Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Fuel user/Non-retail | ||||||||
County | Desoto | Status | OPEN | ||||||||
ID | 9813394 | Latitude | 27° 9' 49.32 | ||||||||
Name |
BLACK WOLF INDUSTRIES INC 4135 SW HWY 17 |
Longitude | 81° 52' 53.04 | ||||||||
ARCADIA, FL 34266 | LL Method | DPHO | |||||||||
Contact | STEVE GAME | LL Status | REVIEWED | ||||||||
Phone | (863) 444-2906 | Status Date | 10/23/2012 | ||||||||
Account Owner Information | |||||||||||
Name | BLACK WOLF INDUSTRIES INC 5443 NE CUBITIS AVE ARCADIA, FL 34266 |
Effective Date | 05/08/2018 | ||||||||
Contact | STEVE GAME | ||||||||||
Phone | (863) 444-3835 | ||||||||||
LOADINGZONE69@YAHOO.COM | |||||||||||
Placard # / Date | |||||||||||
Property Owner Information | |||||||||||
Name | BLACK WOLF INDUSTRIES INC 5443 NE CUBITIS AVE ARCADIA, FL 34266 |
Effective Date | 05/08/2018 | ||||||||
Contact | STEVE GAME | ||||||||||
Phone | (863) 444-3835 | ||||||||||
LOADINGZONE69@YAHOO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 14000 | Unleaded Gas (B) | 09/01/2012 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (M) Spill containment bucket (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Vehicular Diesel (D) | 09/01/2012 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (M) Spill containment bucket (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 1000 | Unleaded Gas (B) | 09/01/2012 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 08/06/2015 | 08/06/2016 | ACE | ||||||||
INSURANCE | 03/19/2014 | 03/19/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/18/2014 | 03/18/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/18/2014 | 03/18/2015 | |||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 11/14/2024 | Accepted | PARKS_J_4 | Enforcement | |||||||
Letter | 05/04/2022 | Satisfied | PARKS_J_4 | Non-Compliance | |||||||
Electronic Communication | 04/08/2022 | Satisfied | PARKS_J_4 | Routine Compliance | |||||||
Phone Conversation | 04/08/2022 | Satisfied | PARKS_J_4 | Routine Compliance | |||||||
Site Inspection | 04/08/2022 | Major Out of Compliance | PARKS_J_4 | 3/0 | Routine Compliance | ||||||
Letter | 03/16/2021 | Satisfied | KLEINMANN_K_1 | Compliance Assistance | |||||||
Site Inspection | 12/23/2020 | Major Out of Compliance | KLEINMANN_K_1 | 3/0 | Routine Compliance | ||||||
Phone Conversation | 12/22/2020 | Satisfied | KLEINMANN_K_1 | Routine Compliance | |||||||
Site Inspection | 05/11/2018 | Major Out of Compliance | ZIMMERMAN_CA_1 | 3/0 | Routine Compliance | ||||||
Letter | 05/11/2018 | Satisfied | ZIMMERMAN_CA_1 | Compliance Assistance | |||||||
Record Document | 09/01/2015 | Satisfied | ZIMMERMAN_CA_1 | Non-Compliance | |||||||
Letter | 07/31/2015 | Satisfied | ZIMMERMAN_CA_1 | Non-Compliance | |||||||
Site Inspection | 07/31/2015 | Major Out of Compliance | ZIMMERMAN_CA_1 | 3/0 | Non-Compliance | ||||||
Letter | 02/13/2015 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 02/13/2015 | Minor Out of Compliance | JOHNSON_SG_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 03/31/2014 | In Compliance | JOHNSON_SG_1 | 3/0 | Non-Compliance | ||||||
Site Inspection | 01/03/2014 | Major Out of Compliance | JOHNSON_SG_1 | 3/0 | Routine Compliance | ||||||
Letter | 01/03/2014 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 08/06/2013 | Major Out of Compliance | STANDIFORD_J | 3/0 | Installation | ||||||
Electronic Communication | 05/29/2013 | Satisfied | STANDIFORD_J | Installation | |||||||
Site Inspection | 04/22/2013 | Major Out of Compliance | STANDIFORD_J | 3/0 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/08/2022 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide a current and valid "Certificate of Financial Responsibility" for review. | |||||||
04/08/2022 | 7095 | Minor | 1.14 Records requiring 3 year documentation period not kept by facility. | Submit the required records for review. | |||||||
04/08/2022 | 7063 | SNC-A | 1.5 Storage tank systems does not have appropriate testing, including breach of integrity, tightness or electronic leak detection. | Repair interstitial Monitoring. | |||||||
04/08/2022 | 7066 | SNC-B | 3.5 Electronic and mechanical release detection not installed, calibrated, operated and maintained per manufacturer's specifications. | Repair Release detection devices. | |||||||
04/08/2022 | 7040 | SNC-B | 3.8 Overfill protection not provided. Fuel transfer not monitored. Alarms not installed. | Perform Annual Operability testing. | |||||||
04/08/2022 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Update the registration information. | |||||||
12/23/2020 | 5004 | Minor | 1.4 Registration fees not paid, placard not posted. | Update status and registration | |||||||
12/23/2020 | 5003 | Minor | 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. | Register tanks with state of Florida. | |||||||
12/23/2020 | 5140 | Minor | 3.30 Spill containment, sumps and interstices not accessible. Water/regulated substance not timely removed for field erected storage tank systems. Petroleum contact water not properly managed. | Remove and properly manage system. | |||||||
12/23/2020 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Obtain financial responsibility | |||||||
12/23/2020 | 5125 | Minor | 3.15 Failure to conduct required periodic containment and interstitial integrity testing for shop fabricated storage tank systems. | Update status service status and perform required testing. | |||||||
05/07/2018 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Have all release detection devices tested and submit results to the county inspector. | |||||||
05/07/2018 | 5126 | Minor | 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. | have water removed | |||||||
05/07/2018 | 5057 | SNC-B | 3.5 Pressurized small diameter piping not installed with line leak detectors and meeting requirements. | Have leak detectors install and tested. | |||||||
05/07/2018 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Obtain current and up to date Financial responsibility. | |||||||
05/07/2018 | 5004 | Minor | 1.4 Registration fees not paid, placard not posted. | Pay fees | |||||||
05/07/2018 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | Have alarm repaired or replaced | |||||||
05/07/2018 | 5126 | Minor | 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. | Have water removed | |||||||
No Discharges Found |