Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9816397 | Latitude | 27° 52' 5.3919 | ||||||||
Name |
AVENTURA PLACE 10401 ROOSEVELT BLVD N |
Longitude | 82° 38' 29.909 | ||||||||
SAINT PETERSBURG, FL 33716 | LL Method | DPHO | |||||||||
Contact | BONNIE ALMOND | LL Status | REVIEWED | ||||||||
Phone | (727) 568-1000 | Status Date | 05/26/2020 | ||||||||
Account Owner Information | |||||||||||
Name | AVENTURA HEALTH GROUP 10401 ROOSEVELT BLVD N SAINT PETERSBURG, FL 77140 |
Effective Date | 12/09/2022 | ||||||||
Contact | BONNIE ALMOND / STEVE MACKENZIE 727-631-6340 | ||||||||||
Phone | (727) 568-1000 | ||||||||||
SMACKENZIE@AVENTURAHG.COM | |||||||||||
Placard # / Date | 701540 - 09/29/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | AVENTURA HEALTH GROUP 10401 ROOSEVELT BLVD N SAINT PETERSBURG, FL 77140 |
Effective Date | 12/09/2022 | ||||||||
Contact | BONNIE ALMOND / STEVE MACKENZIE 727-631-6340 | ||||||||||
Phone | (727) 568-1000 | ||||||||||
SMACKENZIE@AVENTURAHG.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
17-013 | 2666 | Emerg Generator Diesel (G) | 12/01/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system (Z) DEP approved piping |
(6) External piping monitoring (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 01/31/2021 | 01/31/2022 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 01/31/2020 | 01/31/2021 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 01/31/2019 | 01/31/2020 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 02/26/2025 | Major Out of Compliance | PUHR_NM_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 02/25/2025 | Satisfied | PUHR_NM_1 | Routine Compliance | |||||||
Letter | 05/17/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 05/17/2021 | Major Out of Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 04/01/2021 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 05/15/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Record Document | 05/15/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 02/12/2019 | Major Out of Compliance | COLSON_NJ_1 | 1/0 | Installation | ||||||
Letter | 02/12/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/25/2025 | 7091 | Minor | 3.15 Exterior Coatings not maintained to prevent corrosion. | *Need to treat the corrosion to prevent further degradation. Submit documentation to this office once completed. | |||||||
02/25/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | *Submit records from 03/29/2021 to current. If none are available, submit the next two consecutive months of tank system visual inspections including alarm history. | |||||||
02/25/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | *Submit missing records from 2022-current. If no test records are available, have testing completed and submit results to this office. | |||||||
02/25/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | *Submit missing records from 2022-current. If no test records are available, have testing completed and submit results to this office. | |||||||
02/25/2025 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | *Submit Financial Responsibility Part D or Part C (from policy) and a Part P (completed by facility). | |||||||
No Discharges Found |