Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/23/2025 Last Data Refresh: 02/22/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Other Regulated Facility | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 9817238 | Latitude | 27° 53' 33.93 | ||||||||
Name |
TIERRA PINES 7380 ULMERTON RD |
Longitude | 82° 44' 23.4848 | ||||||||
LARGO, FL 33771-4512 | LL Method | DPHO | |||||||||
Contact | DOUG HOUDE | LL Status | REVIEWED | ||||||||
Phone | (813) 558-6521 | Status Date | 05/22/2020 | ||||||||
Account Owner Information | |||||||||||
Name | OPIS SENIOR SERVICES GROUP 10150 HIGHLAND MANOR DR Tampa, FL 33610-9713 |
Effective Date | 07/11/2019 | ||||||||
Contact | LEROY ANDERSON | ||||||||||
Phone | (813) 558-6521 | ||||||||||
ISLANDLAKE@MYSTAMPLI.COM | |||||||||||
Placard # / Date | 687573 - 06/13/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | OPIS SENIOR SERVICES GROUP 10150 HIGHLAND MANOR DR Tampa, FL 33610-9713 |
Effective Date | 07/11/2019 | ||||||||
Contact | LEROY ANDERSON | ||||||||||
Phone | (813) 558-6521 | ||||||||||
ISLANDLAKE@MYSTAMPLI.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1708 | Generator/Pump Diesel (H) | 06/05/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (N) Approved synthetic material |
(F) Monitor dbl wall tank space (I) Not required (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 06/26/2020 | 06/26/2021 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/26/2019 | 06/26/2020 | NAUTILUS INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 02/18/2025 | Major Out of Compliance | PUHR_NM_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 02/18/2025 | Satisfied | PUHR_NM_1 | Compliance Assistance | |||||||
Electronic Communication | 02/17/2025 | Satisfied | PUHR_NM_1 | Routine Compliance | |||||||
Site Inspection | 05/13/2021 | In Compliance | STRAUSS_RH_1 | 1/0 | Routine Compliance | ||||||
Letter | 05/13/2021 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 05/06/2021 | Satisfied | STRAUSS_RH_1 | Installation | |||||||
Electronic Communication | 05/06/2021 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Site Inspection | 09/19/2019 | In Compliance | STRAUSS_RH_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/18/2025 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | If no records are available, please have testing completed and submit new records. | |||||||
02/18/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Submit the missing records if found. If none are available, please submit the next two consecutive months of inspections including a monthly alarm history with an explanation/resolution for any alarms. | |||||||
02/18/2025 | 7004 | Minor | 1.4 Placard not displayed (or available upon request). | *Display the current registration placard at the facility. | |||||||
02/18/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | If no records are available, please have testing completed and submit new records. | |||||||
02/18/2025 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Submit the missing FR documentation. | |||||||
No Discharges Found |