DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 01/22/2025        Last Data Refresh: 01/21/2025        Report Generated from DOPPLER
 
District Central   Type    Fuel user/Non-retail
 
County Brevard   Status    OPEN
 
ID 9814520   Latitude    28° 7' 41.1841
 
Name VICTORIA LANDING WATERFRONT RESORT ASSISTED LIVING
1279 HOUSTON ST
Longitude    80° 37' 28.566
  MELBOURNE, FL 32935-7069 LL Method    DPHO
 
Contact NEIL LAROCHELLE   LL Status    REVIEWED
 
Phone (321) 622-6730   Status Date    09/17/2018
 
Account Owner Information
 
Name VICTORIA LANDING LLC
1279 HOUSTON ST
Melbourne, FL 32935
Effective Date    03/31/2015
 
Contact Victoria Landing
 
Phone (321) 622-6730
 
Email APATRICK@VICTORIALANDING.COM
  Placard # / Date    699346 - 07/11/2024
Property Owner Information
 
Name VICTORIA LANDING LLC
1279 HOUSTON ST
Melbourne, FL 32935
Effective Date    06/08/2020
 
Contact Victoria Landing
 
Phone (321) 622-6730
 
Email APATRICK@VICTORIALANDING.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
2 1877 Emerg Generator Diesel (G) 05/27/2020 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(P) Level gauges/alarms
  (A) Abv, no soil contact
(X) No piping associated w/tank
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
W0419 967 Vehicular Diesel (D) 08/21/2024 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (D) External protective coating
(Y) Unknown
(Q) Visual inspection of ASTs
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Emerg Generator Diesel (G) 06/01/2013 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(Z) DEP approved tank material   (D) External protective coating
(Y) Unknown
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   04/28/2024 04/28/2025 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   04/28/2020 04/28/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   04/28/2018 04/28/2019 COMMERCE & INDUSTRY
INSURANCE   04/28/2018 04/28/2018 COMMERCE & INDUSTRY
INSURANCE   04/28/2015 04/28/2016 COMMERCE & INDUSTRY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 10/08/2024 Satisfied GRANTHAM_JW_1 Compliance Assistance
 
Site Inspection 10/08/2024 Major Out of Compliance GRANTHAM_JW_1 2/0 Routine Compliance
 
Letter 08/23/2022 Satisfied GRANTHAM_JW_1 Compliance Assistance
 
Record Document 08/23/2022 Satisfied GRANTHAM_JW_1 Routine Compliance
 
Letter 03/22/2021 Satisfied GRANTHAM_JW_1 Compliance Assistance
 
Site Inspection 03/15/2021 Minor Out of Compliance GRANTHAM_JW_1 2/0 Routine Compliance
 
Electronic Communication 05/23/2018 Satisfied WEST_KE_1 Compliance Assistance
 
Letter 05/15/2018 Satisfied WEST_KE_1 Compliance Assistance
 
Site Inspection 05/15/2018 Major Out of Compliance WEST_KE_1 1/0 Routine Compliance
 
Site Inspection 07/17/2015 In Compliance WEST_KE_1 1/0 Routine Compliance
 
Emergency Preparedness Information 07/16/2015 Satisfied WEST_KE_1 Routine Compliance
 
Site Inspection 04/28/2015 In Compliance ULRICH_CA_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/08/2024 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Test the 1,877 gallon tank release detection device. Send updated testing to this office.
 
10/08/2024 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Begin inspecting your tanks. Send this office documentation of tank inspections for 2024.
 
10/08/2024 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Send updated overfill prevention testing to this office for the 1,877 gallon tank.
 
 
 
No Discharges Found