Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Federal Government
 
County Manatee   Status    OPEN
 
ID 9813006   Latitude    27° 28' 5.88
 
Name HOMELAND SECURITY - ICE
3614 3RD ST W
Longitude    82° 33' 55.8
  BRADENTON, FL 34205 LL Method    DPHO
 
Contact JEFFREY O'CONNOR   LL Status    REVIEWED
 
Phone (813) 781-4204   Status Date    06/25/2012
 
Account Owner Information
 
Name DAHL BROS BRADENTON ICE LLC
500 N WESTSHORE BLVD #750
TAMPA, FL 33609
Effective Date    01/12/2012
 
Contact BRYAN ZINOBER
 
Phone (813) 658-3354
 
Email BRYAN.ZINOBER@FRANKLINSTREETFINANCIAL.COM
  Placard # / Date   
Property Owner Information
 
Name DAHL BROS BRADENTON ICE LLC
500 N WESTSHORE BLVD #750
TAMPA, FL 33609
Effective Date    01/12/2012
 
Contact BRYAN ZINOBER
 
Phone (813) 658-3354
 
Email BRYAN.ZINOBER@FRANKLINSTREETFINANCIAL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 3000 Emerg Generator Diesel (G) 11/01/2011 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(N) Flow shut-Off
(P) Level gauges/alarms
(T) Small use tank
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
(R) Monitor tank bottom space
(U) Annual piping pressure test
(Z) DEP approved monitoring
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY   01/01/2030
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY   01/01/2015 01/01/2030
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 08/19/2022 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Issue Document 08/19/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Phone Conversation 08/19/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 08/19/2022 Major Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Letter 08/31/2020 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 06/11/2020 Accepted TRETHEWEY_MB_1 Enforcement
 
Electronic Communication 06/03/2020 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Electronic Communication 06/03/2020 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Issue Document 09/27/2019 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Letter 09/27/2019 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 09/27/2019 Major Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Enforcement Tracking 03/13/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Electronic Communication 03/13/2018 Satisfied BROWNLEE_S Enforcement
 
Issue Document 03/12/2018 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Record Document 03/12/2018 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Record Document 01/25/2018 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Record Document 01/24/2018 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Electronic Communication 12/20/2017 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 12/20/2017 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 12/06/2017 Satisfied BROWNLEE_S Enforcement
 
Phone Conversation 12/06/2017 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 12/04/2017 Accepted TRETHEWEY_MB_1 Enforcement
 
Electronic Communication 11/30/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Electronic Communication 11/30/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Phone Conversation 11/30/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Letter 08/14/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 08/14/2017 Major Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Issue Document 08/14/2017 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Letter 10/16/2015 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 10/16/2015 Minor Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Record Document 11/04/2014 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 08/28/2014 Minor Out of Compliance TRETHEWEY_MB_1 1/0 Non-Compliance
 
Letter 08/28/2014 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Record Document 08/14/2014 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Letter 04/09/2014 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 04/09/2014 Major Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Site Inspection 01/20/2012 In Compliance TRETHEWEY_MB_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
08/19/2022 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Immediately have the required tests performed and provide Manatee County NRD with copies of the results.
 
08/19/2022 7090 Minor 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. Remove and properly dispose of water.
 
08/19/2022 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Immediately begin documenting visual inspections along with electronic tapes. Provide Manatee County NRD with copies of the next two months for review.
 
08/19/2022 7066 SNC-B 3.5 Electronic and mechanical release detection not installed, calibrated, operated and maintained per manufacturer's specifications. Immediately have the required tests performed and provide Manatee County NRD with copies of the results.
 
09/27/2019 5095 Minor 3.3 Release detection for shop fabricated storage tank systems not installed, operated, and maintained per manufacturer's instructions and standards. Immediately have the required tests performed and provide Manatee County PNRD with copies of the test results.
 
09/27/2019 5126 Minor 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. Immediately remove and properly dispose of all water.
 
09/27/2019 5094 SNC-B 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. Immediately begin documenting visual inspections along with electronic history. Provide Manatee County PNRD with next three months release detection records.
 
 
 
No Discharges Found