Name |
HAMPTON INN & SUITES-LAKE WALES 22900 HWY 27 |
Longitude | 81° 37' 4.2845 | ||||||||
LAKE WALES, FL 33853 | LL Method | DPHO | |||||||||
Contact | MANAGER ON DUTY | LL Status | REVIEWED | ||||||||
Phone | (863) 734-3000 | Status Date | 02/26/2024 | ||||||||
Account Owner Information | |||||||||||
Name | HAMPTON INN & SUITES 22900 HWY 27 LAKE WALES, FL 33859 |
Effective Date | 04/24/2013 | ||||||||
Contact | DAVID GLAUSSER | ROSE MARIE BARFIELD | ||||||||||
Phone | (863) 763-7439 | ||||||||||
ROSEBARFIELD@JFMINC.BIZ | |||||||||||
Placard # / Date | 702375 - 10/19/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | KKM ENTERPRISES INC 100% 2301 LONGLEAF BLVD LAKE WALES, FL 33859-2548 |
Effective Date | 04/12/2011 | ||||||||
Contact | JOE MIRANDA | ||||||||||
Phone | (863) 734-3000 | ||||||||||
ROSEBARFIELD@JFMINC.BIZ | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1500 | Emerg Generator Diesel (G) | 02/01/2008 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system (N) Approved synthetic material |
(2) Visual inspect pipe sumps (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/04/2015 | 02/04/2017 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 02/04/2013 | 02/04/2015 | AMERICAN SAFETY INDEMNITY CO | ||||||||
INSURANCE | 02/04/2013 | 02/04/2015 | AMERICAN SAFETY INDEMNITY CO | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/31/2020 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Site Inspection | 03/31/2020 | Major Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 03/31/2020 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Phone Conversation | 03/30/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Phone Conversation | 03/30/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 03/30/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 03/30/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 03/30/2020 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 12/01/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Letter | 12/01/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 12/01/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Phone Conversation | 10/27/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/27/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/20/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/12/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Letter | 10/05/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 10/05/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Site Inspection | 10/05/2017 | Major Out of Compliance | WILLIAMSON_KE_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 09/13/2017 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||||||
Enforcement Tracking | 07/28/2017 | Closed With Enforcement | PEDIGO_L | Enforcement | |||||||
Site Inspection | 08/12/2015 | In Compliance | WILLIAMSON_KE_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 07/22/2015 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||||||
Issue Document | 08/28/2013 | Satisfied | WINN_JP_1 | Routine Compliance | |||||||
Site Inspection | 08/28/2013 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Record Document | 08/09/2013 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 05/01/2013 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Site Inspection | 03/18/2013 | In Compliance | DERY_WC_1 | 1/0 | Non-Compliance | ||||||
Letter | 08/01/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 08/01/2012 | Major Out of Compliance | DERY_WC_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 08/01/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Meeting | 08/01/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 06/28/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 06/15/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Issue Document | 04/13/2012 | Satisfied | PEDIGO_L | Enforcement | |||||||
Site Inspection | 11/04/2011 | Major Out of Compliance | DERY_WC_1 | 1/0 | Non-Compliance | ||||||
Letter | 10/28/2011 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Site Inspection | 10/28/2011 | Major Out of Compliance | SLAPPEY_WR_1 | 1/0 | Routine Compliance | ||||||
Record Document | 04/08/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 04/08/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Enforcement Referral | 04/04/2011 | Accepted | PEDIGO_L | Enforcement | |||||||
Electronic Communication | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Letter | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Letter | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 03/18/2011 | Major Out of Compliance | DERY_WC_1 | 1/0 | Installation | ||||||
Electronic Communication | 03/18/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/31/2020 | 5145 | Minor | 1.8 Records not kept until closure of system. | The attached Part P form must be completed for the appropriated coverage period and submitted to the Department. | |||||||
03/31/2020 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | The monthly release detection inspection records for November 2017 to the present must be provided to the Department. | |||||||
03/31/2020 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Test must be performed immediately with the test results submitted to the Department. | |||||||
03/31/2020 | 5003 | Minor | 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. | Therefore, complete and return the attached FDEP storage tank registration form to reflect the correct information for the facility. | |||||||
03/31/2020 | 5097 | SNC-B | 3.5 Electronic release detection devices not inspected monthly for shop fabricated storage tank systems. | The monthly release detection inspection records for November 2017 to the present must be provided to the Department. | |||||||
03/31/2020 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Test must be performed immediately with the test results submitted to the Department. | |||||||
No Discharges Found |