DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Fuel user/Non-retail
 
County Seminole   Status    OPEN
 
ID 9817247   Latitude    28° 42' 1.9116
 
Name VCARE HEALTH CENTER LLC
480 E CHURCH AVE
Longitude    81° 20' 19.6548
  LONGWOOD, FL 32750-4290 LL Method    DPHO
 
Contact JAY ALCORDO   LL Status    REVIEWED
 
Phone (407) 731-2845   Status Date    07/17/2019
 
Account Owner Information
 
Name VCARE HEALTH CENTER LLC
480 EAST CHURCH AVE
LONGWOOD, FL 32750
Effective Date    12/01/2024
 
Contact JAY ALCORDO
 
Phone (407) 731-2845
 
Email VCARELONGWOOD@GMAIL.COM
  Placard # / Date    705800 - 05/06/2025
Property Owner Information
 
Name VCARE HEALTH CENTER LLC
480 EAST CHURCH AVE
LONGWOOD, FL 32750
Effective Date    12/01/2024
 
Contact JAY ALCORDO
 
Phone (407) 731-2845
 
Email VCARELONGWOOD@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
20252 1750 Generator/Pump Diesel (H) 06/17/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(P) Level gauges/alarms
(Q) DEP approved protection
(R) Double wall - tank jacket
(S) DEP approved containment
(W) Built on supports
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(M) Double wall - pipe jacket
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(Z) DEP approved monitoring
 
 
No Insurance Documents Found
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Meeting 10/27/2022 Satisfied DALTON_K Enforcement
 
Letter 08/01/2022 Satisfied DALTON_K Enforcement
 
Enforcement Referral 04/28/2022 Accepted BECKER_GT_1 Enforcement
 
Electronic Communication 04/28/2022 Satisfied DALTON_K Enforcement
 
Issue Document 04/19/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Issue Document 04/01/2022 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 03/30/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 03/29/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 02/21/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Record Document 02/21/2022 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Site Inspection 02/02/2022 Major Out of Compliance KIDDER_MS_1 1/0 Routine Compliance
 
Letter 02/02/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Meeting 02/01/2022 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 01/04/2022 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 12/06/2021 Satisfied KIDDER_MS_1 Routine Compliance
 
Phone Conversation 12/06/2021 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 02/01/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/01/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/01/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Record Document 01/30/2021 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Letter 01/29/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 01/29/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Site Inspection 01/29/2021 Major Out of Compliance BECKER_GT_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/27/2022 7102 SNC-B 3.13 Storage tank system closure requirements not met. Conducting a Closure Integrity Evaluation for shop fabricated storage tank systems as defined in subsection 62-762.201(8), F.A.C. and completing the Closure Integrity Evaluation Report Form for ASTs 62-762.901(7) (Closure Integrity Report), incorporated by reference in paragraph 62-762.411(2)(c), F.A.C. Removing all liquids and accumulated sludges. The removal and disposal of all liquids and accumulated sludges may be required according to other federal, state, and local requirements. Removing or disconnecting and capping all integral piping; Removing and disposing of a storage tank, or in-place closure by rendering the storage tank free of regulated substances and vapors at the time of closure to prevent hazardous explosive conditions, by maintaining the storage tank to prevent future explosive conditions, and by protecting the storage tank from flotation in accordance with Chapter 22 of NFPA 30, 2018 Edition, incorporated by reference in paragraph 62-762.201(36)(a), F.A.C.
 
02/21/2022 7003 Minor 1.3 Registration fees not paid (not receiving fuel). Please pay registration fees.
 
02/01/2022 7001 Minor 1.1 No reasonable access provided. Please contact Matthew Kidder at (321) 239-4050 or matthew.kidder@ocfl.net in order to schedule a re-inspection.
 
01/29/2021 5034 SNC-B 3.15 Storage tank system not installed according to reference guidelines for shop fabricated tank systems. Perform all required onsite testing of the installed tank components or provide documentation of onsite testing to OCEPD. The following tests/documentation is required: -Initial operability test of the interstitial (rupture basin) leak detection sensor/alarm; -Initial operability test of a designated overfill prevention system: high level alarms/sensor.
 
01/29/2021 5027 SNC-B 3.8 Integrity test not conducted before placing into service for shop fabricated tank systems. Perform an onsite interstitial integrity test on the AST's interstitial (rupture basin) space, per manufacturer's specifications. Perform a hydrostatic test on the AST's fill port spill containment. The hydrostatic test shall be performed according to the 'Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment', PEI/RP1200-12, 2012 Edition. Provide documentation of testing to OCEPD.
 
01/29/2021 5003 Minor 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. Complete and provide to OCEPD a DEP storage tank registration form to document the current facility owner/contact information.
 
01/29/2021 5168 Minor 1.2 Storage tank system equipment not registered with the Department. Provide to OCEPD the DEP EQ #s for the AST's leak detection sensor and high fuel level sensor.
 
01/29/2021 5011 SNC-B 1.6 Failure to maintain and demonstrate financial responsibility. Provide to OCEPD the required FR documentation along with the required Florida Certificates.
 
 
 
No Discharges Found