DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Manatee   Status    OPEN
 
ID 9815093   Latitude    27° 29' 55.7376
 
Name ASPIRE AT BRADENTON
105 15TH ST E
Longitude    82° 32' 52.188
  BRADENTON, FL 34208-1337 LL Method    DPHO
 
Contact NOREST MADZVIMBO   LL Status    REVIEWED
 
Phone (941) 747-8681   Status Date    06/08/2016
 
Account Owner Information
 
Name 105 15TH ST E FL OWNER LLC
338 WHITESVILLE RD
JACKSON, FL 8527
Effective Date    09/15/2023
 
Contact TZVI MAGID
 
Phone (732) 719-5750
 
Email TMAGID@ASPIREHEALTHGRP.COM
  Placard # / Date    703667 - 11/25/2024
Property Owner Information
 
Name 105 15TH ST E FL OWNER LLC
338 WHITESVILLE RD
JACKSON, FL 8527
Effective Date    09/15/2023
 
Contact TZVI MAGID
 
Phone (732) 719-5750
 
Email TMAGID@ASPIREHEALTHGRP.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
50994 2400 Emerg Generator Diesel (G) 01/01/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
 
 
 
Tank Tank Size Content Installed Placement Status
BAYVUE 1000 Emerg Generator Diesel (G) 06/15/2015 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
 
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-NOT REQUIRED  
NONE   06/14/2024 06/14/2024
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 09/24/2024 Accepted SHANBERG_VJ_1 Enforcement
 
Electronic Communication 09/19/2024 Satisfied SHANBERG_VJ_1 Compliance Assistance
 
Phone Conversation 09/19/2024 Satisfied SHANBERG_VJ_1 Compliance Assistance
 
Electronic Communication 09/19/2024 Satisfied SHANBERG_VJ_1 Compliance Assistance
 
Electronic Communication 09/19/2024 Satisfied SHANBERG_VJ_1 Compliance Assistance
 
Letter 06/19/2024 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 06/19/2024 Major Out of Compliance TRETHEWEY_MB_1 2/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
06/19/2024 7005 Minor 1.5 Notification of installation, closure, or change in service status not received in required timeframes. Ensure that Manatee County NRD is notified prior to any removal or installation activity. Notification is required in writing or electronic format between 30 and 45 days before the initiation of the work related to the change in service status or closure and between 48 and 72 hours prior to the initiation of the work.
 
06/19/2024 7094 Minor 1.13 Permanent records not available within 5 working days notice. Provide Manatee County NRD with copies of the required records. Ensure that release detection is documented at least once a month not exceeding 35 days apart.
 
06/19/2024 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. Remove any corrosion and repaint affected areas.
 
06/19/2024 7042 SNC-B 3.9 Storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. Install an approved spill bucket at the fill, ensure fill is properly labeled.
 
06/19/2024 7002 Minor 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Submit corrected registration form with updated contact, facility, and tank information.
 
06/19/2024 7009 SNC-B 1.7 No financial responsibility instrument or expired instrument for < 180 days. Provide Manatee County NRD with copies of Financial Responsibility listing the coverage, tanks and address.
 
06/19/2024 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Designate overfill protection (manual or electronic). Provide test if electrical.
 
06/19/2024 7072 Minor 1.8 Annual operability testing of release detection systems not completed. If vacuum monitoring is used, gauge must be tested annually and vacuum replenished. If gauge is removed, monitoring can be manual.
 
 
 
No Discharges Found