Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 03/19/2025 Last Data Refresh: 03/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Manatee | Status | OPEN | ||||||||
ID | 9818105 | Latitude | 27° 23' 3.0595 | ||||||||
Name |
DAKIN NATURAL SOILS 28510 SR 70, FL |
Longitude | 82° 14' 58.5874 | ||||||||
MYAKKA CITY, FL 34251 | LL Method | DPHO | |||||||||
Contact | SCOTT CAGLE | LL Status | REVIEWED | ||||||||
Phone | (941) 219-3076 | Status Date | 12/08/2020 | ||||||||
Account Owner Information | |||||||||||
Name | DAKIN NATURAL SOILS 30771 BETTS RD MYAKKA CITY, FL 34251 |
Effective Date | 12/01/2019 | ||||||||
Contact | SCOTT CAGLE / JERRY DAKIN (941) 650-0307 | ||||||||||
Phone | (941) 893-9181 | ||||||||||
SCOTT.DDF@GMAIL.COM | |||||||||||
Placard # / Date | 683419 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | DAKIN NATURAL SOILS 30771 BETTS RD MYAKKA CITY, FL 34251 |
Effective Date | 12/01/2012 | ||||||||
Contact | SCOTT CAGLE / JERRY DAKIN (941) 650-0307 | ||||||||||
Phone | (941) 893-9181 | ||||||||||
SCOTT.DDF@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 7000 | Vehicular Diesel (D) | 12/01/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (S) DEP approved containment |
(Q) Visual inspection of ASTs | ||||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
NONE | |||||||||||
INSURANCE | 09/11/2021 | 09/11/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/11/2020 | 09/11/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 05/13/2022 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Electronic Communication | 05/13/2022 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Site Inspection | 05/13/2022 | Major Out of Compliance | TRETHEWEY_MB_1 | 1/0 | Routine Compliance | ||||||
Issue Document | 05/13/2022 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Letter | 05/13/2022 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Electronic Communication | 05/13/2022 | Satisfied | TRETHEWEY_MB_1 | Routine Compliance | |||||||
Record Document | 10/02/2020 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Enforcement Referral | 09/24/2020 | Accepted | TRETHEWEY_MB_1 | Enforcement | |||||||
Letter | 09/23/2020 | Satisfied | TRETHEWEY_MB_1 | Non-Compliance | |||||||
Site Inspection | 09/23/2020 | Major Out of Compliance | TRETHEWEY_MB_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/13/2022 | 7030 | Minor | 3.6 Exterior coatings not protected from external corrosion, deterioration or degradation. | Remove any surface corrosion and repaint affected areas. | |||||||
09/23/2020 | 5009 | Minor | 1.4 Notification of an incident not received in a timely manner. | Ensure that INF is submitted within 72 hours of discovery. | |||||||
09/23/2020 | 5044 | Minor | 3.24 Fillbox covers not marked according to requirements for shop fabricated tank systems. | Immediately provide signage at the fill with product ID. | |||||||
09/23/2020 | 5144 | Minor | 1.7 Records requiring 3 year documentation period not kept by facility. | Provide Manatee County PNRD with required records. | |||||||
09/23/2020 | 5052 | Minor | 3.31 Relocated shop fabricated storage tanks do not meet requirements. | Ensure that tanks are tested prior to the introduction of fuel after relocation. | |||||||
09/23/2020 | 5005 | SNC-B | 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. | Ensure that a current placard is displayed prior to the delivery of fuel. | |||||||
09/23/2020 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Immediately begin documenting release detection records. Ensure that release detection is performed and documented at least once a month not exceeding 35 days apart. | |||||||
09/23/2020 | 5047 | SNC-B | 3.26 Dispensers not installed with a dispenser sump meeting performance requirements for shop fabricated tank systems. | Immediately relocate the pump within containment or install over impervious surface. | |||||||
09/23/2020 | 5017 | SNC-B | 1.8 Discharge not reported with 24-hours, or by next business day. | Ensure that a DRF is submitted within 24 hours of discovery. | |||||||
09/23/2020 | 5018 | Minor | 1.3 Analytical results confirming a discharge not submitted timely. | Immediately have analytical tests performed in the stained areas. | |||||||
No Discharges Found |