Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Local Government | ||||||||
County | Hardee | Status | OPEN | ||||||||
ID | 9812668 | Latitude | 27° 29' 26.8029 | ||||||||
Name |
ZOLFO SPRINGS WWTF 1120 SR 66 E |
Longitude | 81° 46' 55.6658 | ||||||||
ZOLFO SPRINGS, FL 33890 | LL Method | DPHO | |||||||||
Contact | LINDA ROBERSON | LL Status | REVIEWED | ||||||||
Phone | (863) 735-0405 | Status Date | 01/27/2023 | ||||||||
Account Owner Information | |||||||||||
Name | TOWN OF ZOLFO SPRINGS PO BOX 162 ZOLFO SPRINGS, FL 33890-162 |
Effective Date | 01/09/2023 | ||||||||
Contact | LINDA ROBERSON | ||||||||||
Phone | (863) 735-0405 | ||||||||||
TOWNMANAGER@TOWNOFZOLFO.COM | |||||||||||
Placard # / Date | 680695 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | TOWN OF ZOLFO SPRINGS PO BOX 162 ZOLFO SPRINGS, FL 33890-162 |
Effective Date | 01/09/2023 | ||||||||
Contact | LINDA ROBERSON | ||||||||||
Phone | (863) 735-0405 | ||||||||||
TOWNMANAGER@TOWNOFZOLFO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
WWTP1 | 850 | Emerg Generator Diesel (G) | 12/01/2009 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 06/20/2022 | 06/20/2023 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 06/06/2022 | 06/20/2023 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 06/20/2021 | 06/20/2022 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 06/06/2021 | 06/20/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 06/20/2020 | 06/20/2021 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 06/06/2020 | 06/06/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 06/20/2019 | 06/20/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 06/20/2018 | 06/20/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 06/20/2017 | 06/20/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/20/2016 | 06/20/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/20/2014 | 06/20/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/20/2012 | 06/20/2013 | CHARTIS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 06/20/2011 | 06/20/2012 | COMMERCE & INDUSTRY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 01/27/2023 | Satisfied | HYPPOLITE_LX_1 | Compliance Assistance | |||||||
Letter | 01/27/2023 | Satisfied | HYPPOLITE_LX_1 | Compliance Assistance | |||||||
Site Inspection | 01/27/2023 | Major Out of Compliance | HYPPOLITE_LX_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 09/03/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/30/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/30/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/30/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/30/2021 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Site Inspection | 11/21/2019 | Major Out of Compliance | CASSELS_CR_2 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 11/21/2019 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 11/21/2019 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Letter | 11/21/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 11/21/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/23/2017 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Site Inspection | 08/17/2017 | In Compliance | CASSELS_CR_2 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 07/20/2017 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 05/05/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Electronic Communication | 04/28/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Letter | 04/28/2015 | Satisfied | JARRETT_SE_1 | Non-Compliance | |||||||
Site Inspection | 04/28/2015 | Minor Out of Compliance | JARRETT_SE_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 07/24/2012 | In Compliance | DERY_WC_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 08/16/2011 | Closed Without Enforcement | MEETZE_A | Enforcement | |||||||
Record Document | 08/15/2011 | Satisfied | MEETZE_A | Enforcement | |||||||
Enforcement Referral | 08/01/2011 | Accepted | MEETZE_A | Enforcement | |||||||
Electronic Communication | 07/25/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 07/25/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 07/25/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 07/25/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 07/25/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 07/05/2011 | In Compliance | DERY_WC_1 | 1/0 | Non-Compliance | ||||||
Electronic Communication | 06/23/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Letter | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 06/13/2011 | Major Out of Compliance | DERY_WC_1 | 1/0 | Installation | ||||||
Electronic Communication | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Electronic Communication | 06/13/2011 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 05/25/2011 | Satisfied | DERY_WC_1 | Installation | |||||||
Phone Conversation | 05/12/2011 | Satisfied | DERY_WC_1 | Installation | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/27/2023 | 7075 | SNC-B | 3.1 Not repaired component or piping which has not caused a discharge or release. | Please properly link the electronic release detection system (rupture basin and alarms) to the generator control of the annunciator panel alarm and send a copy of the test report to the Department. | |||||||
12/13/2022 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Please immediately test facility Rochester fuel level gauge for proper operation and submit a copy of the test results to the Department. | |||||||
12/13/2022 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Please perform and send the next two-month visual inspection monitoring records to the Department. | |||||||
11/20/2019 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Have the electronic release detection system (rupture basin sensor and alarm panel) tested immediately and submit a copy of the test results to the Department. | |||||||
No Discharges Found |