Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9816725 | Latitude | 27° 55' 11.4039 | ||||||||
Name |
EAST BAY REHABILITATION CENTER 4470 E BAY DR |
Longitude | 82° 44' 26.9915 | ||||||||
CLEARWATER, FL 33764-5772 | LL Method | DPHO | |||||||||
Contact | Administrator | LL Status | REVIEWED | ||||||||
Phone | (727) 530-7100 | Status Date | 05/22/2020 | ||||||||
Account Owner Information | |||||||||||
Name | PINELLAS III HEALTHCARE LTD., (L.P.) 709 S. HARBOR CITY BLVD. Clearwater, FL 33764-5772 |
Effective Date | 12/17/2018 | ||||||||
Contact | Administrator | ||||||||||
Phone | (727) 530-7100 | ||||||||||
ADMINISTRATOR@EASTBAYREHAB.COM | |||||||||||
Placard # / Date | 686501 - 06/11/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | PINELLAS III HEALTHCARE LTD., (L.P.) 709 S. HARBOR CITY BLVD. Clearwater, FL 33764-5772 |
Effective Date | 12/17/2018 | ||||||||
Contact | Administrator | ||||||||||
Phone | (727) 530-7100 | ||||||||||
ADMINISTRATOR@EASTBAYREHAB.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
AST-1 | 1000 | Emerg Generator Diesel (G) | 08/06/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket (N) Flow shut-Off (P) Level gauges/alarms (R) Double wall - tank jacket |
(A) Abv, no soil contact (B) Steel/galvanized metal (M) Double wall - pipe jacket |
(4) Visual inspect dispenser liners (6) External piping monitoring (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
AST-2 | 2000 | Emerg Generator Diesel (G) | 10/01/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(M) Spill containment bucket (R) Double wall - tank jacket (X) Concrete |
(A) Abv, no soil contact (B) Steel/galvanized metal (M) Double wall - pipe jacket |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (6) External piping monitoring (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 01/31/2021 | 01/31/2025 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 12/12/2020 | 12/12/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Tracking | 02/04/2025 | Closed Without Enforcement | BROCK_J | Enforcement | |||||||
Document Management | 01/17/2025 | Satisfied | HERNANDEZ_EMC | Enforcement | |||||||
Enforcement Referral | 01/07/2025 | Accepted | MUSLIC_A_1 | Enforcement | |||||||
Record Document | 11/13/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Electronic Communication | 10/23/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Site Inspection | 10/23/2024 | Major Out of Compliance | MUSLIC_A_1 | 2/0 | Routine Compliance | ||||||
Electronic Communication | 09/16/2024 | Satisfied | MUSLIC_A_1 | Routine Compliance | |||||||
Letter | 05/14/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 05/13/2021 | Major Out of Compliance | STRAUSS_RH_1 | 2/0 | Routine Compliance | ||||||
Electronic Communication | 05/06/2021 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 05/12/2020 | Satisfied | PACELKO_A | Enforcement | |||||||
Enforcement Referral | 03/13/2020 | Accepted | STRAUSS_RH_1 | Enforcement | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 03/03/2020 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 12/03/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 12/03/2019 | Major Out of Compliance | STRAUSS_RH_1 | 2/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/23/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Submit annual operability test results of primary overfill protection devices (pump shutoff level sensor for 1k gal tank and Morrison 818 Clock Gauge for 2k gal tank) from October 2021 to present or acknowledge that they are unavailable. If testing was not performed, complete overfill protection device tests and submit test results to this office. | |||||||
10/23/2024 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Submit monthly visual inspection records from September 2021 to July 2022 or acknowledge that they are unavailable. | |||||||
10/23/2024 | 7094 | Minor | 1.13 Permanent records not available within 5 working days notice. | Submit financial responsibility and testing records or acknowledge that they are not available. | |||||||
10/23/2024 | 7095 | Minor | 1.14 Records requiring 3 year documentation period not kept by facility. | Submit past 3 years of financial responsibility, monthly visual inspection, and testing records or acknowledge that they are unavailable. | |||||||
10/23/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Submit annual operability test results of release detection devices (rupture basin sensor for AST-1 and Krueger Tank Gauge for AST-2) from October 2021 to present or acknowledge that they are not available. If the testing was not performed annually, as required, complete release detection device test and submit test results to this office. | |||||||
05/13/2021 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Please provide current test results and ensure these release detection devices are tested annually at intervals not exceeding 12 months | |||||||
05/13/2021 | 5144 | Minor | 1.7 Records requiring 3 year documentation period not kept by facility. | Please ensure all required records are kept for a minimum period of 3 years | |||||||
05/13/2021 | 5143 | Minor | 1.6 Required records not available within 5 working days notice. | Please ensure all required records are available within 5 days notice | |||||||
05/13/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Please provide current test results for these overfill protection devices and ensure they are tested annually at intervals not exceeding 12 months; please provide markings and signage for the Morrison 818 clock gauge visible from the 2000-gal tank's fill port to indicate the 90% full level not to be exceeded when filling the tank | |||||||
05/13/2021 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Please provide all records avaialble for this period and ensure the tanks are inspected and the results recorded on a monthly basis no more than 35 days apart | |||||||
No Discharges Found |