DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Manatee   Status    OPEN
 
ID 9818105   Latitude    27° 23' 3.0595
 
Name DAKIN NATURAL SOILS
28510 SR 70, FL
Longitude    82° 14' 58.5874
  MYAKKA CITY, FL 34251 LL Method    DPHO
 
Contact SCOTT CAGLE   LL Status    REVIEWED
 
Phone (941) 219-3076   Status Date    12/08/2020
 
Account Owner Information
 
Name DAKIN NATURAL SOILS
30771 BETTS RD
MYAKKA CITY, FL 34251
Effective Date    12/01/2019
 
Contact SCOTT CAGLE / JERRY DAKIN (941) 650-0307
 
Phone (941) 893-9181
 
Email SCOTT.DDF@GMAIL.COM
  Placard # / Date    683419 - 06/05/2024
Property Owner Information
 
Name DAKIN NATURAL SOILS
30771 BETTS RD
MYAKKA CITY, FL 34251
Effective Date    12/01/2012
 
Contact SCOTT CAGLE / JERRY DAKIN (941) 650-0307
 
Phone (941) 893-9181
 
Email SCOTT.DDF@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 7000 Vehicular Diesel (D) 12/01/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(S) DEP approved containment
  (Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
NONE  
INSURANCE   09/11/2021 09/11/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   09/11/2020 09/11/2021 COMMERCE & INDUSTRY INSURANCE CO
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 05/13/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Electronic Communication 05/13/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 05/13/2022 Major Out of Compliance TRETHEWEY_MB_1 1/0 Routine Compliance
 
Issue Document 05/13/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Letter 05/13/2022 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Electronic Communication 05/13/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Record Document 10/02/2020 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Enforcement Referral 09/24/2020 Accepted TRETHEWEY_MB_1 Enforcement
 
Letter 09/23/2020 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 09/23/2020 Major Out of Compliance TRETHEWEY_MB_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/13/2022 7030 Minor 3.6 Exterior coatings not protected from external corrosion, deterioration or degradation. Remove any surface corrosion and repaint affected areas.
 
09/23/2020 5009 Minor 1.4 Notification of an incident not received in a timely manner. Ensure that INF is submitted within 72 hours of discovery.
 
09/23/2020 5044 Minor 3.24 Fillbox covers not marked according to requirements for shop fabricated tank systems. Immediately provide signage at the fill with product ID.
 
09/23/2020 5144 Minor 1.7 Records requiring 3 year documentation period not kept by facility. Provide Manatee County PNRD with required records.
 
09/23/2020 5052 Minor 3.31 Relocated shop fabricated storage tanks do not meet requirements. Ensure that tanks are tested prior to the introduction of fuel after relocation.
 
09/23/2020 5005 SNC-B 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. Ensure that a current placard is displayed prior to the delivery of fuel.
 
09/23/2020 5094 SNC-B 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. Immediately begin documenting release detection records. Ensure that release detection is performed and documented at least once a month not exceeding 35 days apart.
 
09/23/2020 5047 SNC-B 3.26 Dispensers not installed with a dispenser sump meeting performance requirements for shop fabricated tank systems. Immediately relocate the pump within containment or install over impervious surface.
 
09/23/2020 5017 SNC-B 1.8 Discharge not reported with 24-hours, or by next business day. Ensure that a DRF is submitted within 24 hours of discovery.
 
09/23/2020 5018 Minor 1.3 Analytical results confirming a discharge not submitted timely. Immediately have analytical tests performed in the stained areas.
 
 
 
No Discharges Found