Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Fuel user/Non-retail | ||||||||
County | Leon | Status | OPEN | ||||||||
ID | 9815451 | Latitude | 30° 24' 33.5979 | ||||||||
Name |
TALLAHASSEE VA LLC 2181 ORANGE AVE E |
Longitude | 84° 14' 54.7994 | ||||||||
TALLAHASSEE, FL 32311 | LL Method | DPHO | |||||||||
Contact | RYAN OSGOOD | LL Status | REVIEWED | ||||||||
Phone | (850) 661-1471 | Status Date | 12/20/2023 | ||||||||
Account Owner Information | |||||||||||
Name | TALLAHASSEE VA LLC 4706 BROADWAY ,SU#240 KANSAS CITY, MO 64112 |
Effective Date | 02/08/2017 | ||||||||
Contact | HEATHER JORDAN / KRISTI STUEDLE | ||||||||||
Phone | (816) 490-0119 | ||||||||||
HJORDAN@USAS-LLC.COM | |||||||||||
Placard # / Date | 693462 - 06/21/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | TALLAHASSEE VA LLC 4706 BROADWAY ,SU#240 KANSAS CITY, MO 64112 |
Effective Date | 02/08/2017 | ||||||||
Contact | HEATHER JORDAN / KRISTI STUEDLE | ||||||||||
Phone | (816) 490-0119 | ||||||||||
HJORDAN@USAS-LLC.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
22364 | 20000 | Emerg Generator Diesel (G) | 06/01/2016 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(Z) DEP approved tank material | (B) Steel/galvanized metal | (L) Automatic tank gauging - USTs | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 05/16/2023 | 05/16/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 05/16/2022 | 05/16/2023 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 05/16/2019 | 05/16/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 05/15/2017 | 05/16/2018 | ACE | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 08/02/2024 | Satisfied | MERRITT_S | Enforcement | |||||||
Electronic Communication | 07/30/2024 | Satisfied | BONDS_M | Enforcement | |||||||
Document Management | 06/04/2024 | Satisfied | BONDS_M | Incident | |||||||
Record Document | 05/29/2024 | Satisfied | BONDS_M | Enforcement | |||||||
Enforcement Referral | 03/20/2024 | Accepted | HATCHER_JD_1 | Enforcement | |||||||
Site Inspection | 10/16/2023 | Major Out of Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
Letter | 10/16/2023 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 05/23/2022 | In Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 02/27/2020 | In Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 08/14/2019 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Letter | 06/11/2019 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 06/11/2019 | Major Out of Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 11/13/2017 | In Compliance | HATCHER_JD_1 | 0/1 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/29/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Repair and provide passing test results for transitional sumps 1, 2, and 3. | |||||||
05/29/2024 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | Complete an investigation to confirm if a discharge happened from the transitional sump components. Provide written documentation of investigation results. | |||||||
10/16/2023 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Perform required annual testing and provide results | |||||||
10/16/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Perform and provide required annual testing. | |||||||
No Discharges Found |