Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9816962 | Latitude | 28° 7' 2.6381 | ||||||||
Name |
ADDINGTON PLACE OF EAST LAKE 1755 E LAKE RD |
Longitude | 82° 41' 37.0042 | ||||||||
TARPON SPRINGS, FL 34688 | LL Method | DPHO | |||||||||
Contact | CARIE SARGENT | LL Status | REVIEWED | ||||||||
Phone | (727) 943-8878 | Status Date | 06/28/2019 | ||||||||
Account Owner Information | |||||||||||
Name | HEALTH CARE TRUST INC 405 PARK AVE NEW YORK, NY 10022 |
Effective Date | 04/05/2019 | ||||||||
Contact | PATRICK COLLINS | ||||||||||
Phone | (760) 688-4104 | ||||||||||
PCOLLINS@AR-GLOBAL.COM | |||||||||||
Placard # / Date | 617801 - 07/08/2021 | ||||||||||
Property Owner Information | |||||||||||
Name | HEALTH CARE TRUST INC 405 PARK AVE NEW YORK, NY 10022 |
Effective Date | 04/05/2019 | ||||||||
Contact | PATRICK COLLINS | ||||||||||
Phone | (760) 688-4104 | ||||||||||
PCOLLINS@AR-GLOBAL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2802 | Emerg Generator Diesel (G) | 05/01/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (N) Approved synthetic material |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 11/08/2020 | 11/08/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 06/10/2019 | 06/10/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Record Document | 02/07/2025 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Record Document | 01/30/2025 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Letter | 01/17/2025 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Site Inspection | 01/17/2025 | Major Out of Compliance | MUSLIC_A_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 12/30/2024 | Satisfied | MUSLIC_A_1 | Routine Compliance | |||||||
Letter | 05/10/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 05/10/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 04/30/2021 | Minor Out of Compliance | STRAUSS_RH_1 | 1/0 | Routine Compliance | ||||||
Record Document | 04/30/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Letter | 04/30/2021 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 04/20/2021 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 06/28/2019 | Satisfied | STRAUSS_RH_1 | Installation | |||||||
Site Inspection | 06/28/2019 | In Compliance | STRAUSS_RH_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/17/2025 | 7125 | SNC-A | 1.17 Owner, operator, or supplier deposited motor fuel into storage tank without current valid registration placard. | Stop depositing fuel into the storage tank until the tank is properly registered and the current placard is received. | |||||||
01/17/2025 | 7095 | Minor | 1.14 Records requiring 3 year documentation period not kept by facility. | Submit financial responsibility, monthly visual inspection, and testing records that were unavailable or acknowledge that they are unavailable. | |||||||
01/17/2025 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Submit financial responsibility records from 11/8/2021 to present to this office. This will include insurance policies and relevant DEP forms. | |||||||
01/17/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Submit annual operability test results of rupture basin sensor from April 2022, 2023, and 2024 or acknowledge that they are not available. If the testing was not performed annually, as required, complete release detection device test and submit test results to this office. | |||||||
01/17/2025 | 7003 | Minor | 1.3 Registration fees not paid (not receiving fuel). | Please pay all registration fees. | |||||||
01/17/2025 | 7011 | Minor | 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. | Submit financial responsibility records, including insurance policies and relevant State forms, from 11/8/2021 to present, to this office. | |||||||
01/17/2025 | 7004 | Minor | 1.4 Placard not displayed (or available upon request). | Obtain current placard and display it in plain view in the facility. Submit current placard to this office. | |||||||
01/17/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Submit annual operability test results of Rochester tank gauge for years 2022, 2023, and 2024 or acknowledge that they are unavailable. If testing was not performed, complete overfill protection device test and submit test results to this office. | |||||||
01/17/2025 | 7094 | Minor | 1.13 Permanent records not available within 5 working days notice. | Submit placard, financial responsibility, monthly visual inspection, and testing records that were missing or acknowledge that they are unavailable. | |||||||
No Discharges Found |