DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District South   Type    Fuel user/Non-retail
 
County Desoto   Status    OPEN
 
ID 9813394   Latitude    27° 9' 49.32
 
Name BLACK WOLF INDUSTRIES INC
4135 SW HWY 17
Longitude    81° 52' 53.04
  ARCADIA, FL 34266 LL Method    DPHO
 
Contact STEVE GAME   LL Status    REVIEWED
 
Phone (863) 444-2906   Status Date    10/23/2012
 
Account Owner Information
 
Name BLACK WOLF INDUSTRIES INC
5443 NE CUBITIS AVE
ARCADIA, FL 34266
Effective Date    05/08/2018
 
Contact STEVE GAME
 
Phone (863) 444-3835
 
Email LOADINGZONE69@YAHOO.COM
  Placard # / Date   
Property Owner Information
 
Name BLACK WOLF INDUSTRIES INC
5443 NE CUBITIS AVE
ARCADIA, FL 34266
Effective Date    05/08/2018
 
Contact STEVE GAME
 
Phone (863) 444-3835
 
Email LOADINGZONE69@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 14000 Unleaded Gas (B) 09/01/2012 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Vehicular Diesel (D) 09/01/2012 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
3 1000 Unleaded Gas (B) 09/01/2012 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   08/06/2015 08/06/2016 ACE
INSURANCE   03/19/2014 03/19/2015 COMMERCE & INDUSTRY
INSURANCE   03/18/2014 03/18/2015 COMMERCE & INDUSTRY
INSURANCE   03/18/2014 03/18/2015
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/14/2024 Accepted PARKS_J_4 Enforcement
 
Letter 05/04/2022 Satisfied PARKS_J_4 Non-Compliance
 
Electronic Communication 04/08/2022 Satisfied PARKS_J_4 Routine Compliance
 
Phone Conversation 04/08/2022 Satisfied PARKS_J_4 Routine Compliance
 
Site Inspection 04/08/2022 Major Out of Compliance PARKS_J_4 3/0 Routine Compliance
 
Letter 03/16/2021 Satisfied KLEINMANN_K_1 Compliance Assistance
 
Site Inspection 12/23/2020 Major Out of Compliance KLEINMANN_K_1 3/0 Routine Compliance
 
Phone Conversation 12/22/2020 Satisfied KLEINMANN_K_1 Routine Compliance
 
Site Inspection 05/11/2018 Major Out of Compliance ZIMMERMAN_CA_1 3/0 Routine Compliance
 
Letter 05/11/2018 Satisfied ZIMMERMAN_CA_1 Compliance Assistance
 
Record Document 09/01/2015 Satisfied ZIMMERMAN_CA_1 Non-Compliance
 
Letter 07/31/2015 Satisfied ZIMMERMAN_CA_1 Non-Compliance
 
Site Inspection 07/31/2015 Major Out of Compliance ZIMMERMAN_CA_1 3/0 Non-Compliance
 
Letter 02/13/2015 Satisfied JOHNSON_SG_1 Non-Compliance
 
Site Inspection 02/13/2015 Minor Out of Compliance JOHNSON_SG_1 3/0 Routine Compliance
 
Site Inspection 03/31/2014 In Compliance JOHNSON_SG_1 3/0 Non-Compliance
 
Site Inspection 01/03/2014 Major Out of Compliance JOHNSON_SG_1 3/0 Routine Compliance
 
Letter 01/03/2014 Satisfied JOHNSON_SG_1 Non-Compliance
 
Site Inspection 08/06/2013 Major Out of Compliance STANDIFORD_J 3/0 Installation
 
Electronic Communication 05/29/2013 Satisfied STANDIFORD_J Installation
 
Site Inspection 04/22/2013 Major Out of Compliance STANDIFORD_J 3/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/08/2022 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. Provide a current and valid "Certificate of Financial Responsibility" for review.
 
04/08/2022 7095 Minor 1.14 Records requiring 3 year documentation period not kept by facility. Submit the required records for review.
 
04/08/2022 7063 SNC-A 1.5 Storage tank systems does not have appropriate testing, including breach of integrity, tightness or electronic leak detection. Repair interstitial Monitoring.
 
04/08/2022 7066 SNC-B 3.5 Electronic and mechanical release detection not installed, calibrated, operated and maintained per manufacturer's specifications. Repair Release detection devices.
 
04/08/2022 7040 SNC-B 3.8 Overfill protection not provided. Fuel transfer not monitored. Alarms not installed. Perform Annual Operability testing.
 
04/08/2022 7002 Minor 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Update the registration information.
 
12/23/2020 5004 Minor 1.4 Registration fees not paid, placard not posted. Update status and registration
 
12/23/2020 5003 Minor 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. Register tanks with state of Florida.
 
12/23/2020 5140 Minor 3.30 Spill containment, sumps and interstices not accessible. Water/regulated substance not timely removed for field erected storage tank systems. Petroleum contact water not properly managed. Remove and properly manage system.
 
12/23/2020 5011 SNC-B 1.6 Failure to maintain and demonstrate financial responsibility. Obtain financial responsibility
 
12/23/2020 5125 Minor 3.15 Failure to conduct required periodic containment and interstitial integrity testing for shop fabricated storage tank systems. Update status service status and perform required testing.
 
05/07/2018 5102 Minor 3.3 Shop fabricated storage tank system release detection devices not tested annually. Have all release detection devices tested and submit results to the county inspector.
 
05/07/2018 5126 Minor 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. have water removed
 
05/07/2018 5057 SNC-B 3.5 Pressurized small diameter piping not installed with line leak detectors and meeting requirements. Have leak detectors install and tested.
 
05/07/2018 5011 SNC-B 1.6 Failure to maintain and demonstrate financial responsibility. Obtain current and up to date Financial responsibility.
 
05/07/2018 5004 Minor 1.4 Registration fees not paid, placard not posted. Pay fees
 
05/07/2018 5114 Minor 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. Have alarm repaired or replaced
 
05/07/2018 5126 Minor 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. Have water removed
 
 
 
No Discharges Found