Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Other Regulated Facility | ||||||||
County | Manatee | Status | OPEN | ||||||||
ID | 9816663 | Latitude | 27° 29' 40.2684 | ||||||||
Name |
BRADENTON OAKS 1015 7TH AVE E |
Longitude | 82° 33' 9.7488 | ||||||||
BRADENTON, FL 34208-2103 | LL Method | DPHO | |||||||||
Contact | LL Status | REVIEWED | |||||||||
Phone | Status Date | 11/29/2018 | |||||||||
Account Owner Information | |||||||||||
Name | GAHC4 BRADENTON OAKS FL SH LLC 6931 ARLINGTON RD #320 BETHERDA, MD 20814 |
Effective Date | 11/26/2018 | ||||||||
Contact | ANTHONY MILES / TAMMIE ALLISON (828) 851-3118 | ||||||||||
Phone | (407) 451-3544 | ||||||||||
TMILES@MEDPROCM.COM | |||||||||||
Placard # / Date | 671418 - 11/01/2023 | ||||||||||
Property Owner Information | |||||||||||
Name | GAHC4 BRADENTON OAKS FL SH, LLC 5049 N HIGHWAY A1A HUTCHINSON ISLAND, FL 34949-8289 |
Effective Date | 11/26/2018 | ||||||||
Contact | ANTHONY | ||||||||||
Phone | (407) 451-3544 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
GEN1 | 1090 | Emerg Generator Diesel (G) | 11/16/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (D) External protective coating (F) Double wall (I) Suction piping system |
(E) Monitor UST/liner space (F) Monitor dbl wall tank space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/13/2020 | 10/13/2021 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 10/13/2019 | 10/13/2020 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 11/01/2018 | 10/13/2019 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 05/06/2025 | Major Out of Compliance | SHANBERG_VJ_1 | 1/0 | Routine Compliance | ||||||
Issue Document | 05/06/2025 | Satisfied | SHANBERG_VJ_1 | Routine Compliance | |||||||
Letter | 05/06/2025 | Satisfied | SHANBERG_VJ_1 | Compliance Assistance | |||||||
Enforcement Referral | 08/17/2021 | Accepted | TRETHEWEY_MB_1 | Enforcement | |||||||
Electronic Communication | 08/13/2021 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Issue Document | 03/25/2021 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Letter | 03/25/2021 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Site Inspection | 03/25/2021 | Major Out of Compliance | TRETHEWEY_MB_1 | 1/0 | Routine Compliance | ||||||
Record Document | 05/29/2019 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Issue Document | 05/29/2019 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Letter | 12/31/2018 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Site Inspection | 12/31/2018 | Major Out of Compliance | TRETHEWEY_MB_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/01/2025 | 7003 | Minor | 1.3 Registration fees not paid (not receiving fuel). | Immediately submit registration fee to receive placard and submit photos of the placard properly displayed to Manatee County NRD. | |||||||
05/01/2025 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Submit correct registration to FDEP. | |||||||
05/01/2025 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Submit the completed appropriate part(s) of Form 62-761.900(3) for the policy period 10/13/2021- current to Manatee County NRD to demonstrate proof of financial responsibility. | |||||||
05/01/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Conduct and record overfill device operability testing and send documentation to Manatee County NRD for review. | |||||||
05/01/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Submit 05/2025 and 06/2025 logs to Manatee County NRD for review. | |||||||
05/01/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Conduct and record release detection operability testing and send documentation to Manatee County NRD for review. | |||||||
03/25/2021 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Immediately begin documenting monthly visual inspections. Visual inspections must include condition of tank, equipment, piping and the interstitial. Ensure that release detection is performed at least once a month not exceeding 35 days apart. Provide Manatee County PNRD with copies of the next two months records for review. | |||||||
No Discharges Found |