Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9817110 | Latitude | 27° 51' 24.7901 | ||||||||
Name |
BAYSIDE TERRACE 9381 US HWY 19 N |
Longitude | 82° 41' 39.3012 | ||||||||
PINELLAS PARK, FL 33782-5410 | LL Method | DPHO | |||||||||
Contact | STEVEN BOHLEN | LL Status | REVIEWED | ||||||||
Phone | (727) 647-2800 | Status Date | 05/22/2020 | ||||||||
Account Owner Information | |||||||||||
Name | BAYSIDE TERRACE SENIOR LIVING LLC 5801 ULMERTON RD #200 CLEARWATER, FL 33760 |
Effective Date | 02/08/2023 | ||||||||
Contact | STEVEN BOHLEN | ||||||||||
Phone | (727) 683-1200 | ||||||||||
SBOHLEN@TJMPROPERTIES.US | |||||||||||
Placard # / Date | 686651 - 06/11/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | BAYSIDE TERRACE SENIOR LIVING LLC 5801 ULMERTON RD #200 CLEARWATER, FL 33760 |
Effective Date | 02/08/2023 | ||||||||
Contact | STEVEN BOHLEN | ||||||||||
Phone | (727) 683-1200 | ||||||||||
SBOHLEN@TJMPROPERTIES.US | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2060 | Emerg Generator Diesel (G) | 06/01/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket |
(A) Abv, no soil contact (D) External protective coating (I) Suction piping system (X) No piping associated w/tank |
(8) Manually sampled wells (F) Monitor dbl wall tank space (R) Monitor tank bottom space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/06/2025 | 02/06/2026 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 02/06/2024 | 02/06/2025 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/13/2016 | 10/13/2019 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 02/24/2025 | Major Out of Compliance | PUHR_NM_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 02/24/2025 | Satisfied | PUHR_NM_1 | Routine Compliance | |||||||
Letter | 02/24/2025 | Satisfied | PUHR_NM_1 | Compliance Assistance | |||||||
Electronic Communication | 01/09/2025 | Satisfied | REIS_A | Enforcement | |||||||
Letter | 07/15/2024 | Satisfied | REIS_A | Enforcement | |||||||
Enforcement Referral | 06/09/2023 | Accepted | COLSON_NJ_1 | Enforcement | |||||||
Electronic Communication | 04/24/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 04/24/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Record Document | 03/31/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 06/04/2021 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 05/27/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 05/27/2021 | Major Out of Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 07/09/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 07/09/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 06/28/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 06/28/2019 | Minor Out of Compliance | COLSON_NJ_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/24/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | *Submit two new consecutive months of tank system visual inspections including an alarm history. The alarm history needs to include an explanation and resolution. | |||||||
02/24/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | *Submit the missing records if found; otherwise, having testing performed and submit results to this office for review. | |||||||
02/24/2025 | 7004 | Minor | 1.4 Placard not displayed (or available upon request). | *Display the current registration placard at the facility. Provide a copy of the placard to document this. | |||||||
02/24/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | *Submit the missing records if found; otherwise, having testing performed and submit results to this office for review. | |||||||
05/27/2021 | 5102 | Minor | 3.3 Shop fabricated storage tank system release detection devices not tested annually. | Be sure to have the required testing performed within 12 months of the last test date. Submit current test results for the rupture basin alarm system. | |||||||
05/27/2021 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Submit FR (tank insurance) documentation since 10/13/2019. | |||||||
05/27/2021 | 5012 | Minor | 1.7 Incomplete documentation demonstrating financial responsibility. | Submit FR documentation since 10/13/2019 on the appropriate Part D and Part P forms. | |||||||
05/27/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Be sure to have the required testing performed within 12 months of the last test date. Submit current test results for the primary overfill protection device. | |||||||
No Discharges Found |