DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 9817110   Latitude    27° 51' 24.7901
 
Name BAYSIDE TERRACE
9381 US HWY 19 N
Longitude    82° 41' 39.3012
  PINELLAS PARK, FL 33782-5410 LL Method    DPHO
 
Contact STEVEN BOHLEN   LL Status    REVIEWED
 
Phone (727) 647-2800   Status Date    05/22/2020
 
Account Owner Information
 
Name BAYSIDE TERRACE SENIOR LIVING LLC
5801 ULMERTON RD #200
CLEARWATER, FL 33760
Effective Date    02/08/2023
 
Contact STEVEN BOHLEN
 
Phone (727) 683-1200
 
Email SBOHLEN@TJMPROPERTIES.US
  Placard # / Date    686651 - 06/11/2024
Property Owner Information
 
Name BAYSIDE TERRACE SENIOR LIVING LLC
5801 ULMERTON RD #200
CLEARWATER, FL 33760
Effective Date    02/08/2023
 
Contact STEVEN BOHLEN
 
Phone (727) 683-1200
 
Email SBOHLEN@TJMPROPERTIES.US
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 2060 Emerg Generator Diesel (G) 06/01/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
  (A) Abv, no soil contact
(D) External protective coating
(I) Suction piping system
(X) No piping associated w/tank
(8) Manually sampled wells
(F) Monitor dbl wall tank space
(R) Monitor tank bottom space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   02/06/2025 02/06/2026 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   02/06/2024 02/06/2025 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   10/13/2016 10/13/2019 ILLINOIS UNION INSURANCE COMPANY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 02/24/2025 Major Out of Compliance PUHR_NM_1 1/0 Routine Compliance
 
Electronic Communication 02/24/2025 Satisfied PUHR_NM_1 Routine Compliance
 
Letter 02/24/2025 Satisfied PUHR_NM_1 Compliance Assistance
 
Electronic Communication 01/09/2025 Satisfied REIS_A Enforcement
 
Letter 07/15/2024 Satisfied REIS_A Enforcement
 
Enforcement Referral 06/09/2023 Accepted COLSON_NJ_1 Enforcement
 
Electronic Communication 04/24/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 04/24/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 03/31/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 06/04/2021 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 05/27/2021 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 05/27/2021 Major Out of Compliance COLSON_NJ_1 1/0 Routine Compliance
 
Electronic Communication 07/09/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 07/09/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 06/28/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 06/28/2019 Minor Out of Compliance COLSON_NJ_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/24/2025 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. *Submit two new consecutive months of tank system visual inspections including an alarm history. The alarm history needs to include an explanation and resolution.
 
02/24/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, *Submit the missing records if found; otherwise, having testing performed and submit results to this office for review.
 
02/24/2025 7004 Minor 1.4 Placard not displayed (or available upon request). *Display the current registration placard at the facility. Provide a copy of the placard to document this.
 
02/24/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. *Submit the missing records if found; otherwise, having testing performed and submit results to this office for review.
 
05/27/2021 5102 Minor 3.3 Shop fabricated storage tank system release detection devices not tested annually. Be sure to have the required testing performed within 12 months of the last test date. Submit current test results for the rupture basin alarm system.
 
05/27/2021 5011 SNC-B 1.6 Failure to maintain and demonstrate financial responsibility. Submit FR (tank insurance) documentation since 10/13/2019.
 
05/27/2021 5012 Minor 1.7 Incomplete documentation demonstrating financial responsibility. Submit FR documentation since 10/13/2019 on the appropriate Part D and Part P forms.
 
05/27/2021 5042 SNC-B 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. Be sure to have the required testing performed within 12 months of the last test date. Submit current test results for the primary overfill protection device.
 
 
 
No Discharges Found