District Northeast   Type    Retail Station
 
County Clay   Status    OPEN
 
ID 9814267   Latitude    30° 8' 21.2915
 
Name MURPHY USA #7564
909 BLANDING BLVD
Longitude    81° 46' 15.7753
  ORANGE PARK, FL 32065 LL Method    DPHO
 
Contact BRAD WEINISCHKE   LL Status    REVIEWED
 
Phone (870) 875-7610   Status Date    02/06/2024
 
Account Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    07/30/2014
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
  Placard # / Date    680024 - 06/05/2024
Property Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    07/30/2014
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 20000 Unleaded Gas (B) 08/01/2014 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 20000 Vehicular Diesel (D) 08/01/2014 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2023 04/30/2025
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2021 04/30/2023
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2018 04/30/2021
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2016 04/30/2018
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2015 04/30/2016
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2014 04/30/2015
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 03/25/2025 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 03/16/2025 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Record Document 01/02/2025 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 11/25/2024 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 11/25/2024 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 11/25/2024 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 04/23/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 04/23/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 04/23/2023 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Letter 01/31/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 01/31/2021 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 01/31/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 11/06/2020 Satisfied RAMSEY_TH_1 Discharge
 
Discharge Reporting 11/06/2020 Satisfied HARRINGTON_RD_1 Discharge
 
Document Management 11/05/2018 Satisfied HARRINGTON_RD_1 Incident
 
Document Management 11/05/2018 Satisfied HARRINGTON_RD_1 Discharge
 
Incident 11/05/2018 Led to Discharge (Incident promoted) HARRINGTON_RD_1 Incident
 
Letter 10/26/2018 Satisfied LIBBY_KK_1 Compliance Assistance
 
Record Document 10/07/2018 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 09/28/2018 Satisfied GOODMAN_TA_1 Closure
 
Letter 09/28/2018 Satisfied GOODMAN_TA_1 Closure
 
TCAR 09/28/2018 Satisfied GOODMAN_TA_1 Closure
 
Electronic Communication 09/28/2018 Satisfied GOODMAN_TA_1 Closure
 
Electronic Communication 09/28/2018 Satisfied LIBBY_KK_1 Compliance Assistance
 
Discharge Reporting 07/30/2018 Satisfied HARRINGTON_RD_1 Discharge
 
Document Management 07/29/2018 Satisfied HARRINGTON_RD_1 Discharge
 
Electronic Communication 04/29/2018 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 04/29/2018 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 04/22/2018 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 03/14/2016 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Phone Conversation 03/14/2016 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 03/14/2016 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Site Inspection 10/31/2014 In Compliance HARRINGTON_RD_1 0/2 Installation
 
Emergency Preparedness Information 10/31/2014 Satisfied HARRINGTON_RD_1 Installation
 
Electronic Communication 10/31/2014 Satisfied HARRINGTON_RD_1 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/25/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide current Integrity Test results of the double wall spill buckets.
 
11/25/2024 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Provide 6-month visual inspection documentation.
 
11/25/2024 6002 Minor 2.1 Operator Training records not available. Provide verification of C Operator Certificates for the facility.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
07/13/2018   INACTIVE MCKEEHEN_D