DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northeast   Type    Agricultural
 
County Alachua   Status    OPEN
 
ID 9816595   Latitude    29° 50' 7.2425
 
Name AYR WELLNESS/ AYR CANNABIS DISPENSARY
18770 N CR 225
Longitude    82° 16' 12.9974
  GAINESVILLE, FL 32609 LL Method    DPHO
 
Contact BRENT GADBOIS   LL Status    REVIEWED
 
Phone (508) 989-6692   Status Date    11/05/2018
 
Account Owner Information
 
Name DFMMJ INVESTMENTS
18770 N CR 225
GAINESVILLE, FL 32609
Effective Date    02/28/2023
 
Contact WENDY RICHTER
 
Phone (386) 462-0141
 
Email WENDY.RICHTER@AYRWELLNESS.COM
  Placard # / Date    705438 - 03/28/2025
Property Owner Information
 
Name DFMMJ INVESTMENTS
18770 N CR 225
GAINESVILLE, FL 32609
Effective Date    02/28/2023
 
Contact WENDY RICHTER
 
Phone (386) 462-0141
 
Email WENDY.RICHTER@AYRWELLNESS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 3690 Emerg Generator Diesel (G) 09/01/2018 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (F) Double wall
(L) Bulk product system
(X) No piping associated w/tank
 
 
Tank Tank Size Content Installed Placement Status
7 2388 Vehicular Diesel (D) 06/01/2023 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
WG1 2310 Vehicular Diesel (D) 03/01/2025 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
WG2 2310 Vehicular Diesel (D) 03/01/2025 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 2388 Vehicular Diesel (D) 04/01/2022 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
3 2388 Vehicular Diesel (D) 04/01/2022 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
5 2388 Vehicular Diesel (D) 06/01/2023 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
6 2388 Vehicular Diesel (D) 06/01/2023 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(M) Double wall - pipe jacket
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   02/01/2024 02/01/2025 ACE AMERICAN INSURANCE COMPANY
INSURANCE   11/01/2019 11/01/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   11/01/2018 11/01/2019 ACE
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
TCAR 03/30/2025 Satisfied HARRINGTON_RD_1 Closure
 
Document Management 03/30/2025 Satisfied HARRINGTON_RD_1 Closure
 
Phone Conversation 03/06/2025 Satisfied HARRINGTON_RD_1 Closure
 
Document Management 07/01/2024 Satisfied HARRINGTON_RD_1 Discharge
 
Discharge Reporting 07/01/2024 Satisfied HARRINGTON_RD_1 Discharge
 
Site Inspection 06/16/2024 Minor Out of Compliance HARRINGTON_RD_1 6/0 Complaint
 
Incident 05/31/2024 Has not led to Discharge RAMSEY_TH_1 Incident
 
Document Management 05/31/2024 Satisfied RAMSEY_TH_1 Incident
 
Document Management 03/29/2024 Satisfied HARRINGTON_RD_1 Discharge
 
Enforcement Referral 03/27/2024 Accepted HARRINGTON_RD_1 Enforcement
 
Enforcement Tracking 03/27/2024 Closed Without Enforcement JACKSON_SM Enforcement
 
Electronic Communication 03/26/2024 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 03/26/2024 Major Out of Compliance HARRINGTON_RD_1 6/0 Routine Compliance
 
Electronic Communication 03/17/2024 Satisfied HARRINGTON_RD_1 Discharge
 
Site Inspection 03/14/2024 Minor Out of Compliance HARRINGTON_RD_1 3/0 Discharge
 
Enforcement Tracking 02/23/2024 Closed Without Enforcement JACKSON_SM Enforcement
 
Enforcement Referral 02/21/2024 Accepted HARRINGTON_RD_1 Enforcement
 
Enforcement Referral 02/21/2024 Accepted HARRINGTON_RD_1 Enforcement
 
Meeting 08/15/2023 Satisfied RAMSEY_TH_1 Discharge
 
Discharge Reporting 08/15/2023 Satisfied HARRINGTON_RD_1 Discharge
 
Electronic Communication 05/25/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Record Document 05/23/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 05/23/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 05/23/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 05/23/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 03/24/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 03/12/2023 Major Out of Compliance HARRINGTON_RD_1 3/0 Installation
 
Electronic Communication 03/12/2023 Satisfied HARRINGTON_RD_1 Installation
 
Record Document 02/26/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Document Management 02/19/2023 Satisfied HARRINGTON_RD_1 Discharge
 
Site Inspection 02/19/2023 Major Out of Compliance HARRINGTON_RD_1 1/0 Complaint
 
Site Inspection 09/15/2020 Major Out of Compliance ZIMMERMAN_RA_2 1/0 Routine Compliance
 
Electronic Communication 09/15/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 09/15/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 09/02/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 11/04/2018 In Compliance HARRINGTON_RD_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
06/16/2024 7020 Minor 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. Provide containment box (spill containment box) integrity test results for Tanks 5,6 and 7.
 
06/16/2024 6062 Minor 2.5 Release detection devices not tested annually. Provide current interstice sensor and overfill test results for Tank 1 (genset).
 
03/26/2024 6039 Minor 4.10 Small diameter piping with gravity head not properly installed or meeting standards. Install anti-siphon valve as required. Check that all of the Western Global tanks have the appropriate anti siphon valves installed. Provide verification.
 
03/22/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Provide current overfill prevention device function tests for the regulated tanks. Please clarify test procedure for the Western Global tank overfill devices.
 
 
 
No Discharges Found