Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Manatee | Status | OPEN | ||||||||
ID | 9818466 | Latitude | 27° 31' 42.3062 | ||||||||
Name |
COAST CONCRETE COMPANY LLC 2825 17TH ST E |
Longitude | 82° 32' 6.2909 | ||||||||
ELLENTON, FL 34222 | LL Method | DPHO | |||||||||
Contact | RICK CRIPE | LL Status | REVIEWED | ||||||||
Phone | (941) 698-4923 | Status Date | 05/11/2021 | ||||||||
Account Owner Information | |||||||||||
Name | COAST CONCRETE COMPANY LLC 5200 LINWOOD RD PLACIDA, FL 33946 |
Effective Date | 04/02/2021 | ||||||||
Contact | RICK CRIPE | ||||||||||
Phone | (941) 698-4923 | ||||||||||
MPITTMAN@COASTCONCRETE.NET | |||||||||||
Placard # / Date | 683482 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | COAST CONCRETE COMPANY LLC 5200 LINWOOD RD PLACIDA, FL 33946 |
Effective Date | 04/02/2021 | ||||||||
Contact | RICK CRIPE | ||||||||||
Phone | (941) 698-4923 | ||||||||||
MPITTMAN@COASTCONCRETE.NET | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Vehicular Diesel (D) | 03/01/2021 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (N) Flow shut-Off |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/30/2024 | 10/30/2025 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 09/16/2021 | 09/16/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 04/01/2025 | Satisfied | SHANBERG_VJ_1 | Compliance Assistance | |||||||
Site Inspection | 03/31/2025 | Major Out of Compliance | SHANBERG_VJ_1 | 1/0 | Routine Compliance | ||||||
Enforcement Referral | 10/20/2022 | Accepted | TRETHEWEY_MB_1 | Enforcement | |||||||
Letter | 06/29/2022 | Satisfied | TRETHEWEY_MB_1 | Compliance Assistance | |||||||
Site Inspection | 06/29/2022 | Minor Out of Compliance | TRETHEWEY_MB_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/31/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Submit 04/2025 and 05/2025 log to Manatee County NRD for review | |||||||
06/29/2022 | 7098 | Minor | 1.16 Testing shall be up-to-date and indicate proper operation before adding regulated substances to the storage tank system or returning system to service. | Provide Manatee County PNRD with copies of the required tests. | |||||||
06/29/2022 | 7110 | Minor | 1.16 Equipment not registered with DEP before installation or use. | Immediately provide Manatee County with exact location and former Facility ID this tank originated from. | |||||||
06/29/2022 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | Provide Manatee County PNRD with copies of the required test. | |||||||
No Discharges Found |