DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Northeast   Type    Fuel user/Non-retail
 
County Duval   Status    OPEN
 
ID 9815327   Latitude    30° 16' 3.954
 
Name TOUCHTON SURGERY CTR
9726 TOUCHTON RD
Longitude    81° 33' 19.0584
  JACKSONVILLE, FL 32246 LL Method    DPHO
 
Contact ANDRE BAHRI   LL Status    REVIEWED
 
Phone (904) 686-6020   Status Date    11/30/2016
 
Account Owner Information
 
Name OUTPATIENT SERVICE PROVIDERS LLC
9726 TOUCHTON RD #305
JACKSONVILLE, FL 32246
Effective Date    11/29/2016
 
Contact ANDRE BAHRI
 
Phone (904) 349-8679
 
Email ANDREBAHRI@GMAIL.COM
  Placard # / Date    686591 - 06/11/2024
Property Owner Information
 
Name TINSELTOWN PARTNERS LLP
6100 KENNERLY RD #100
JACKSONVILLE, FL 32216
Effective Date    07/24/2018
 
Contact LORI BAHRI
 
Phone (904) 868-3602
 
Email LORIBAHRI@COMCAST.NET
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4P74 1000 Emerg Generator Diesel (G) 10/01/2016 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (X) No piping associated w/tank (F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
NONE  
INSURANCE   08/16/2024 08/16/2025 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   08/16/2022 08/16/2023 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   08/16/2020 08/16/2021 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   08/16/2019 08/16/2020 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   08/16/2018 08/16/2019 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   08/16/2017 08/16/2018 CRUM & FORSTER SPECIALTY INS. CO.
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 04/02/2025 Major Out of Compliance WESTERMAN_ML_1 1/0 Routine Compliance
 
Letter 04/02/2025 Satisfied WESTERMAN_ML_1 Compliance Assistance
 
Electronic Communication 03/18/2025 Satisfied WESTERMAN_ML_1 Compliance Assistance
 
Letter 07/10/2023 Satisfied MCKINLEY_D Enforcement
 
Enforcement Tracking 07/10/2023 Closed Without Enforcement MCKINLEY_D Enforcement
 
Phone Conversation 02/08/2023 Satisfied MCKINLEY_D Enforcement
 
Phone Conversation 01/26/2023 Satisfied MCKINLEY_D Enforcement
 
Electronic Communication 12/20/2022 Satisfied MCKINLEY_D Enforcement
 
Letter 08/17/2022 Satisfied MCKINLEY_D Enforcement
 
Enforcement Referral 05/23/2022 Accepted GAINEY_H_1 Enforcement
 
Letter 03/15/2022 Satisfied GREGORY_HM_1 Compliance Assistance
 
Site Inspection 03/15/2022 Major Out of Compliance GREGORY_HM_1 1/0 Complaint
 
Letter 03/29/2021 Satisfied BRANCH_BL_1 Compliance Assistance
 
Site Inspection 03/26/2021 In Compliance BRANCH_BL_1 1/0 Routine Compliance
 
Electronic Communication 03/08/2021 Satisfied BRANCH_BL_1 Compliance Assistance
 
Enforcement Tracking 06/25/2019 Closed With Enforcement OBRIEN_S Enforcement
 
Letter 06/25/2019 Satisfied OBRIEN_S Enforcement
 
Document Management 06/17/2019 Satisfied OBRIEN_S Enforcement
 
Letter 03/20/2019 Satisfied OBRIEN_S Enforcement
 
Letter 01/30/2018 Satisfied OBRIEN_S Enforcement
 
Letter 01/30/2018 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 11/06/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 08/18/2017 Satisfied DOHANEY_T Enforcement
 
Electronic Communication 08/18/2017 Satisfied DOHANEY_T Enforcement
 
Phone Conversation 06/28/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 06/28/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 06/28/2017 Satisfied OBRIEN_S Enforcement
 
Enforcement Referral 05/15/2017 Accepted RICHARDS_JE_1 Enforcement
 
Letter 05/04/2017 Satisfied RICHARDS_JE_1 Non-Compliance
 
Letter 03/01/2017 Satisfied RICHARDS_JE_1 Non-Compliance
 
Letter 01/23/2017 Satisfied LUNN_RJ_1 Non-Compliance
 
Electronic Communication 01/17/2017 Satisfied LUNN_RJ_1 Installation
 
Site Inspection 01/13/2017 Major Out of Compliance LUNN_RJ_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/02/2025 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. The facility must provide EQD with current documentation for three consecutive months of monthly inspections.
 
04/02/2025 7095 Minor 1.14 Records requiring 3 year documentation period not kept by facility. Facilities are required to maintain a minimum of three years of records for financial responsibility, monthly inspections, and annual operability testing of the overfill protection and leak detection devices.
 
04/02/2025 7011 Minor 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. The facility must provide EQD with either Part C or Part D from the insurance carrier and Part P.
 
04/02/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. The facility must provide EQD with documentation for annual operability testing of the Leak Detection Device.
 
04/02/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, The facility must provide EQD with documentation for Annual Operability Testing of the Overfill Protection Device.
 
 
 
No Discharges Found