District | Northwest | Type | Fuel user/Non-retail | ||||||||
County | Leon | Status | OPEN | ||||||||
ID | 9817082 | Latitude | 30° 25' 27.5847 | ||||||||
Name |
DXC TECHNOLOGY SERVICES LLC 2562 EXECUTIVE CIR |
Longitude | 84° 14' 5.636 | ||||||||
TALLAHASSEE, FL 32301 | LL Method | DPHO | |||||||||
Contact | ROGER MARTINEZ | LL Status | REVIEWED | ||||||||
Phone | (469) 990-6085 | Status Date | 07/17/2019 | ||||||||
Account Owner Information | |||||||||||
Name | DXC TECHNOLOGY SERVICES LLC 1840 OAK AVE, SU#300 EVANSTON, IL 60201 |
Effective Date | 05/22/2019 | ||||||||
Contact | JAMES MURPHY | ||||||||||
Phone | (404) 774-3138 | ||||||||||
JWMURPHY@DXC.COM | |||||||||||
Placard # / Date | 705890 - 05/16/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | DRA CRT TALLAHASSEE CTR 1311 Executive Center Dr Tallahassee, FL 32301-5027 |
Effective Date | 05/22/2019 | ||||||||
Contact | DERRICK WILLIAMS | ||||||||||
Phone | (850) 877-3151 | ||||||||||
RDORANJR@AUTOMATED-HEALTH.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2562-0 | 2130 | Emerg Generator Diesel (G) | 05/01/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Q) Visual inspection of ASTs | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
SURETY BOND | 05/29/2019 | 05/29/2020 | ZURICH AMERICAN INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 02/28/2025 | Satisfied | MERRITT_S | Enforcement | |||||||
Electronic Communication | 02/25/2025 | Satisfied | MERRITT_S | Enforcement | |||||||
Enforcement Referral | 11/08/2024 | Accepted | HATCHER_JD_1 | Enforcement | |||||||
Electronic Communication | 10/30/2024 | Satisfied | PROFFITT_B | Routine Compliance | |||||||
Site Inspection | 10/29/2024 | Major Out of Compliance | HATCHER_JD_1 | 1/0 | Routine Compliance | ||||||
Letter | 09/30/2024 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/29/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide any testing for overfill device that may have been perfomed | |||||||
10/29/2024 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Storage tank system must be visually inspected and documented each month not to exceed a 35 day period between inspections. | |||||||
10/29/2024 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide current proof of FR for Storage Tank System | |||||||
10/29/2024 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide any testing that may have been performed and monthly visuals need to be performed and documented | |||||||
10/29/2024 | 7005 | Minor | 1.5 Notification of installation, closure, or change in service status not received in required timeframes. | Notification before install must be provided. | |||||||
10/29/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Release detection equipment must be tested annually. Provide any testing that may have been performed | |||||||
10/29/2024 | 7003 | Minor | 1.3 Registration fees not paid (not receiving fuel). | No current placard. Put AST out of service or update placard. | |||||||
09/30/2024 | 7011 | Minor | 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. | Provide current proof of insurance for storage tank system | |||||||
09/30/2024 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Submit registration to show current owner, contact info and local contact | |||||||